Zone Sizing Summary for FCU-1F-01

Project Name: G+4-SAGE


Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-01
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
16.3 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
215

Minimum
Air
Flow
(L/s)
215

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.7

Coil
Entering
DB / WB
(C)
23.4 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
215

Fan
Motor
(BHP)
0.054

Zone
Floor
Area
(m)
16.3

Zone
L/(s-m)
13.17

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEC-MASTR BED ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Aug 1500

215

0.3

16.3

13.17

Page 1 of 81

Zone Sizing Summary for FCU-1F-02


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-02
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
51.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.3

Design
Air
Flow
(L/s)
497

Minimum
Air
Flow
(L/s)
497

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.9

Total
Coil
Load
(kW)
6.6

Sens
Coil
Load
(kW)
6.3

Coil
Entering
DB / WB
(C)
23.4 / 16.5

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
497

Fan
Motor
(BHP)
0.125

Zone
Floor
Area
(m)
51.5

Zone
L/(s-m)
9.65

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.099

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEC- LIVING ROOM-1
FF-TYPEC-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

4.9
1.4

Aug 1500
Sep 1600

386
111

0.7
0.2

43.0
8.5

8.98
13.03

Page 2 of 81

Zone Sizing Summary for FCU-1F-03


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-03
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
13.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.4

Design
Air
Flow
(L/s)
188

Minimum
Air
Flow
(L/s)
188

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.4

Sens
Coil
Load
(kW)
2.3

Coil
Entering
DB / WB
(C)
23.6 / 16.7

Coil
Leaving
DB / WB
(C)
13.4 / 12.7

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
188

Fan
Motor
(BHP)
0.047

Zone
Floor
Area
(m)
13.5

Zone
L/(s-m)
13.94

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.038

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEC- BED R0OM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.4

Aug 1500

188

0.3

13.5

13.94

Page 3 of 81

Zone Sizing Summary for FCU-1F-04


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-04
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
51.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.2

Design
Air
Flow
(L/s)
493

Minimum
Air
Flow
(L/s)
493

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.9

Total
Coil
Load
(kW)
6.4

Sens
Coil
Load
(kW)
6.1

Coil
Entering
DB / WB
(C)
23.6 / 16.7

Coil
Leaving
DB / WB
(C)
13.3 / 12.7

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
493

Fan
Motor
(BHP)
0.124

Zone
Floor
Area
(m)
51.5

Zone
L/(s-m)
9.57

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.099

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEC- LIVING ROOM-2
FF-TYPEC-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

4.9
1.3

Aug 1500
Jul 1500

386
106

0.7
0.2

43.0
8.5

8.98
12.52

Page 4 of 81

Zone Sizing Summary for FCU-1F-05


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-05
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
13.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.4

Design
Air
Flow
(L/s)
188

Minimum
Air
Flow
(L/s)
188

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.4

Sens
Coil
Load
(kW)
2.3

Coil
Entering
DB / WB
(C)
23.6 / 16.7

Coil
Leaving
DB / WB
(C)
13.4 / 12.7

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
188

Fan
Motor
(BHP)
0.047

Zone
Floor
Area
(m)
13.5

Zone
L/(s-m)
13.94

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.038

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEC- BED R0OM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.4

Aug 1500

188

0.3

13.5

13.94

Page 5 of 81

Zone Sizing Summary for FCU-1F-06


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-06
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
16.3 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
215

Minimum
Air
Flow
(L/s)
215

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.7

Coil
Entering
DB / WB
(C)
23.4 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
215

Fan
Motor
(BHP)
0.054

Zone
Floor
Area
(m)
16.3

Zone
L/(s-m)
13.17

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEC-MASTR BED ROM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Aug 1500

215

0.3

16.3

13.17

Page 6 of 81

Zone Sizing Summary for FCU-1F-07


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-07
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.4

Design
Air
Flow
(L/s)
186

Minimum
Air
Flow
(L/s)
186

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.4

Sens
Coil
Load
(kW)
2.3

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
186

Fan
Motor
(BHP)
0.047

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
12.86

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.037

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.4

Sep 1600

186

0.2

14.5

12.86

Page 7 of 81

Zone Sizing Summary for FCU-1F-08


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-08
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.4

Design
Air
Flow
(L/s)
510

Minimum
Air
Flow
(L/s)
510

Time
of
Peak
Load
Aug 1600

Maximum
Heating
Load
(kW)
0.8

Total
Coil
Load
(kW)
6.7

Sens
Coil
Load
(kW)
6.4

Coil
Entering
DB / WB
(C)
23.4 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
510

Fan
Motor
(BHP)
0.129

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
11.73

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.102

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-1
FF-TYPEB-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

5.1
1.4

Sep 1600
Jul 1700

401
109

0.6
0.2

35.0
8.5

11.46
12.83

Page 8 of 81

Zone Sizing Summary for FCU-1F-09


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-09
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.8

Design
Air
Flow
(L/s)
141

Minimum
Air
Flow
(L/s)
141

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.0

Sens
Coil
Load
(kW)
1.7

Coil
Entering
DB / WB
(C)
23.5 / 17.1

Coil
Leaving
DB / WB
(C)
13.2 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
141

Fan
Motor
(BHP)
0.036

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
5.76

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.028

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-LOBBY
FF-TYPEB- TELE. ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.2
0.6

Jul 1500
Jul 1500

94
47

0.0
0.1

20.0
4.5

4.68
10.53

Page 9 of 81

Zone Sizing Summary for FCU-1F-10


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-10
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
162

Minimum
Air
Flow
(L/s)
162

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.0

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
162

Fan
Motor
(BHP)
0.041

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
11.15

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Jul 1500

162

0.2

14.5

11.15

Page 10 of 81

Zone Sizing Summary for FCU-1F-11


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-11
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
5.8

Design
Air
Flow
(L/s)
459

Minimum
Air
Flow
(L/s)
459

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.8

Total
Coil
Load
(kW)
6.0

Sens
Coil
Load
(kW)
5.7

Coil
Entering
DB / WB
(C)
23.6 / 16.8

Coil
Leaving
DB / WB
(C)
13.4 / 12.8

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
459

Fan
Motor
(BHP)
0.116

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
10.55

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.092

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-2
FF-TYPEB-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

4.4
1.4

Jul 1500
Jul 1700

350
109

0.6
0.2

35.0
8.5

9.99
12.83

Page 11 of 81

Zone Sizing Summary for FCU-1F-12


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-12
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
3.2

Design
Air
Flow
(L/s)
256

Minimum
Air
Flow
(L/s)
256

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.4

Total
Coil
Load
(kW)
3.3

Sens
Coil
Load
(kW)
3.2

Coil
Entering
DB / WB
(C)
23.4 / 16.4

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
256

Fan
Motor
(BHP)
0.065

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
13.06

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.051

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

3.2

Jul 1500

256

0.4

19.6

13.06

Page 12 of 81

Zone Sizing Summary for FCU-1F-13


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-13
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
3.4

Design
Air
Flow
(L/s)
268

Minimum
Air
Flow
(L/s)
268

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.4

Total
Coil
Load
(kW)
3.5

Sens
Coil
Load
(kW)
3.3

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
268

Fan
Motor
(BHP)
0.068

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
13.70

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.054

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

3.4

Sep 1600

268

0.4

19.6

13.70

Page 13 of 81

Zone Sizing Summary for FCU-1F-14


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-14
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
3.4

Design
Air
Flow
(L/s)
268

Minimum
Air
Flow
(L/s)
268

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.4

Total
Coil
Load
(kW)
3.5

Sens
Coil
Load
(kW)
3.3

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
268

Fan
Motor
(BHP)
0.068

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
13.70

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.054

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

3.4

Sep 1600

268

0.4

19.6

13.70

Page 14 of 81

Zone Sizing Summary for FCU-1F-15


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-15
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
3.2

Design
Air
Flow
(L/s)
256

Minimum
Air
Flow
(L/s)
256

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.4

Total
Coil
Load
(kW)
3.3

Sens
Coil
Load
(kW)
3.2

Coil
Entering
DB / WB
(C)
23.4 / 16.4

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
256

Fan
Motor
(BHP)
0.065

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
13.06

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.051

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

3.2

Jul 1500

256

0.4

19.6

13.06

Page 15 of 81

Zone Sizing Summary for FCU-1F-16


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-16
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
5.8

Design
Air
Flow
(L/s)
456

Minimum
Air
Flow
(L/s)
456

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.8

Total
Coil
Load
(kW)
6.0

Sens
Coil
Load
(kW)
5.7

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
456

Fan
Motor
(BHP)
0.115

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
10.49

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.091

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-4
FF-TYPEB-KITCHEN-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

4.4
1.3

Jul 1500
Aug 1500

350
107

0.6
0.2

35.0
8.5

9.99
12.53

Page 16 of 81

Zone Sizing Summary for FCU-1F-17


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-17
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
162

Minimum
Air
Flow
(L/s)
162

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.0

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
162

Fan
Motor
(BHP)
0.041

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
11.15

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Jul 1500

162

0.2

14.5

11.15

Page 17 of 81

Zone Sizing Summary for FCU-1F-18


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-18
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
5.8

Design
Air
Flow
(L/s)
456

Minimum
Air
Flow
(L/s)
456

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.8

Total
Coil
Load
(kW)
6.0

Sens
Coil
Load
(kW)
5.7

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
456

Fan
Motor
(BHP)
0.115

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
10.49

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.091

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-3
FF-TYPEB-KITCHEN-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

4.4
1.3

Jul 1500
Aug 1500

350
107

0.6
0.2

35.0
8.5

9.99
12.53

Page 18 of 81

Zone Sizing Summary for FCU-1F-19


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-19
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.3

Design
Air
Flow
(L/s)
178

Minimum
Air
Flow
(L/s)
178

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.3

Sens
Coil
Load
(kW)
2.2

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
178

Fan
Motor
(BHP)
0.045

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
12.30

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.036

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.3

Sep 1600

178

0.2

14.5

12.30

Page 19 of 81

Zone Sizing Summary for FCU-1F-20


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-20
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.8

Design
Air
Flow
(L/s)
146

Minimum
Air
Flow
(L/s)
146

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
1.8

Coil
Entering
DB / WB
(C)
23.4 / 17.0

Coil
Leaving
DB / WB
(C)
13.2 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
146

Fan
Motor
(BHP)
0.037

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
5.95

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.029

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-LOBBY
FF-TYPEB- ELECT. ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.2
0.7

Jul 1500
Jul 1500

94
52

0.0
0.1

20.0
4.5

4.68
11.58

Page 20 of 81

Zone Sizing Summary for FCU-1F-21


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-21
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.9

Design
Air
Flow
(L/s)
232

Minimum
Air
Flow
(L/s)
232

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(kW)
0.4

Total
Coil
Load
(kW)
3.0

Sens
Coil
Load
(kW)
2.9

Coil
Entering
DB / WB
(C)
23.7 / 16.8

Coil
Leaving
DB / WB
(C)
13.4 / 12.8

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
232

Fan
Motor
(BHP)
0.058

Zone
Floor
Area
(m)
18.5

Zone
L/(s-m)
12.53

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.046

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEA-MASTR BED ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.9

Jul 1700

232

0.4

18.5

12.53

Page 21 of 81

Zone Sizing Summary for FCU-1F-22


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-22
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.6

Design
Air
Flow
(L/s)
204

Minimum
Air
Flow
(L/s)
204

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.6

Sens
Coil
Load
(kW)
2.5

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
204

Fan
Motor
(BHP)
0.051

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
14.05

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.041

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEA- BED ROOM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.6

Jul 1700

204

0.3

14.5

14.05

Page 22 of 81

Zone Sizing Summary for FCU-1F-23


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-23
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
49.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.3

Design
Air
Flow
(L/s)
503

Minimum
Air
Flow
(L/s)
503

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(kW)
0.9

Total
Coil
Load
(kW)
6.8

Sens
Coil
Load
(kW)
6.3

Coil
Entering
DB / WB
(C)
23.5 / 16.7

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
503

Fan
Motor
(BHP)
0.127

Zone
Floor
Area
(m)
49.5

Zone
L/(s-m)
10.16

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.101

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEA- LIVING R0OM-1
FF-TYPEA-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

5.1
1.3

Jul 1600
Sep 1600

403
100

0.7
0.1

41.5
8.0

9.71
12.51

Page 23 of 81

Zone Sizing Summary for FCU-1F-24


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-24
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
49.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.3

Design
Air
Flow
(L/s)
496

Minimum
Air
Flow
(L/s)
496

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(kW)
0.9

Total
Coil
Load
(kW)
6.6

Sens
Coil
Load
(kW)
6.2

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
496

Fan
Motor
(BHP)
0.125

Zone
Floor
Area
(m)
49.5

Zone
L/(s-m)
10.02

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.099

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEA- LIVING R0OM-2
FF-TYPEA-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

5.0
1.3

Jul 1600
Jul 1500

391
105

0.7
0.1

41.5
8.0

9.42
13.15

Page 24 of 81

Zone Sizing Summary for FCU-1F-25


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-25
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.6

Design
Air
Flow
(L/s)
204

Minimum
Air
Flow
(L/s)
204

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.6

Sens
Coil
Load
(kW)
2.5

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
204

Fan
Motor
(BHP)
0.051

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
14.05

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.041

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEA- BED ROOM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.6

Jul 1700

204

0.3

14.5

14.05

Page 25 of 81

Zone Sizing Summary for FCU-1F-26


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-1F-26
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.9

Design
Air
Flow
(L/s)
232

Minimum
Air
Flow
(L/s)
232

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(kW)
0.4

Total
Coil
Load
(kW)
3.0

Sens
Coil
Load
(kW)
2.9

Coil
Entering
DB / WB
(C)
23.7 / 16.8

Coil
Leaving
DB / WB
(C)
13.4 / 12.8

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
232

Fan
Motor
(BHP)
0.058

Zone
Floor
Area
(m)
18.5

Zone
L/(s-m)
12.53

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.046

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-TYPEA-MASTR BED ROM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.9

Jul 1700

232

0.4

18.5

12.53

Page 26 of 81

Zone Sizing Summary for FCU-4F-01


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-01
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.8

Design
Air
Flow
(L/s)
141

Minimum
Air
Flow
(L/s)
141

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.9

Sens
Coil
Load
(kW)
1.8

Coil
Entering
DB / WB
(C)
23.4 / 16.5

Coil
Leaving
DB / WB
(C)
12.9 / 12.2

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
141

Fan
Motor
(BHP)
0.036

Zone
Floor
Area
(m)
18.0

Zone
L/(s-m)
7.85

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.028

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEB- BEDROOM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.8

Aug 1500

141

0.1

18.0

7.85

Page 27 of 81

Zone Sizing Summary for FCU-4F-02


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-02
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.8

Design
Air
Flow
(L/s)
143

Minimum
Air
Flow
(L/s)
143

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.9

Sens
Coil
Load
(kW)
1.8

Coil
Entering
DB / WB
(C)
23.4 / 16.6

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
143

Fan
Motor
(BHP)
0.036

Zone
Floor
Area
(m)
19.0

Zone
L/(s-m)
7.55

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.029

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEB- BEDROOM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.8

Aug 1500

143

0.1

19.0

7.55

Page 28 of 81

Zone Sizing Summary for FCU-4F-03


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-03
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
54.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.3

Design
Air
Flow
(L/s)
511

Minimum
Air
Flow
(L/s)
511

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.5

Total
Coil
Load
(kW)
6.6

Sens
Coil
Load
(kW)
6.3

Coil
Entering
DB / WB
(C)
23.5 / 16.7

Coil
Leaving
DB / WB
(C)
13.3 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
511

Fan
Motor
(BHP)
0.129

Zone
Floor
Area
(m)
54.0

Zone
L/(s-m)
9.47

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.102

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-LVNG-1
FOURTHF-TYPB-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

5.2
1.3

Oct 1500
Jun 1600

408
103

0.4
0.1

40.3
13.7

10.12
7.54

Page 29 of 81

Zone Sizing Summary for FCU-4F-04


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-04
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.7

Design
Air
Flow
(L/s)
133

Minimum
Air
Flow
(L/s)
133

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.0

Total
Coil
Load
(kW)
1.9

Sens
Coil
Load
(kW)
1.7

Coil
Entering
DB / WB
(C)
23.4 / 17.0

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
133

Fan
Motor
(BHP)
0.034

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
5.44

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.027

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-LOBBY
FOURTHF-TYPEB-TELE ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.2
0.5

Jul 1500
Jul 1400

94
40

0.0
0.0

20.0
4.5

4.68
8.81

Page 30 of 81

Zone Sizing Summary for FCU-4F-05


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-05
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.8 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
216

Minimum
Air
Flow
(L/s)
216

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.8

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.8 / 12.2

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
216

Fan
Motor
(BHP)
0.055

Zone
Floor
Area
(m)
18.8

Zone
L/(s-m)
11.51

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Jun 1700

216

0.2

18.8

11.51

Page 31 of 81

Zone Sizing Summary for FCU-4F-06


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-06
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.8

Design
Air
Flow
(L/s)
143

Minimum
Air
Flow
(L/s)
143

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.9

Sens
Coil
Load
(kW)
1.8

Coil
Entering
DB / WB
(C)
23.4 / 16.6

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
143

Fan
Motor
(BHP)
0.036

Zone
Floor
Area
(m)
19.0

Zone
L/(s-m)
7.55

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.029

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEB- BEDROOM-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.8

Aug 1500

143

0.1

19.0

7.55

Page 32 of 81

Zone Sizing Summary for FCU-4F-07


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-07
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
54.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
5.8

Design
Air
Flow
(L/s)
458

Minimum
Air
Flow
(L/s)
458

Time
of
Peak
Load
Jun 1400

Maximum
Heating
Load
(kW)
0.5

Total
Coil
Load
(kW)
6.1

Sens
Coil
Load
(kW)
5.8

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
458

Fan
Motor
(BHP)
0.115

Zone
Floor
Area
(m)
54.0

Zone
L/(s-m)
8.48

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.092

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-LVNG-2
FOURTHF-TYPB-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

4.5
1.3

Jun 1400
Jun 1600

355
103

0.4
0.1

40.3
13.7

8.80
7.54

Page 33 of 81

Zone Sizing Summary for FCU-4F-08


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-08
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
23.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.6

Design
Air
Flow
(L/s)
208

Minimum
Air
Flow
(L/s)
208

Time
of
Peak
Load
Sep 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.7

Sens
Coil
Load
(kW)
2.6

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
208

Fan
Motor
(BHP)
0.052

Zone
Floor
Area
(m)
23.0

Zone
L/(s-m)
9.03

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.042

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-MSTR BDRM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.6

Sep 1500

208

0.2

23.0

9.03

Page 34 of 81

Zone Sizing Summary for FCU-4F-09


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-09
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
23.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.6

Design
Air
Flow
(L/s)
208

Minimum
Air
Flow
(L/s)
208

Time
of
Peak
Load
Sep 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.7

Sens
Coil
Load
(kW)
2.6

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
208

Fan
Motor
(BHP)
0.052

Zone
Floor
Area
(m)
23.0

Zone
L/(s-m)
9.03

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.042

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-MSTR BDRM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.6

Sep 1500

208

0.2

23.0

9.03

Page 35 of 81

Zone Sizing Summary for FCU-4F-10


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-10
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
23.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.5

Design
Air
Flow
(L/s)
195

Minimum
Air
Flow
(L/s)
195

Time
of
Peak
Load
Jun 1400

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.6

Sens
Coil
Load
(kW)
2.5

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
195

Fan
Motor
(BHP)
0.049

Zone
Floor
Area
(m)
23.0

Zone
L/(s-m)
8.48

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.039

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-MSTR BDRM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.5

Jun 1400

195

0.2

23.0

8.48

Page 36 of 81

Zone Sizing Summary for FCU-4F-11


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-11
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
23.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.5

Design
Air
Flow
(L/s)
195

Minimum
Air
Flow
(L/s)
195

Time
of
Peak
Load
Jun 1400

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.6

Sens
Coil
Load
(kW)
2.5

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
195

Fan
Motor
(BHP)
0.049

Zone
Floor
Area
(m)
23.0

Zone
L/(s-m)
8.48

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.039

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-MSTR BDRM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.5

Jun 1400

195

0.2

23.0

8.48

Page 37 of 81

Zone Sizing Summary for FCU-4F-12


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-12
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
54.1 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
7.2

Design
Air
Flow
(L/s)
570

Minimum
Air
Flow
(L/s)
570

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.6

Total
Coil
Load
(kW)
7.5

Sens
Coil
Load
(kW)
7.1

Coil
Entering
DB / WB
(C)
23.6 / 16.8

Coil
Leaving
DB / WB
(C)
13.3 / 12.7

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
570

Fan
Motor
(BHP)
0.144

Zone
Floor
Area
(m)
54.1

Zone
L/(s-m)
10.54

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.114

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-LVNG-1
FOURTHF-TYPA-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

5.9
1.3

Oct 1500
Sep 1400

467
104

0.5
0.1

40.3
13.8

11.58
7.53

Page 38 of 81

Zone Sizing Summary for FCU-4F-13


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-13
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.9

Design
Air
Flow
(L/s)
152

Minimum
Air
Flow
(L/s)
152

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.0

Total
Coil
Load
(kW)
2.2

Sens
Coil
Load
(kW)
1.9

Coil
Entering
DB / WB
(C)
23.5 / 17.0

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
152

Fan
Motor
(BHP)
0.038

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
6.20

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.030

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-LOBBY
FOURTHF-TYPEA- ELEC ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.2
0.7

Jul 1500
Jul 1500

94
58

0.0
0.0

20.0
4.5

4.68
12.93

Page 39 of 81

Zone Sizing Summary for FCU-4F-14


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-14
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
54.1 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
7.2

Design
Air
Flow
(L/s)
570

Minimum
Air
Flow
(L/s)
570

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.6

Total
Coil
Load
(kW)
7.5

Sens
Coil
Load
(kW)
7.1

Coil
Entering
DB / WB
(C)
23.6 / 16.8

Coil
Leaving
DB / WB
(C)
13.3 / 12.7

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
570

Fan
Motor
(BHP)
0.144

Zone
Floor
Area
(m)
54.1

Zone
L/(s-m)
10.54

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.114

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-LVNG-2
FOURTHF-TYPA-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

5.9
1.3

Oct 1500
Sep 1400

467
104

0.5
0.1

40.3
13.8

11.58
7.53

Page 40 of 81

Zone Sizing Summary for FCU-4F-15


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-15
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.8 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
216

Minimum
Air
Flow
(L/s)
216

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.8

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.8 / 12.2

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
216

Fan
Motor
(BHP)
0.055

Zone
Floor
Area
(m)
18.8

Zone
L/(s-m)
11.51

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Jun 1700

216

0.2

18.8

11.51

Page 41 of 81

Zone Sizing Summary for FCU-4F-16


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-16
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.7

Design
Air
Flow
(L/s)
138

Minimum
Air
Flow
(L/s)
138

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.8

Sens
Coil
Load
(kW)
1.7

Coil
Entering
DB / WB
(C)
23.4 / 16.4

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
138

Fan
Motor
(BHP)
0.035

Zone
Floor
Area
(m)
18.0

Zone
L/(s-m)
7.64

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.028

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.7

Jul 1500

138

0.1

18.0

7.64

Page 42 of 81

Zone Sizing Summary for FCU-4F-17


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-17
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.8 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
216

Minimum
Air
Flow
(L/s)
216

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.8

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.8 / 12.2

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
216

Fan
Motor
(BHP)
0.055

Zone
Floor
Area
(m)
18.8

Zone
L/(s-m)
11.51

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Jun 1700

216

0.2

18.8

11.51

Page 43 of 81

Zone Sizing Summary for FCU-4F-18


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-4F-18
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.7

Design
Air
Flow
(L/s)
138

Minimum
Air
Flow
(L/s)
138

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.8

Sens
Coil
Load
(kW)
1.7

Coil
Entering
DB / WB
(C)
23.4 / 16.4

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
138

Fan
Motor
(BHP)
0.035

Zone
Floor
Area
(m)
18.0

Zone
L/(s-m)
7.64

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.028

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.7

Jul 1500

138

0.1

18.0

7.64

Page 44 of 81

Zone Sizing Summary for FCU-GF-01


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-01
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
42.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
5.9

Design
Air
Flow
(L/s)
464

Minimum
Air
Flow
(L/s)
464

Time
of
Peak
Load
Aug 1900

Maximum
Heating
Load
(kW)
0.7

Total
Coil
Load
(kW)
6.1

Sens
Coil
Load
(kW)
5.8

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
464

Fan
Motor
(BHP)
0.117

Zone
Floor
Area
(m)
42.6

Zone
L/(s-m)
10.90

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.093

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-SHOP-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

5.9

Aug 1900

464

0.7

42.6

10.90

Page 45 of 81

Zone Sizing Summary for FCU-GF-02


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-02
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
58.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.4

Design
Air
Flow
(L/s)
506

Minimum
Air
Flow
(L/s)
506

Time
of
Peak
Load
Sep 1100

Maximum
Heating
Load
(kW)
0.6

Total
Coil
Load
(kW)
7.4

Sens
Coil
Load
(kW)
6.5

Coil
Entering
DB / WB
(C)
23.5 / 16.9

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
506

Fan
Motor
(BHP)
0.128

Zone
Floor
Area
(m)
58.6

Zone
L/(s-m)
8.64

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1100

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.101

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-SHOP-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

6.4

Sep 1100

506

0.6

58.6

8.64

Page 46 of 81

Zone Sizing Summary for FCU-GF-03


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-03
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
58.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
6.3

Design
Air
Flow
(L/s)
496

Minimum
Air
Flow
(L/s)
496

Time
of
Peak
Load
Oct 1100

Maximum
Heating
Load
(kW)
0.5

Total
Coil
Load
(kW)
7.3

Sens
Coil
Load
(kW)
6.3

Coil
Entering
DB / WB
(C)
23.5 / 16.9

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
496

Fan
Motor
(BHP)
0.125

Zone
Floor
Area
(m)
58.6

Zone
L/(s-m)
8.47

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1100

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.099

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-SHOP-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

6.3

Oct 1100

496

0.5

58.6

8.47

Page 47 of 81

Zone Sizing Summary for FCU-GF-04


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-04
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
6.1 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.1

Design
Air
Flow
(L/s)
86

Minimum
Air
Flow
(L/s)
86

Time
of
Peak
Load
Aug 1600

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.1

Sens
Coil
Load
(kW)
1.1

Coil
Entering
DB / WB
(C)
23.4 / 16.5

Coil
Leaving
DB / WB
(C)
13.1 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
86

Fan
Motor
(BHP)
0.022

Zone
Floor
Area
(m)
6.1

Zone
L/(s-m)
14.10

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.017

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-WATCHMAN ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.1

Aug 1600

86

0.1

6.1

14.10

Page 48 of 81

Zone Sizing Summary for FCU-GF-05


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-05
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
12.7 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.1

Design
Air
Flow
(L/s)
88

Minimum
Air
Flow
(L/s)
88

Time
of
Peak
Load
Aug 1900

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
1.2

Sens
Coil
Load
(kW)
1.1

Coil
Entering
DB / WB
(C)
23.4 / 16.9

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
88

Fan
Motor
(BHP)
0.022

Zone
Floor
Area
(m)
12.7

Zone
L/(s-m)
6.95

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 2000

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.018

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-GARBAGE ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.1

Aug 1900

88

0.2

12.7

6.95

Page 49 of 81

Zone Sizing Summary for FCU-GF-06


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-06
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
23.8 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
3.9

Design
Air
Flow
(L/s)
309

Minimum
Air
Flow
(L/s)
309

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(kW)
0.6

Total
Coil
Load
(kW)
4.0

Sens
Coil
Load
(kW)
3.9

Coil
Entering
DB / WB
(C)
23.7 / 16.7

Coil
Leaving
DB / WB
(C)
13.3 / 12.7

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
309

Fan
Motor
(BHP)
0.078

Zone
Floor
Area
(m)
23.8

Zone
L/(s-m)
12.99

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.062

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-LV ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

3.9

Jul 1600

309

0.6

23.8

12.99

Page 50 of 81

Zone Sizing Summary for FCU-GF-07+08


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-07+08
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
72.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
9.6

Design
Air
Flow
(L/s)
757

Minimum
Air
Flow
(L/s)
757

Time
of
Peak
Load
Aug 1600

Maximum
Heating
Load
(kW)
1.3

Total
Coil
Load
(kW)
10.4

Sens
Coil
Load
(kW)
9.5

Coil
Entering
DB / WB
(C)
23.5 / 16.8

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
757

Fan
Motor
(BHP)
0.191

Zone
Floor
Area
(m)
72.0

Zone
L/(s-m)
10.51

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.151

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-ENTRANCE LOBBY

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

9.6

Aug 1600

757

1.3

72.0

10.51

Page 51 of 81

Zone Sizing Summary for FCU-GF-09


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-GF-09
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
7.1 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.8

Design
Air
Flow
(L/s)
143

Minimum
Air
Flow
(L/s)
143

Time
of
Peak
Load
Aug 2000

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
1.8

Sens
Coil
Load
(kW)
1.8

Coil
Entering
DB / WB
(C)
23.7 / 7.6

Coil
Leaving
DB / WB
(C)
13.3 / 2.2

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
143

Fan
Motor
(BHP)
0.036

Zone
Floor
Area
(m)
7.1

Zone
L/(s-m)
20.16

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 2000

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.029

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-TELECOM ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.8

Aug 2000

143

0.1

7.1

20.16

Page 52 of 81

Zone Sizing Summary for FCU-RF-01


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-RF-01
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.5

Design
Air
Flow
(L/s)
204

Minimum
Air
Flow
(L/s)
204

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
2.6

Sens
Coil
Load
(kW)
2.5

Coil
Entering
DB / WB
(C)
23.4 / 16.6

Coil
Leaving
DB / WB
(C)
13.3 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
204

Fan
Motor
(BHP)
0.051

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
8.34

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.041

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
ROOF-LOBBY
ROOF FLOOR-ELC ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.5
1.1

Jul 1500
Aug 2000

118
86

0.1
0.1

20.0
4.5

5.90
19.17

Page 53 of 81

Zone Sizing Summary for FCU-RF-02+03


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-RF-02+03
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
68.0 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
15.4

Design
Air
Flow
(L/s)
1212

Minimum
Air
Flow
(L/s)
1212

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(kW)
1.6

Total
Coil
Load
(kW)
21.0

Sens
Coil
Load
(kW)
15.2

Coil
Entering
DB / WB
(C)
23.7 / 18.0

Coil
Leaving
DB / WB
(C)
13.3 / 12.8

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
1212

Fan
Motor
(BHP)
0.306

Zone
Floor
Area
(m)
68.0

Zone
L/(s-m)
17.82

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.242

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
ROOF FLOOR GYM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

15.4

Jul 1600

1212

1.6

68.0

17.82

Page 54 of 81

Zone Sizing Summary for FCU-TF-01


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-01
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
16.3 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.2

Design
Air
Flow
(L/s)
170

Minimum
Air
Flow
(L/s)
170

Time
of
Peak
Load
Oct 1200

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.3

Sens
Coil
Load
(kW)
2.1

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
170

Fan
Motor
(BHP)
0.043

Zone
Floor
Area
(m)
16.3

Zone
L/(s-m)
10.44

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.034

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEC-MASTR BED RM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.2

Oct 1200

170

0.1

16.3

10.44

Page 55 of 81

Zone Sizing Summary for FCU-TF-02


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-02
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
51.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.6

Design
Air
Flow
(L/s)
371

Minimum
Air
Flow
(L/s)
371

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.0

Sens
Coil
Load
(kW)
4.6

Coil
Entering
DB / WB
(C)
23.4 / 16.7

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
371

Fan
Motor
(BHP)
0.093

Zone
Floor
Area
(m)
51.5

Zone
L/(s-m)
7.20

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.074

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEC- LIVING ROOM-1
TYP-TYPEC-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.6
1.1

Oct 1100
Oct 1600

283
88

0.2
0.1

43.0
8.5

6.57
10.36

Page 56 of 81

Zone Sizing Summary for FCU-TF-03


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-03
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
13.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.9

Design
Air
Flow
(L/s)
152

Minimum
Air
Flow
(L/s)
152

Time
of
Peak
Load
Oct 1100

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.0

Sens
Coil
Load
(kW)
1.9

Coil
Entering
DB / WB
(C)
23.4 / 16.4

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
152

Fan
Motor
(BHP)
0.038

Zone
Floor
Area
(m)
13.5

Zone
L/(s-m)
11.27

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Nov 1200

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.030

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEC- BED R0OM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.9

Oct 1100

152

0.1

13.5

11.27

Page 57 of 81

Zone Sizing Summary for FCU-TF-04


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-04
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
51.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.6

Design
Air
Flow
(L/s)
371

Minimum
Air
Flow
(L/s)
371

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.0

Sens
Coil
Load
(kW)
4.6

Coil
Entering
DB / WB
(C)
23.4 / 16.7

Coil
Leaving
DB / WB
(C)
13.1 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
371

Fan
Motor
(BHP)
0.093

Zone
Floor
Area
(m)
51.5

Zone
L/(s-m)
7.20

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.074

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEC- LIVING ROOM-2
TYP-TYPEC-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.6
1.1

Oct 1100
Oct 1600

283
88

0.2
0.1

43.0
8.5

6.57
10.36

Page 58 of 81

Zone Sizing Summary for FCU-TF-05


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-05
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
13.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.9

Design
Air
Flow
(L/s)
152

Minimum
Air
Flow
(L/s)
152

Time
of
Peak
Load
Oct 1100

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.0

Sens
Coil
Load
(kW)
1.9

Coil
Entering
DB / WB
(C)
23.4 / 16.4

Coil
Leaving
DB / WB
(C)
13.0 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
152

Fan
Motor
(BHP)
0.038

Zone
Floor
Area
(m)
13.5

Zone
L/(s-m)
11.27

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Nov 1200

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.030

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEC- BED R0OM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1.9

Oct 1100

152

0.1

13.5

11.27

Page 59 of 81

Zone Sizing Summary for FCU-TF-06


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-06
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
16.3 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.2

Design
Air
Flow
(L/s)
170

Minimum
Air
Flow
(L/s)
170

Time
of
Peak
Load
Oct 1200

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.3

Sens
Coil
Load
(kW)
2.1

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
170

Fan
Motor
(BHP)
0.043

Zone
Floor
Area
(m)
16.3

Zone
L/(s-m)
10.44

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.034

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEC-MASTR BED RM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.2

Oct 1200

170

0.1

16.3

10.44

Page 60 of 81

Zone Sizing Summary for FCU-TF-07


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-07
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.9

Design
Air
Flow
(L/s)
391

Minimum
Air
Flow
(L/s)
391

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.2

Sens
Coil
Load
(kW)
4.9

Coil
Entering
DB / WB
(C)
23.5 / 16.7

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
391

Fan
Motor
(BHP)
0.098

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
8.98

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.078

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-1
TYP-TYPEB-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.9
1.1

Oct 1500
Jun 1700

305
85

0.2
0.1

35.0
8.5

8.72
10.04

Page 61 of 81

Zone Sizing Summary for FCU-TF-08


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-08
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
161

Minimum
Air
Flow
(L/s)
161

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.1

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.7 / 12.1

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
161

Fan
Motor
(BHP)
0.041

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
11.13

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Oct 1500

161

0.1

14.5

11.13

Page 62 of 81

Zone Sizing Summary for FCU-TF-09


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-09
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.6

Design
Air
Flow
(L/s)
128

Minimum
Air
Flow
(L/s)
128

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.0

Total
Coil
Load
(kW)
1.9

Sens
Coil
Load
(kW)
1.6

Coil
Entering
DB / WB
(C)
23.5 / 17.1

Coil
Leaving
DB / WB
(C)
13.2 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
128

Fan
Motor
(BHP)
0.032

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
5.22

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.026

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-LOBBY
TYP-TYPEB- TELE. ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.2
0.4

Jul 1500
Jan 2300

94
34

0.0
0.0

20.0
4.5

4.68
7.58

Page 63 of 81

Zone Sizing Summary for FCU-TF-10


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-10
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
161

Minimum
Air
Flow
(L/s)
161

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.1

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.7 / 12.1

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
161

Fan
Motor
(BHP)
0.041

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
11.13

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Oct 1500

161

0.1

14.5

11.13

Page 64 of 81

Zone Sizing Summary for FCU-TF-11


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-11
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.9

Design
Air
Flow
(L/s)
391

Minimum
Air
Flow
(L/s)
391

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.2

Sens
Coil
Load
(kW)
4.9

Coil
Entering
DB / WB
(C)
23.5 / 16.7

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
391

Fan
Motor
(BHP)
0.098

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
8.98

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.078

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-2
TYP-TYPEB-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.9
1.1

Oct 1500
Jun 1700

305
85

0.2
0.1

35.0
8.5

8.72
10.04

Page 65 of 81

Zone Sizing Summary for FCU-TF-12


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-12
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
214

Minimum
Air
Flow
(L/s)
214

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.7

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
214

Fan
Motor
(BHP)
0.054

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
10.94

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Sep 1600

214

0.1

19.6

10.94

Page 66 of 81

Zone Sizing Summary for FCU-TF-13


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-13
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
214

Minimum
Air
Flow
(L/s)
214

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.7

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
214

Fan
Motor
(BHP)
0.054

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
10.94

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Sep 1600

214

0.1

19.6

10.94

Page 67 of 81

Zone Sizing Summary for FCU-TF-14


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-14
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
214

Minimum
Air
Flow
(L/s)
214

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.7

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
214

Fan
Motor
(BHP)
0.054

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
10.94

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Sep 1600

214

0.1

19.6

10.94

Page 68 of 81

Zone Sizing Summary for FCU-TF-15


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-15
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
19.6 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.7

Design
Air
Flow
(L/s)
214

Minimum
Air
Flow
(L/s)
214

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.8

Sens
Coil
Load
(kW)
2.7

Coil
Entering
DB / WB
(C)
23.5 / 16.6

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
214

Fan
Motor
(BHP)
0.054

Zone
Floor
Area
(m)
19.6

Zone
L/(s-m)
10.94

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.043

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.7

Sep 1600

214

0.1

19.6

10.94

Page 69 of 81

Zone Sizing Summary for FCU-TF-16


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-16
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.9

Design
Air
Flow
(L/s)
391

Minimum
Air
Flow
(L/s)
391

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.2

Sens
Coil
Load
(kW)
4.9

Coil
Entering
DB / WB
(C)
23.5 / 16.7

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
391

Fan
Motor
(BHP)
0.098

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
8.98

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.078

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-4
TYP-TYPEB-KITCHEN-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.9
1.1

Oct 1500
Jun 1700

305
85

0.2
0.1

35.0
8.5

8.72
10.04

Page 70 of 81

Zone Sizing Summary for FCU-TF-17


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-17
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
161

Minimum
Air
Flow
(L/s)
161

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.1

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.7 / 12.1

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
161

Fan
Motor
(BHP)
0.041

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
11.13

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-4

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Oct 1500

161

0.1

14.5

11.13

Page 71 of 81

Zone Sizing Summary for FCU-TF-18


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-18
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
43.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.9

Design
Air
Flow
(L/s)
391

Minimum
Air
Flow
(L/s)
391

Time
of
Peak
Load
Sep 1600

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.2

Sens
Coil
Load
(kW)
4.9

Coil
Entering
DB / WB
(C)
23.5 / 16.7

Coil
Leaving
DB / WB
(C)
13.2 / 12.5

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
391

Fan
Motor
(BHP)
0.098

Zone
Floor
Area
(m)
43.5

Zone
L/(s-m)
8.98

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Sep 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.078

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-3
TYP-TYPEB-KITCHEN-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.9
1.1

Oct 1500
Jun 1700

305
85

0.2
0.1

35.0
8.5

8.72
10.04

Page 72 of 81

Zone Sizing Summary for FCU-TF-19


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-19
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
161

Minimum
Air
Flow
(L/s)
161

Time
of
Peak
Load
Oct 1500

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.1

Coil
Entering
DB / WB
(C)
23.4 / 16.3

Coil
Leaving
DB / WB
(C)
12.7 / 12.1

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
161

Fan
Motor
(BHP)
0.041

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
11.13

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Oct 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-3

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Oct 1500

161

0.1

14.5

11.13

Page 73 of 81

Zone Sizing Summary for FCU-TF-20


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-20
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
24.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
1.7

Design
Air
Flow
(L/s)
136

Minimum
Air
Flow
(L/s)
136

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(kW)
0.0

Total
Coil
Load
(kW)
2.0

Sens
Coil
Load
(kW)
1.7

Coil
Entering
DB / WB
(C)
23.4 / 16.9

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
136

Fan
Motor
(BHP)
0.034

Zone
Floor
Area
(m)
24.5

Zone
L/(s-m)
5.57

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.027

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-LOBBY
TYP-TYPEB- ELECT. ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

1.2
0.5

Jul 1500
Jan 2300

94
43

0.0
0.0

20.0
4.5

4.68
9.51

Page 74 of 81

Zone Sizing Summary for FCU-TF-21


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-21
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.3

Design
Air
Flow
(L/s)
180

Minimum
Air
Flow
(L/s)
180

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.4

Sens
Coil
Load
(kW)
2.3

Coil
Entering
DB / WB
(C)
23.6 / 16.7

Coil
Leaving
DB / WB
(C)
13.3 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
180

Fan
Motor
(BHP)
0.045

Zone
Floor
Area
(m)
18.5

Zone
L/(s-m)
9.73

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.036

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEA-MASTR BD ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.3

Jun 1700

180

0.1

18.5

9.73

Page 75 of 81

Zone Sizing Summary for FCU-TF-22


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-22
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
159

Minimum
Air
Flow
(L/s)
159

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.0

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
159

Fan
Motor
(BHP)
0.040

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
10.95

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEA- BED ROOM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Jun 1700

159

0.1

14.5

10.95

Page 76 of 81

Zone Sizing Summary for FCU-TF-23


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-23
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
49.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.6

Design
Air
Flow
(L/s)
364

Minimum
Air
Flow
(L/s)
364

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.2

Sens
Coil
Load
(kW)
4.6

Coil
Entering
DB / WB
(C)
23.4 / 16.7

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
364

Fan
Motor
(BHP)
0.092

Zone
Floor
Area
(m)
49.5

Zone
L/(s-m)
7.35

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.073

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEA- LIVING R0OM-1
TYP-TYPEA-KITCHEN-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.6
1.0

Jun 1700
Oct 1600

286
79

0.2
0.0

41.5
8.0

6.88
9.82

Page 77 of 81

Zone Sizing Summary for FCU-TF-24


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-24
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
49.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4.6

Design
Air
Flow
(L/s)
364

Minimum
Air
Flow
(L/s)
364

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.2

Total
Coil
Load
(kW)
5.2

Sens
Coil
Load
(kW)
4.6

Coil
Entering
DB / WB
(C)
23.4 / 16.7

Coil
Leaving
DB / WB
(C)
12.9 / 12.3

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
364

Fan
Motor
(BHP)
0.092

Zone
Floor
Area
(m)
49.5

Zone
L/(s-m)
7.35

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.073

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEA- LIVING R0OM-2
TYP-TYPEA-KITCHEN-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

3.6
1.0

Jun 1700
Oct 1600

286
79

0.2
0.0

41.5
8.0

6.88
9.82

Page 78 of 81

Zone Sizing Summary for FCU-TF-25


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-25
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
14.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.0

Design
Air
Flow
(L/s)
159

Minimum
Air
Flow
(L/s)
159

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.1

Sens
Coil
Load
(kW)
2.0

Coil
Entering
DB / WB
(C)
23.5 / 16.5

Coil
Leaving
DB / WB
(C)
13.0 / 12.4

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
159

Fan
Motor
(BHP)
0.040

Zone
Floor
Area
(m)
14.5

Zone
L/(s-m)
10.95

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.032

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEA- BED ROOM-2

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.0

Jun 1700

159

0.1

14.5

10.95

Page 79 of 81

Zone Sizing Summary for FCU-TF-26


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-TF-26
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
18.5 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.3

Design
Air
Flow
(L/s)
180

Minimum
Air
Flow
(L/s)
180

Time
of
Peak
Load
Jun 1700

Maximum
Heating
Load
(kW)
0.1

Total
Coil
Load
(kW)
2.4

Sens
Coil
Load
(kW)
2.3

Coil
Entering
DB / WB
(C)
23.6 / 16.7

Coil
Leaving
DB / WB
(C)
13.3 / 12.6

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
180

Fan
Motor
(BHP)
0.045

Zone
Floor
Area
(m)
18.5

Zone
L/(s-m)
9.73

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jun 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.036

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
TYP-TYPEA-MASTR BD ROM-1

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.3

Jun 1700

180

0.1

18.5

9.73

Page 80 of 81

Zone Sizing Summary for FCU-UG-01


Project Name: G+4-SAGE
Prepared by: CEC

10-30-2015
06:14PM

Air System Information


Air System Name
Equipment Class
Air System Type

FCU-UG-01
TERM
SPLT-FC

Number of zones
Floor Area
Location

1
44.4 m
Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s
Space L/s

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
2.4

Design
Air
Flow
(L/s)
190

Minimum
Air
Flow
(L/s)
190

Time
of
Peak
Load
Jul 1400

Maximum
Heating
Load
(kW)
0.3

Total
Coil
Load
(kW)
2.4

Sens
Coil
Load
(kW)
2.4

Coil
Entering
DB / WB
(C)
23.4 / 7.5

Coil
Leaving
DB / WB
(C)
12.8 / 2.0

Water
Flow
@ 5.6 K
(L/s)
-

Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3

Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00

Fan
Design
AirFlow
(L/s)
190

Fan
Motor
(BHP)
0.048

Zone
Floor
Area
(m)
44.4

Zone
L/(s-m)
4.28

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Fan
Motor
(kW)
0.038

OA Vent
Design
AirFlow
(L/s)
0

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
UG - PUMP ROOM

Hourly Analysis Program v4.70

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

2.4

Jul 1400

190

0.3

44.4

4.28

Page 81 of 81