DESIGN OF RETAINING WALL FOR A MINOR BRIDGE
Bachelor of Technology
In
Civil Engineering
By
SIRIPURAM ANUSHA
(09241A0157)
M.BALAKOTESHWARI
(09241A0160)
R.SABITHA RAJ
(09241A0195)
A.SWETHA
(09241A01A7)
2012-2013
1
CERTIFICATE
This is to certify that the dissertation entitled DESIGN OF RETAINING WALL FOR A
MINOR BRIDGE is a bonafide project work done under the guidance of Mrs. C.LAVANYA ,
Assistant Professor in the Department Of Civil Engineering, GOKARAJU RANGARAJU
INSTITUTE OF ENGINEERING AND TECHNOLOGY, Hyderabad.
Project done by
Mrs.C.Lavanya
Guide
SIRIPURAM ANUSHA
(09241A0157)
M.BALAKOTESHWARI
(09241A0160)
R.SABITHA RAJ
(09241A0195)
A.SWETHA
(09241A01A7)
Prof.Dr.G.Venkata Ramana
HOD Civil Engineering
External Examiner
STUDENT DECLARATION
We hereby declare that the project entitled DESIGN OF RETAINING WALL FOR A MINOR
BRIDGE is the work done by us during the academic year 2012-13. This project report is
submitted in partial fulfillment of the requirements for the award of degree of bachelor of
technology in CIVIL ENGINEERING from JNTU, Hyderabad.
SIRIPURAM ANUSHA
(09241A0157)
M.BALAKOTESHWARI
(09241AO160)
R.SABITHA RAJ
(09241A0195)
A.SWETHA
(09241A01A7)
ACKNOWLEDGEMENT
Salutations to our beloved and highly esteemed institute Gokaraju Rangaraju Institute of
Engineering and Technology for having well qualified staff and labs furnished with necessary
equipment and computers.
Firstly we would like to express our deep sense of gratitude towards Dr. G.Venkata Ramana,
Head of the Department, Civil Engineering for giving us the opportunity to do an industrial
oriented project work.
We would also like to thank our project guide, Mrs.C.Lavanya, Assistant Professor, Department
of Civil Engineering at Gokaraju Rangaraju Institute of Engineering and Technology for always
being available when we required her guidance.
Special thanks to all our team members for this team work and other friends for their support.
CONTENTS
PAGE NUMBER
1. Introduction
3. Site location
12
6. Retaining wall
13
13
7. Tests
17
7.1 Standard compaction test
17
25
34
42
43
43
48
49
49
50
52
52
52
53
9.4 Design
54
57
Existing section
58
Trial section 1
59
Trial section 2
64
Trial section 3
69
11. Conclusion
75
12. Bibliography
76
LIST OF FIGURES
Fig.3
Fig 4.1
Moorum soil
Fig. 5
13
Fig 6.1.1
14
Fig 6.1.2
15
Fig. 6.1.3
15
Fig. 6.1.4
Piling Wall
16
Fig. 6.1.5
16
Fig. 7.1.1
Fig. 7.1.2
Fig. 7.1.3
Fig.7.2.1
Fig. 7.2.2
Scraping
18
20
20
25
26
Fig. 7.2.3
Fig.7.2.4
Fig.7.2.5
Fig.7.2.6
Fig.7.3.1
Fig.7.3.2
Fig. 7.3.3
Fig.7.3.4
Fig. 7.3.5
Fig.7.3.6
Proving Ring
Sample Extractor
Cylindrical Mould
28
28
29
30
35
36
37
37
38
39
Fig. 8.1
42
Fig. 8.2.2
45
Fig. 8.2.3
Fig.9.3.1
Fig. 10.1
Fig. 10.2
Trial section1
48
53
58
59
Fig. 10.3
Trial Section2
64
Fig. 10.4
Trial section 3
69
Fig.10.5
74
LIST OF TABLES
Table No.1
Table No.2
Table No.3
22
31
40
Table No.5
60
Table No.6
65
Table No. 4
Table No.7
10
47
70
LIST OF GRAPHS
24
11
33
ABSTRACT
Structures which are used to hold back a soil mass are called retaining structures. Our
project is to design retaining wall for a minor bridge. As the metro rail project is running through
Miyapur, there is a need for the extension of 4 lane carriage way to 6 lane carriage way. But the
carriage way includes a minor bridge, which too has to be extended for facilitating the traffic
flow. Thus, this project focuses on the design of retaining wall for the modified section of the
minor bridge.
Retaining walls are the structures designed to restrain soil to unnatural slopes. They are
used to bound soils between two different elevations in areas of terrain possessing undesirable
slopes. They are also used in areas where the landscape needs to be shaped severely and
engineered for more specific purposes like hillside farming or roadway overpasses. They are also
used in bridge abutments and wing walls.
The design of structures like retaining wall requires the knowledge of the earth pressure
acting on the back of the wall because of the soil backfill in contact with it. Hence relation
between the earth pressure on the retaining wall and strains within a backfill is a prerequisite.
The project also includes the estimation of safe bearing capacity of soil and its properties, earth
pressure calculations and design criteria of a modified section of a retaining wall. The design
criteria includes: check for stability against sliding, overturning and bearing capacity.
12
1. INTRODUCTION
A soil mass is stable when the slope of the surface of the soil mass is flatter than the
safe slope. At some locations where the space is limited, it is not possible to provide flat slope
and the soil is to be retained at a slope steeper than the surface one. In such cases, a retaining
structure is required to provide lateral support to the soil mass. Retaining walls are relatively
rigid walls used for supporting the soil mass laterally so that the soil can be retained at different
levels on the two sides. Generally, the soil masses are vertical or nearly vertical behind the
retaining structure. Thus, a retaining wall maintains the soil at different elevations on its either
side. In the absence of a retaining wall, the soil on the higher side would have a tendency to slide
and may not remain stable. However for a minor bridge of span 15 m a retaining wall is
constructed without considering the slope factor but only the soil properties.
The project concentrates on the designing of a retaining wall located on National
Highway-9; Pune- Hyderabad via Miyapur. The road in this region is extended for two lanes,
from four lane road way to six lane road way to accommodate free traffic flow because of metro
railway construction process. The minor bridge located in this region is also to be extended.
Thus, our project is been cleared with the design of a retaining wall to this bridge on one side and
hence replicating it to remaining.
Structures which are used to hold back a soil mass are called retaining structures.
Retaining walls, sheet pile walls, crib walls, sheeting in excavations, basement walls, etc., are
examples of retaining structures. A retaining wall helps in maintaining the ground surface at
different elevations on either side of it. Without such a structure, the soil at higher elevation
would tend to move down till it acquires its natural, stable configuration. Consequently, the soil
that is retained at a slope steeper than it can sustain by virtue of its shearing strength, exerts a
force on the retaining wall. This force is called the earth pressure and the material that is retained
by the wall is referred to as backfill. The gravity retaining wall is the simplest type of retaining
wall along with other common types of retaining walls such as the cantilever, and the counterfort walls.
The design of structures like a retaining wall requires the knowledge of the earth
pressure acting on the back of the wall because of the soil backfill in contact with it.
13
The magnitude of earth pressure itself, on the other hand, is a function of the
magnitude and nature of the absolute and relative movements of the soil and the structure.
Problems such as these, where structure is in contact with the soil mass and the behavior of each
one is influenced by that of the other, are classed as soil-structure interaction problems. Often,
the earth pressures are statistically indeterminate and hence pose problems in evaluation. In some
cases, the desired accuracy in determination cannot be achieved. But knowledge of the
relationship between the earth pressure on the retaining wall and strains within a backfill is a
prerequisite for the solution of earth pressure problems.
The design of the retaining structure requires determination of the magnitude and line
of action of the lateral earth pressure. The magnitude of the lateral earth pressure depends upon a
number of factors, such as the mode of the movement of the wall, the flexibility of the wall, the
properties of the soil, and the drainage conditions. It is a soil-structure interaction problem, as the
earth pressure depends on the flexibility of the wall.
The design has been accomplished with few tests which we have done in the college
laboratory. The results extracted were used in the design. The site being in a hard rocky soil
strata, we got very high safe bearing capacity. Hence, two more sections apart from actual
section according to standard specifications were also evaluated for economic reasons with
increased safety factor.
The definition of minor bridge, retaining wall and their types, tests and tests results
with brief procedure were explained in this report in addition to the safe bearing capacity of the
ground, designed sections and their evaluations for safety conditions.
14
15
3. SITE LOCATION
The site is located opposite to Talkie Town, Miyapur on Pune-Hyderabad section of NH-9.
The figure here shows the existing minor bridge.
cc
Fig 3 Existing Minor Bridge
3.1 BRIDGE
A bridge is a structure built to span physical obstacles such as a body of water, valley, or road,
for the purpose of providing passage over the obstacle.In other words Bridge is a structure
having a length of above 6 m between the inner faces of dirt walls for carrying traffic or other
moving loads over a depression or obstruction such as channels,raods,railways etc. There are
16
many different designs that all serve unique purposes and apply to different situations. Bridges
can be categorized in several different ways. Common categories include the type of structural
elements used, by what they carry, whether they are fixed or movable, and by the materials used
and by the span of bridge..In this project we carried out work for designing of retaining wall for a
minor bridge.
3.2.3 CULVERT
Culverts are cross drainage structures having a total length upto 6m or less between the inner
faces of dirt walls or extreme vent way boundaries measured at right angles thereto. A large
number of culverts are needed for taking care of the streams crossing the railway lines. A culvert
is a cutting under or beside a road which allows water to drain, rather than pooling and making
road conditions hazardous.
17
3.3 SPECIFICATIONS
The work shall be carried out as per M.O.R.T & Hs (Ministry of Road Transport and
Highways)
The work will be governed by design considerations & specifications contained in IRC
codes of practice for roads/bridges.
The grading, size, quality of coarse aggregates shall be strictly as per Specifications for
Road and Bridge works M.O.R.T & Hs and relevant I.R.C codes.
The size, quality of aggregates and mixing etc for plain concrete and R.C.C works shall
be as per Specifications for Road and Bridge works and relevant I.S codes
18
19
capacity is the theoretical maximum pressure which can be supported without failure; allowable
bearing capacity is the ultimate bearing capacity multiplied by a factor of safety. Sometimes, on
soft soil sites, large settlements may occur under loaded foundations without actual shear failure
occurring; in such cases, the allowable bearing capacity is based on the maximum allowable
settlement. Terzaghis Bearing Capacity theory is used in this project to calculate safe bearing
capacity of soil which can be further used to evaluate stability analysis of retaining wall.
4.2.2. DRY DENSITY
This is one of the important strength parameters need to be calculated. It can be determined from
Standard Compaction Test. The safe and economic design of retaining wall depends on the dry
density of surrounding soil. Bearing capacity of soil in turn depends on dry density of the soil. If
the soil is not having sufficient dry density the structure built on it couldnt carry loads. To make
it strengthened soil is stabilized which will be expensive. Hence dry density of oil is the
important parameter for any structure. Dry density of soil can be achieved by Compaction.
Compaction is the process of increasing the density of the soil by packing the solid particles
closer together by reducing the volume of the air. The degree of compaction is measured in terms
of dry density, d. The dry density after compaction depends on;
type of soil
and depends on the water content and compactive effort (weight of hammer, number of impacts,
weight of roller, number of passes). For a given compactive effort, the maximum dry unit weight
occurs at an optimum water content.
4.2.4. SHEAR STRENGTH PARAMETERS
The shear strength of a soil is a function of:
The particle shape -- (Angular vs. rounded)
The gradation of the soil (Poor vs. well graded)
The soil density (Loose vs. dense)
The amount and types of fines
The pore pressure u and how the rate of loading affects it
4.2.4.1. COHESION
This is the shear strength parameter which is determined from direct shear test. Shear
strength is a term used in soil mechanics to describe the magnitude of the shear stress that a
soil can sustain. The shear resistance of soil is a result of friction and interlocking of
particles, and possibly cementation or bonding at particle contacts. Soil derives its shear
strength in two forms - Cohesion and angle of internal friction. Cohesion is the interlocking
strength between the soil particles. It is stress independent component.
stress dependent component. This is due to frictional resistance due to particles. The
mechanical strength of soil is an important concept in considering (and predicting) soil
behavior. We use strength to represent the reaction of a soil to an applied force. Highstrength soils resist deformation (compaction especially), break-up (shearing and shattering),
and slippage. However, high-strength soils also resist root penetration and exploration.
Strength is imparted to a soil by virtue of:
22
frictional resistance met by particles that are forced to slide over one another, or move
from interlocked positions.
The above specified earth pressures are used according to the situation i.e according to the
movement of the wall and the soil pressure acting on it.
mobilization of shearing resistance in a direction opposing the movement of the earth mass.
When the wall moves away from the backfill, a portion of the backfill locates next to the
retaining wall tends to break away from the rest of the soil mass and tends to move downwards
and outwards relative to the wall. Since the shearing resistance is mobilized in directions away
from the wall, there is a resultant decrease in earth pressure which continues, until, at a certain
amount of displacement, failure will occur in the backfill and slip surfaces will be developed. At
this stage, the entire shearing resistance has been mobilized. The forces acting on the wall at this
stage does not decrease anymore beyond this point even with further wall movement. This force
is called the active earth pressure.
On the other hand, if the wall is pushed towards the backfill, the soil is compressed and
the soil offers resistance to this movement by virtue of its shearing resistance. Since the shearing
resistance builds up in directions towards the wall, the earth pressure gradually increases. If this
force reaches a value which the backfill cannot withstand, failure again ensues and slip surfaces
develop. The pressure reaches a maximum value when the entire shearing resistance has been
mobilized and does not increase any more with further wall movement. This pressure is called
the passive earth pressure.
The active earth pressure and passive earth pressure develop corresponding to two
limiting states of equilibrium. The soil mass is said to be in a state of plastic equilibrium at these
two stages. A small increase in stress at this stage will cause a continuous increase in the
corresponding strain- a condition known as plastic flow.
24
6. RETAINING WALL
A retaining wall is a structure that retains holds back any material usually earth and prevents it
from sliding or eroding away. It is designed so that to resist the material pressure of the material
that it is holding back.
25
26
need a tie-back anchor placed in the soil a distance behind the face of the wall that is tied to the
wall, usually by a cable or a rod. Anchors are then placed behind the potential failure plane in the
soil.
28
Purpose:
This laboratory test is performed to determine the relationship between the moisture content and
the dry density of a soil compacted in a mould of given size.
Significance:
Mechanical compaction is one of the most common and cost effective means of stabilizing soils.
An extremely important task of geotechnical engineers is the performance and analysis of field
control tests to assure that compacted fills are meeting the prescribed design specifications.
Design specifications usually state the required density (as a percentage of the maximum
density measured in a standard laboratory test), and the water content. In general, most
engineering properties, such as the strength, stiffness, resistance to shrinkage and imperviousness
of the soil, will improve by increasing the soil density.
The optimum water content is the water content that results in the greatest density
for a specified compactive effort. Compacting at water contents higher than (wet of) the
optimum water content results in a relatively dispersed soil structure (parallel particle
orientations) that is weaker, more ductile, less pervious, softer, more susceptible to shrinking,
and less susceptible to swelling than soil compacted dry of optimum to the same density. The
soil compacted lower than (dry of) the optimum water content typically results in a flocculated
soil structure (random particle orientations) that has the opposite characteristics of the soil
compacted wet of the optimum water content to the same density.
29
Equipment:
1. Proctor mould having a capacity of 944cc with an internal diameter of 100mm and
effective height of 127.3mm. The mould shall have a detachable collar assembly and a
detachable base plate.
2. Rammer
3. Sample extruder
4. Straight edge
5. Graduated cylinder
6. Mixing tools such as mixing pan, spoon, spatula, etc.
7. Moisture tins
Procedure:
1. About 3kg of air-dried, pulverized soil passing 4.75mm sieve is taken. Thoroughly mix
the sample with sufficient water to dampen it.
2. The mould is cleaned, dried and greased lightly.
3. The mass of the empty mould with the base plate, without collar, is taken.
4. The collar is then fitted to the mould.
30
5. The mould is placed on a solid base and filled with fully matured soil to about one-third
its height.
6. The soil is compacted by 25 blows of the rammer, weighing 2.6kg, with a free fall of
310mm.
7. The blows are evenly distributed over the surface. The soil surface is scratched with a
spatula before the second layer is placed.
8. The mould is fitted to about two-thirds height with the soil and compacted again by 25
blows.
9. Likewise, the third layer is placed and compacted.
10. The third layer should project above the top of the mould into the collar by not more than
6mm.
11. The collar is rotated to break the bond between the soil in the mould and that in collar.
12. The collar is then removed, and the soil is trimmed off flush with the top of the mould.
13. The mass of the mould, base plate and compacted soil is taken and thus the mass of
compacted soil is determined.
14. The bulk density of the soil is computed from the mass of the compacted soil and the
volume of the mould.
15. Representative soil samples are taken from the bottom, middle and top of the mould for
determining the water content.
16. The soil is removed from the mould.
17. More water is added to the soil so as to increase the water content 2-3%. It is thoroughly
mixed and allowed to mature.
18. The test is repeated and the dry density and water content are determined.
19. Continue this series of determination until there is either a decrease or no change in the
wet unit weight of compacted soil.
31
32
Analysis:
1. Calculate the moisture content of each compacted soil specimen.
2. Compute the wet density in grams per cm3 of the compacted soil sample by dividing the wet
mass by the volume of the mold used.
3. Compute the dry density using the wet density and the water content determined in step 1. Use
the following formula:
d= / (1+w)
Where w = moisture content in percent divided by 100, and = wet density
Formulae:
Wet density (gm/cc) = weight of compacted soil/944
Dry density = Wet density/ (1+w)
Where w is the moisture content of the soil.
Observations:
Diameter of the cylinder = 10 cm
Height of the cylinder = 12 cm
Volume of the cylinder = 944 cc
Weight of the empty cylinder = 2219 gm
33
Details
10
12
240
300
360
4151.36
4250.48
4294.85
1932.36
2031.48
2075.86
Container No.
12
14
99
105
98
94
100
92
49
52
48
6.8
9.2
12.8
2.047
2.152
2.199
1.915
1.97
1.949
soil(gm)
(gm)
34
Calculations:
1. For 8% water,
Wet density = Weight of compacted soil / 944
= 1932.36/944
= 2.047 gm/cc
Dry density = Wet density / (1+w)
= 2.047 / (1+0.068)
= 1.915 gm/cc
2. For 10% water,
Wet density = Weight of compacted soil / 944
= 2031.48 /944
= 2.152 gm/cc
Dry density = Wet density / (1+w)
= 2.152 / (1+0.092)
= 1.97 gm/cc
3. For 12% water,
Wet density = Weight of compacted soil / 944
= 2075.86/944
= 2.199 gm/cc
Dry density = Wet density / (1+w)
= 2.199 / (1+0.128)
= 1.949 gm/cc
35
Graph 1:
1. Plot the dry density values on the y-axis and the moisture contents on the x-axis.
2. Draw a smooth curve connecting the plotted points.
Fig Graph showing the variation of moisture content and dry density in compaction test
Result:
From the graph,
Maximum Dry Density of the Moorum soil = 1.97 gm/cc
36
Significance:
37
The direct shear test is one of the oldest strength tests for soils. In this laboratory, a direct shear
device will be used to determine the shear strength of a soil (i.e. angle of internal friction ()).
From the plot of the shear stress versus the horizontal displacement, the maximum shear stress is
obtained for a specific vertical confining stress. After the experiment is run several times for
various vertical-confining stresses, a plot of the maxi mum shear stresses versus the vertical
(normal) confining stresses for each of the tests is produced. From the plot, a straight-line
approximation of the Mohr-Coulomb failure envelope curve can be drawn and is determined.
Equipment:
1. Direct shear device
2. Load and deformation dial gauges
3. Balance
4. Spatula
Procedure:
1. A soil specimen of size 60x60x25 mm is taken.
2. The base plate is attached to the lower half of the box. A porous stone is placed in the
box.
38
3. The upper grid, porous stone and the pressure pad are placed on the specimen.
4. The box is placed inside the large container and mounted on the loading frame.
5. The upper half of the box is brought in contact with the proving ring.
6. The loading yoke is mounted on the steel ball placed on the pressure pad.
7. The dial gauge is fitted to the container to give the shear displacement.
8. The other dial gauge is mounted on the loading yoke to record the vertical movement.
9. The locking pins are removed and the upper half of the box is slightly raised with the
help of spacing screws.
10. The space between two halves is adjusted, depending upon the maximum particle size.
11. The normal load is applied to give a normal stress of 25kN/m2.
12. Shear load is then applied at a constant rate of strain. For undrained tests, the rate is
generally between 1.0 mm to 2.0 mm per minute.
13. The sample shears along the horizontal plane between the two halves.
14. The readings of the proving ring and the dial gauge are taken every 30 seconds.
15. The test is continued till the specimen fails. The failure is indicated when the proving ring
dial gauge begins to recede after having reached the maximum.
16. At the end of the test, the specimen is removed from the box and its water content is
found.
17. The test is repeated under the normal stress of 50,100, 200 and 400 kN/m2. The range of
the normal stress should cover the range of loading in the field problem for which the
shear parameters are required.
18. Readings are noted down carefully. Set the dial gauges zero, before starting the
experiment.
Mechanism:
1. The direct shear test uses a box split into top and bottom halves.
2. The bottom half is fixed while the top half can slide.
3. A constant normal force P is applied to the top of the box while a shearing force T is
gradually applied to one side.
4. As the shear force increases, the lateral displacement is measured.
39
5. The normal force divided by the cross sectional area of the box is the normal stress and
the shear force T divided by the area is the shear stress.
40
Analysis:
1. Calculate the density of the soil sample from the mass of soil and volume of the shear
box.
2. Convert the dial readings to the appropriate length and load units and enter the values on
the data sheet in the correct locations. Compute the sample area A, and the vertical
(Normal) stress sv.
sv=Nv/A
Where Nv = normal vertical force, and sv = normal vertical stress
3. Calculate shear stress (t) using
t = Fh / A
Where Fh= shear stress (measured with shear load gage)
4. Plot the horizontal shear stress (t) versus horizontal (lateral) displacement (H).
5. Calculate the maximum shear stress for each test.
6. Plot the value of the maximum shear stress versus the corresponding vertical stress for
each test, and determine the angle of internal friction () from the slope of the
approximated Mohr-Coulomb failure envelope.
41
Formulae:
Shear stress = (Proving Ring Reading * calibration) / area of container
1 division of proving ring reading= 0.3797 kg
Observations:
Dimensions of shear box = 6x6 cm
42
S. No.
Normal
(kg)
reading
1.
0.5
0.5
6.4
0.33
2.
14.4
0.78
3.
1.5
1.5
18.8
1.03
Calculations:
Maximum Dry Density, d = 1.97 gm/cc
Optimum moisture content = 11%
Volume of the mould, V = 6*6*2.5
= 90 cc
1.97= weight/ 90
Weight of sample to be taken = 1.97*90
= 178.3 gm
Water to be added = 178.3 * 0.11
= 19.6 20 ml
(1) Normal stress = 0.5 kg/cm2
Proving ring reading = 6.4
= (6*5) + 4
= 34
Area of mould = 6*6 = 36 cm2
43
44
Graph 2:
Fig: ; Graph showing variation of normal load and shear stress in direct shear test.
Result:
Shear strength of the given soil sample is 0.03 kg/ cm2
45
Purpose:
The primary purpose of this test is to determine the unconfined compressive strength, which is
then used to calculate the unconsolidated undrained shear strength of the clay under unconfined
conditions. According to the ASTM standard, the unconfined compressive strength (qu) is
defined as the compressive stress at which an unconfined cylindrical specimen of soil will fail in
a simple compression test.
Significance:
For soils, the undrained shear strength (su) is necessary for the determination of the bearing
capacity of foundations, dams, etc. The undrained shear strength (su) of clays is commonly
determined from an unconfined compression test. The undrained shear strength (su) of a cohesive
soil is equal to one-half the unconfined compressive strength (qu) when the soil is under the = 0
condition ( = the angle of internal friction). The most critical condition for the soil usually
occurs immediately after construction, which represents undrained conditions, when the
undrained shear strength is basically equal to the cohesion (c).This is expressed as:
Su = c = qu/2
Then, as time passes, the pore water in the soil slowly dissipates, and the Inter-granular stress
increases, so that the drained shear strength (s), given by s = c + stan , must be used. Where s
= inter-granular pressure acting perpendicular to the shear plane; and s = (s - u), s = total
pressure, and u = pore water pressure; c is drained shear strength parameter.
Equipment:
1. Compression device
2. Load and deformation dial gauges
3. Sample trimming equipment
4. Balance
46
5. Moisture can.
Procedure:
1. Sample is prepared at the desired water content and dry density.
2. It is compacted in three layers in a cylindrical tube of standard dimensions.
3. In this type of unconfined compression testing machine, a proving ring is used to measure
the compressive force.
4. There are two plate, having cone seating for the specimen.
5. The specimen is placed on the bottom plate so that it makes contact with the upper plate.
6. The dial gauge and proving ring are set to zero.
7. Compressive load is applied to the specimen by turning the handle.
8. As the handle is turned, the upper plate moves downward and causes compression.
9. The handle is turned gradually so as to produce an axial strain of % to 2 % per minute.
10. The shearing is continued till the specimen fails.
47
11. The compressive force is determined from proving ring reading and axial strain from dial
gauge reading.
48
49
Analysis:
1. Convert the dial readings to the appropriate load and length units, and enter these values
on the data sheet in the deformation and total load columns. (Confirm that the conversion
is done correctly, particularly proving dial gage readings conversion into load)
2. Compute the sample cross-sectional area A0 = d2/4
3. Compute the strain, e = L / L0
4. Computed the corrected area, A' = A0 / (1- e)
5. Using A, compute the specimen stress, sc = P/ A (Be careful with unit conversions and
use constant units).
6. Compute the water content, w%.
7. Plot the stress versus strain. Show qu as the peak stress of the test. Be sure that the strain
is plotted on the abscissa.
8. Draw Mohrs circle using qu from the last step and show the undrained shear strength, su
= c (or cohesion) = qu/2.
50
Formulae:
Observations:
Diameter of the sample = 3.8 cm
Initial height of the sample = 7.8 cm
Area of cross-section = 11.34 cm2
51
(mm)
Proving
Axial
A/(1-c )
ring
(kg)
(cm2)
reading
(div)
50
0.641
11.413
0.7
0.26873
0.02354
100
1.282
11.487
0.8
0.30712
0.02673
150
1.923
11.562
1.8
4.9907
0.4316
200
2.564
11.638
2.6
6.1424
0.5277
250
3.205
11.715
3.3
6.9102
0.5898
300
3.846
11.79
3.6
8.0619
0.6837
350
4.487
11.872
4.4
9.2136
0.776
400
5.128
11.95
5.4
11.1331
0.9316
450
5.769
12.034
5.6
11.9009
0.9888
500
6.41
12.11
6.2
12.2848
1.0144
550
7.051
12.2
6.6
13.8204
1.1328
600
7.692
12.28
7.2
14.2043
1.1567
650
8.33
12.37
7.7
16.1238
1.3034
52
Calculations:
Maximum Dry Density, d = 1.97 gm/cc
Optimum moisture content = 11%
Cross-sectional Area of sample = (*d2)/4
= (*3.82)/4
= 11.34 cm2
Volume of the sample = ((*d2)/4)*h
= ((*3.82)/4)*7.8
= 11.34*7.8
= 88.46 cm3
Density = weight / volume
1.97 = weight / 88.46
Weight of sample to be taken = 1.97*88.46
= 175 gm
Water to be added = 175 * 0.11
= 19.36 20 ml
Result:
53
Bearing capacity is the power of foundation soil to hold the forces from the
superstructure without undergoing shear failure or excessive settlement. Foundation soil is that
portion of ground which is subjected to additional stresses when foundation and superstructure
are constructed on the ground. The following are a few important terminologies related to
bearing capacity of soil.
Super Structure
Ground Level
Foundation
Foundation Soil
54
8.2.1 Assumptions
1. Soil is homogeneous and Isotropic.
2. The shear strength of soil is represented by Mohr Coulombs Criteria.
3. The footing is of strip footing type with rough base. It is essentially a two dimensional plane
strain problem.
4. Elastic zone has straight boundaries inclined at an angle equal to to the horizontal.
5. Failure zone is not extended above, beyond the base of the footing. Shear resistance of soil
above the base of footing is neglected.
55
8.2.2 Limitations
1. The theory is applicable to shallow foundations
2. As the soil compresses, increases which is not considered. Hence fully plastic zone may
not develop at the assumed .
3. All points need not experience limit equilibrium condition at different loads.
4. Method of superstition is not acceptable in plastic conditions as the ground is near failure
zone.
56
Fig. 8.2.2 : Terzaghis concept of Footing with five distinct failure zones in foundation soil
8.2.3 Concept
A strip footing of width B gradually compresses the foundation soil underneath due to the
vertical load from superstructure. Let qf be the final load at which the foundation soil experiences
failure due to the mobilization of plastic equilibrium. The foundation soil fails along the
composite failure surface and the region is divided in to five zones, Zone 1 which is elastic, two
numbers of Zone 2 which are the zones of radial shear and two zones of Zone 3 which are the
zones of linear shear. Considering horizontal force equilibrium and incorporating empirical
relation, the equation for ultimate bearing capacity is obtained as follows.
Ultimate bearing capacity, q f = cN c + DN q + 0.5BN
If the ground is subjected to additional surcharge load q, then
q f = cN c + (D + q) N q + 0.5BN
57
] F1 + D
Net safe bearing capacity is the net soil pressure which can be safely applied to the soil
considering only shear failure. It is obtained by dividing the net ultimate bearing capacity by a
suitable factor of safety.
qns
qnu / F
Net ultimate bearing capacity is the net increase in pressure at the base pf the foundation that
causes shear failure of the soil. It is equal to gross pressure minus overburden pressure.
qnu = qu - Df
58
TABLE NO.4
BEARING CAPACITY FACTORS FOR DIFFERENT
Nc
Nq
Ng
N'c
N'q
N'g
5.7
1.0
0.0
5.7
1.0
0.0
7.3
1.6
0.5
6.7
1.4
0.2
10
9.6
2.7
1.2
8.0
1.9
0.5
15
12.9
4.4
2.5
9.7
2.7
0.9
20
17.7
7.4
5.0
11.8
3.9
1.7
25
25.1
12.7
9.7
14.8
5.6
3.2
30
37.2
22.5
19.7
19.0
8.3
5.7
34
52.6
36.5
35.0
23.7
11.7
9.0
35
57.8
41.4
42.4
25.2
12.6
10.1
40
95.7
81.3
100.4
34.9
20.5
18.8
45
172.3
173.3
297.5
51.2
35.1
37.7
48
258.3
287.9
780.1
66.8
50.5
60.4
50
347.6
415.1
1153.2
81.3
65.6
87.1
59
The shape of footing influences the bearing capacity. Terzaghi and other contributors have
suggested the correction to the bearing capacity equation for shapes other than strip footing
based on their experimental findings. The following are the corrections for circular, square and
rectangular footings.
Circular footing
q f = 1 .3cN c + DN q + 0 .3 BN
60
Square footing
q f = 1.3cN c + DN q + 0.4BN
Rectangular footing
B
B
q f = (1 + 0.3 )cN c + DN q + (1 0.2 )0.5BN
L
L
sc
sq
Square
1.3
0.8
Round
1.3
0.6
B
(1 + 0.3 )
L
B
(1 0.2 )
L
Strip
Rectangle
Nq
Nc
Kp
62
Result
Ultimate bearing capacity,
qu = 202.18 t/ m2
Net ultimate bearing capacity,
qnu = 198 t/ m2
Net safe bearing capacity,
qns = 198/3
= 66.06 t/ m2
63
likely to cause unpredictable earth pressures and wall movements while shrinkage may lead to
tension cracks in soil. The cracks may subsequently get filled with water, adding considerably to
the lateral pressure.
65
The earth pressure can be computed using Rankines theory or Coulombs theory. For using
Rankines theory a vertical line AB is drawn through the heel point A. it is assumed that Rankine
active condition exist along vertical line AB. However, the assumption for the development of
Rankines conditions along AB is theoretically justified only if the shear zone bounded by the
line AC is not obstructed by the stem of the wall, where AC makes an angle with the vertical,
given by
= (450 + i/2) - l/2 - sin-1(sin i/ sin l)
where i is the angle of surcharge.
The angle which the line AC makes with the horizontal is given by,
= (450+ l/2) i/2 + sin-1(sin i/ sin l)
when i=0, the value of is equal to (450+ l/2)
While checking the stability, the weight of soil (Ws) above the heel in the zone ABC
should also be taken into consideration, in addition to the earth pressure on the back face (Pa), the
forces to be considered are only Pa (coulomb) and the weight of the wall (Wc). In this case, the
weight of the soil (Ws) is not to be considered separately.
Once the forces acting on the wall have been determined, the stability is checked using
the procedure shown in the preceding section. For convenience, the section of the retaining wall
is divided into rectangles and triangles for the computation of weight and determination of the
line of action of the weights.
9.4 DESIGN
The earth pressure is computed using Rankines theory on the vertical plane AB, provided the
shear zone bounded by the line AC is not obstructed by the stem of the wall. The line AC makes
an angle with the vertical given by the equation,
= (450 + i/2) - l/2 - sin-1(sin i/ sin l)
Figure below shows the forces acting on the wall. The Rankine pressure Pa acts at an angle i with
the horizontal. It is resolved into vertical and horizontal components Pv and Ph, as shown. The
66
passive pressure Pp is generally neglected. For convenience, the weight of soil (Ws) over the slab
is divided into two parts. Likewise, the weight of stem is divided into two parts.
a) Factor of safety against sliding
The factor of safety against sliding may be expressed as
Fs = FR / Fd
Where FR =sum of the horizontal resisting forces,
and Fd =sum of horizontal driving forces
hence the final equation is, Fs= ((V) tan 2 + bc2 + Pp) / (Ph)
where b = base width,
V = sum of all vertical forces; Wc, Ws, Pv
Pv = Pa sini, Ph = Pa cosi
Pp = passive force in the front of the wall
= Kp22D2 + 2c2 Kp21/2 D
where c2, 2 and 2 are parameters of the foundation soil.
The factor of safety can also be determined from the equation
Fs = RV / RH
Where RV and RH are vertical and horizontal reaction forces
= coefficient of friction between base of the wall and the soil
= tan 2/3
A minimum factor of safety of 1.5 against sliding is generally recommended.
67
68
e = b/2 - xl
if e > b/6, the section should be changed as it indicates tension.
The pressure distribution under the base slab is determined as
Pmax = (V/b) * (1+ (6e/b))
Pmin = (V/b) * (1- (6e/b))
The factor of safety against bearing failure is given by
Fb = qna / Pmax
Where qna= allowable bearing pressure.
Generally, a factor of safety of 3 is usually specified, provided the settlement is also within the
allowable limit.
69
10.
By considering the above design procedure and keeping in view of soil analysis, the existing
section should be modified and reconstructed. The Existing section of Retaining wall is shown in
the figure below.
EXISTING SECTION
0.55 m
3.68 m
1m
0.55 m
1.5 m
3.05 m
70
0.5 m
TRIAL SECTION 1
0.55 m
2.245 m
0.5 m
1m
0.5 m
0.5 m
1.6 m
0.5 m
2.6 m
71
Components
Load
Moment
Lever
arm at sill sill
at Lever
arm at
floor level
Moment at
floor level
0.717
0.926
1.767
2.281
0.275
0.781
1.325
3.763
1.05
Rectangular portion
0.55*2.245*2.3 =
2.84
4.131
1.707
6.044
Trapezoidal footing
a
Rectangular portion
1.05*1*2.3
2.415
1.575
3.804
0.633
0.867
0.549
2.99
1.3
3.887
0.5*3.245*2
3.245
2.123
6.89
Total
13.414
Triangular portion
1*0.5*1*2.3
Final footing
2.6*0.5*2.3
Weight of earth
21.174
72
73
= 1.6
e = -((b / 2) - xl)
= -((2.6/2) 1.6)
=0.3
b/6 = 2.6/6
=0.433
e<b/6
Thus, safe against tension
Maximum stress, Pmax = (V/b) * (1+ (6e/b))
= (10.169/2.6) * (1+(6*0.3/2.6))
= 6.042 t/m2
Minimum stress, Pmin = (V/b) * (1- (6e/b))
= (10.169/2.6) * (1+(6*0.3/2.6))
= 1.098 t/m2 < 53 t/m2 for M20 grade concrete
Factor of safety against bearing capacity,
Fb = qna / Pmax
= (66 / 6.042)
= 10.92 > 3
Thus, safe against bearing failure
Where qna = allowable bearing pressure.
Check for sliding failure:Fs = RV / RH
= (0.674*10.169) / 3.245
= 2.11 >1.5
Thus, safe against sliding
74
75
TRIAL SECTION 2
0.55m
2.245 m
0.5m
1m
0.5 m
0.25 m
0.7 m
2.5 m
76
0.5 m
Load
Lever
Moment
arm at sill sill
at Lever
arm at
floor level
Moment at
floor level
Total
0.716
0.923
1.66
2.15
0.275
0.78
1.225
3.47
4.129
1.703
5.62
Trapezoidal footing
a
Rectangular portion
1.05*1*2.3
2.415
1.475
3.56
0.805
0.716
0.576
2.875
1.25
3.593
0.25*3.245*2
1.6225
2.122
3.44
Total
11.846
Triangular portion
0.7*0.5*1*2.3
Final footing
2.5*0.5*2.3
Weight of earth
16.789
77
78
79
= (0.674*10.223) /1.6225
= 4.24 >1.5
Thus, safe against sliding
Where RV and RH are vertical and horizontal reaction forces
= coefficient of friction between base of the wall and the soil
= tan (where = 340)
Check for overturning failure:The wall must be safe against overturning about toe. The factor of safety against overturning is
given by
F0 = MR / M0
= 16.78/3.44
= 4.87> 2
Thus, safe against overturning
Where MR = sum of the resisting moments about toe
M0 = sum of the overturning moments about toe
80
TRIAL SECTION 3
0.55m
2.245 m
0.5 m
1m
0.25 m
0.4m
0.7 m
2.4 m
81
0.5 m
Components
Load
Moment
Lever
arm at sill sill
at Lever
arm at
floor level
Moment at
floor level
0.716
0.923
1.66
2.15
0.55*2.245*2.3 =
2.839
0.275
0.78
1.225
3.47
Total
4.129
1.703
5.62
Trapezoidal footing
a
Rectangular portion
1.05*1*2.3
2.415
1.475
3.562
0.805
0.716
0.576
2.76
1.2
3.312
0.25*3.245*2
1.622
2.123
3.44
Total
11.731
Triangular portion
0.5*0.7*1*2.3
Final footing
2.4 *0.5*2.3
Weight of earth
16.51
82
83
84
= (0.674*10.109)/1.622
= 4.205 >1.5
Thus, safe against sliding
Where RV and RH are vertical and horizontal reaction forces
= coefficient of friction between base of the wall and the soil
= tan (where = 340)
Check for overturning failure:The wall must be safe against overturning about toe. The factor of safety against overturning is
given by
F0 = MR / M0
= 13.07/3.44
= 3.79 > 2
Thus, safe against overturning
Where MR = sum of the resisting moments about toe
M0 = sum of the overturning moments about toe
85
Result
The width of the foundation for the third trial section is less when compared to other two
sections. Hence, among the three trial sections, the third trial section is economical.
86
CONCLUSION
The project, designing of retaining wall for a minor bridge is the consequence of
prestigious metro rail project. In the construction course of metro railway, a four lane road way
has to be extended to six lanes, to avoid the occurrence of traffic problems. The minor bridgein
this course also has to be extended.
We took existing four lane retaining wall as an example and designed retaining wall
for the six lane road way. Each section has been analyzed for failure against sliding, overturning,
tension and bearing capacity. After doing trials for many sections, we got a section satisfying all
the safety conditions, approximating the standard dimensions of a gravity retaining wall.
The location of minor bridge being in rocky strata, with moorum soil, we got a high
bearing capacity value. Taking this as a reference, we also designed two economical sectionswith reduced dimensions. Hence, apart from the main modified section other two sections can
also be considered to make the project economical, which is the main philosophy behind the
project.
87
BIBLIOGRAPHY
88