Sei sulla pagina 1di 4

Estimation of Population

Area:
Open Area:
Roads etc.:
Built-up area:
Built-up area:
FAR:
Total Floor Space:
Average Height of Buildings
Percent Residential Area:
Residential Area:
Population Density:
Estimated Population (2032):

100
60
10
30
121380
2.5
1011500
8
75
758625
25
30345

Estimation of Water Demand


Average per capita domestic Demand (2033):
Domestic Water Demand (2033):
Temporary Population (2033):
Average per capita temporary Demand (2033):
Temporary Water Demand (2033):
Commercial Water Demand (2033):
Horticultural Demand:
Average Daily Demand (2033):
Maximum Daily Demand (2033):
Maximum Hourly Demand (2033):
Fire Demand (2032):
Storage Required for:
Storage Capacity (2033):

235
7.13
10000
60
0.60
3.57
1.21
12.51
22.52
37.53
0.55
6.00
4.30

Inlet Channel Design


Design
Q (Maximum Daily Demand):
Q (Maximum Daily Demand):
Scourning Velocity (Vsc): (2.5 mm particles)
n
b
h
S
R
Horizontal velocity (Vh):

0.261

Okay

22.519
0.261
0.805
0.012
0.200
1.090
0.005
0.092
1.197

Design of Silt Excluder


Design
Q (Maximum Daily Demand):
Scourning Velocity (Vsc): (0.25 mm particles)
Settling Velocity (Vs): (0.2 mm particles):
Width (B):
Cw:
Height over Weir (H):
Height of Weir (Hw):
Depth of flow in weir (h1):
Horizontal velocity (VH):
Detention time (T):
Length (L):
Length provided:
Effective Detention Time (TE):

Okay

0.261
0.254
0.032
0.900
0.950
0.168
1.100
1.268
0.228
40.028
9.142
13.713
60.04

on
acres
acres
acres
acres
sq. m.

Given
Given
Given
Given
Calculated
Given
sq. m.
Calculated
stories
Calculated
percent
Given
sq. m.
Calculated
sq m / person
Given
persons
Calculated

mand
lpcd
MLD
persons
lpcd
MLD
MLD
MLD
MLD
MLD
MLD
ML
hours
ML

Given
Calculated
Given
Given
Calculated
Calculated
Calculated
Calculated
Calculated
Calculated
Calculated
Given
Calculated

annel Design
Low Flow
MLD
cum / s
m/s
m
m
m
m/s

Calculated
Calculated
Calculated
Given
Given
Calculated
Given
Calculated
Calculated

0.072

Okay

6.255
0.072
0.805
0.012
0.200
0.336
0.005
0.077
1.067

MLD
cum / s
m/s
m
m
m
m/s

f Silt Excluder
Low Flow
cum / s
m/s
m/s
m
m
m
m
s
m
m
s

Calculated
Calculated
Calculated
Given
Given
Calculated
Given
Calculated
Calculated
Calculated
Calculated
Calculated
Calculated

Okay

0.072
0.254
0.032
0.900
0.950
0.071
1.100
1.171
0.069
133.139
9.142
13.713
199.71

cum / s
m/s
m/s
m
m
m
m
s
m
m
s

Potrebbero piacerti anche