10-30-2015
06:14PM
FCU-1F-01
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
16.3 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
215
Minimum
Air
Flow
(L/s)
215
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.7
Coil
Entering
DB / WB
(C)
23.4 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
215
Fan
Motor
(BHP)
0.054
Zone
Floor
Area
(m)
16.3
Zone
L/(s-m)
13.17
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEC-MASTR BED ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Aug 1500
215
0.3
16.3
13.17
Page 1 of 81
10-30-2015
06:14PM
FCU-1F-02
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
51.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.3
Design
Air
Flow
(L/s)
497
Minimum
Air
Flow
(L/s)
497
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.9
Total
Coil
Load
(kW)
6.6
Sens
Coil
Load
(kW)
6.3
Coil
Entering
DB / WB
(C)
23.4 / 16.5
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
497
Fan
Motor
(BHP)
0.125
Zone
Floor
Area
(m)
51.5
Zone
L/(s-m)
9.65
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.099
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEC- LIVING ROOM-1
FF-TYPEC-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
4.9
1.4
Aug 1500
Sep 1600
386
111
0.7
0.2
43.0
8.5
8.98
13.03
Page 2 of 81
10-30-2015
06:14PM
FCU-1F-03
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
13.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.4
Design
Air
Flow
(L/s)
188
Minimum
Air
Flow
(L/s)
188
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.4
Sens
Coil
Load
(kW)
2.3
Coil
Entering
DB / WB
(C)
23.6 / 16.7
Coil
Leaving
DB / WB
(C)
13.4 / 12.7
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
188
Fan
Motor
(BHP)
0.047
Zone
Floor
Area
(m)
13.5
Zone
L/(s-m)
13.94
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.038
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEC- BED R0OM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.4
Aug 1500
188
0.3
13.5
13.94
Page 3 of 81
10-30-2015
06:14PM
FCU-1F-04
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
51.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.2
Design
Air
Flow
(L/s)
493
Minimum
Air
Flow
(L/s)
493
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.9
Total
Coil
Load
(kW)
6.4
Sens
Coil
Load
(kW)
6.1
Coil
Entering
DB / WB
(C)
23.6 / 16.7
Coil
Leaving
DB / WB
(C)
13.3 / 12.7
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
493
Fan
Motor
(BHP)
0.124
Zone
Floor
Area
(m)
51.5
Zone
L/(s-m)
9.57
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.099
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEC- LIVING ROOM-2
FF-TYPEC-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
4.9
1.3
Aug 1500
Jul 1500
386
106
0.7
0.2
43.0
8.5
8.98
12.52
Page 4 of 81
10-30-2015
06:14PM
FCU-1F-05
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
13.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.4
Design
Air
Flow
(L/s)
188
Minimum
Air
Flow
(L/s)
188
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.4
Sens
Coil
Load
(kW)
2.3
Coil
Entering
DB / WB
(C)
23.6 / 16.7
Coil
Leaving
DB / WB
(C)
13.4 / 12.7
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
188
Fan
Motor
(BHP)
0.047
Zone
Floor
Area
(m)
13.5
Zone
L/(s-m)
13.94
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.038
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEC- BED R0OM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.4
Aug 1500
188
0.3
13.5
13.94
Page 5 of 81
10-30-2015
06:14PM
FCU-1F-06
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
16.3 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
215
Minimum
Air
Flow
(L/s)
215
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.7
Coil
Entering
DB / WB
(C)
23.4 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
215
Fan
Motor
(BHP)
0.054
Zone
Floor
Area
(m)
16.3
Zone
L/(s-m)
13.17
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEC-MASTR BED ROM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Aug 1500
215
0.3
16.3
13.17
Page 6 of 81
10-30-2015
06:14PM
FCU-1F-07
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.4
Design
Air
Flow
(L/s)
186
Minimum
Air
Flow
(L/s)
186
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.4
Sens
Coil
Load
(kW)
2.3
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
186
Fan
Motor
(BHP)
0.047
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
12.86
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.037
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.4
Sep 1600
186
0.2
14.5
12.86
Page 7 of 81
10-30-2015
06:14PM
FCU-1F-08
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.4
Design
Air
Flow
(L/s)
510
Minimum
Air
Flow
(L/s)
510
Time
of
Peak
Load
Aug 1600
Maximum
Heating
Load
(kW)
0.8
Total
Coil
Load
(kW)
6.7
Sens
Coil
Load
(kW)
6.4
Coil
Entering
DB / WB
(C)
23.4 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
510
Fan
Motor
(BHP)
0.129
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
11.73
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.102
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-1
FF-TYPEB-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
5.1
1.4
Sep 1600
Jul 1700
401
109
0.6
0.2
35.0
8.5
11.46
12.83
Page 8 of 81
10-30-2015
06:14PM
FCU-1F-09
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.8
Design
Air
Flow
(L/s)
141
Minimum
Air
Flow
(L/s)
141
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.0
Sens
Coil
Load
(kW)
1.7
Coil
Entering
DB / WB
(C)
23.5 / 17.1
Coil
Leaving
DB / WB
(C)
13.2 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
141
Fan
Motor
(BHP)
0.036
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
5.76
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.028
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-LOBBY
FF-TYPEB- TELE. ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.2
0.6
Jul 1500
Jul 1500
94
47
0.0
0.1
20.0
4.5
4.68
10.53
Page 9 of 81
10-30-2015
06:14PM
FCU-1F-10
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
162
Minimum
Air
Flow
(L/s)
162
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.0
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
162
Fan
Motor
(BHP)
0.041
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
11.15
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Jul 1500
162
0.2
14.5
11.15
Page 10 of 81
10-30-2015
06:14PM
FCU-1F-11
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
5.8
Design
Air
Flow
(L/s)
459
Minimum
Air
Flow
(L/s)
459
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.8
Total
Coil
Load
(kW)
6.0
Sens
Coil
Load
(kW)
5.7
Coil
Entering
DB / WB
(C)
23.6 / 16.8
Coil
Leaving
DB / WB
(C)
13.4 / 12.8
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
459
Fan
Motor
(BHP)
0.116
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
10.55
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.092
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-2
FF-TYPEB-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
4.4
1.4
Jul 1500
Jul 1700
350
109
0.6
0.2
35.0
8.5
9.99
12.83
Page 11 of 81
10-30-2015
06:14PM
FCU-1F-12
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
3.2
Design
Air
Flow
(L/s)
256
Minimum
Air
Flow
(L/s)
256
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.4
Total
Coil
Load
(kW)
3.3
Sens
Coil
Load
(kW)
3.2
Coil
Entering
DB / WB
(C)
23.4 / 16.4
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
256
Fan
Motor
(BHP)
0.065
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
13.06
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.051
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.2
Jul 1500
256
0.4
19.6
13.06
Page 12 of 81
10-30-2015
06:14PM
FCU-1F-13
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
3.4
Design
Air
Flow
(L/s)
268
Minimum
Air
Flow
(L/s)
268
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.4
Total
Coil
Load
(kW)
3.5
Sens
Coil
Load
(kW)
3.3
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
268
Fan
Motor
(BHP)
0.068
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
13.70
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.054
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.4
Sep 1600
268
0.4
19.6
13.70
Page 13 of 81
10-30-2015
06:14PM
FCU-1F-14
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
3.4
Design
Air
Flow
(L/s)
268
Minimum
Air
Flow
(L/s)
268
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.4
Total
Coil
Load
(kW)
3.5
Sens
Coil
Load
(kW)
3.3
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
268
Fan
Motor
(BHP)
0.068
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
13.70
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.054
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.4
Sep 1600
268
0.4
19.6
13.70
Page 14 of 81
10-30-2015
06:14PM
FCU-1F-15
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
3.2
Design
Air
Flow
(L/s)
256
Minimum
Air
Flow
(L/s)
256
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.4
Total
Coil
Load
(kW)
3.3
Sens
Coil
Load
(kW)
3.2
Coil
Entering
DB / WB
(C)
23.4 / 16.4
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
256
Fan
Motor
(BHP)
0.065
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
13.06
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.051
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB-MASTR BED ROM-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.2
Jul 1500
256
0.4
19.6
13.06
Page 15 of 81
10-30-2015
06:14PM
FCU-1F-16
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
5.8
Design
Air
Flow
(L/s)
456
Minimum
Air
Flow
(L/s)
456
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.8
Total
Coil
Load
(kW)
6.0
Sens
Coil
Load
(kW)
5.7
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
456
Fan
Motor
(BHP)
0.115
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
10.49
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.091
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-4
FF-TYPEB-KITCHEN-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
4.4
1.3
Jul 1500
Aug 1500
350
107
0.6
0.2
35.0
8.5
9.99
12.53
Page 16 of 81
10-30-2015
06:14PM
FCU-1F-17
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
162
Minimum
Air
Flow
(L/s)
162
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.0
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
162
Fan
Motor
(BHP)
0.041
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
11.15
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Jul 1500
162
0.2
14.5
11.15
Page 17 of 81
10-30-2015
06:14PM
FCU-1F-18
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
5.8
Design
Air
Flow
(L/s)
456
Minimum
Air
Flow
(L/s)
456
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.8
Total
Coil
Load
(kW)
6.0
Sens
Coil
Load
(kW)
5.7
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
456
Fan
Motor
(BHP)
0.115
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
10.49
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.091
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- LIVING R0OM-3
FF-TYPEB-KITCHEN-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
4.4
1.3
Jul 1500
Aug 1500
350
107
0.6
0.2
35.0
8.5
9.99
12.53
Page 18 of 81
10-30-2015
06:14PM
FCU-1F-19
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.3
Design
Air
Flow
(L/s)
178
Minimum
Air
Flow
(L/s)
178
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.3
Sens
Coil
Load
(kW)
2.2
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
178
Fan
Motor
(BHP)
0.045
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
12.30
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.036
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEB- BED ROOM-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.3
Sep 1600
178
0.2
14.5
12.30
Page 19 of 81
10-30-2015
06:14PM
FCU-1F-20
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.8
Design
Air
Flow
(L/s)
146
Minimum
Air
Flow
(L/s)
146
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
1.8
Coil
Entering
DB / WB
(C)
23.4 / 17.0
Coil
Leaving
DB / WB
(C)
13.2 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
146
Fan
Motor
(BHP)
0.037
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
5.95
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.029
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-LOBBY
FF-TYPEB- ELECT. ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.2
0.7
Jul 1500
Jul 1500
94
52
0.0
0.1
20.0
4.5
4.68
11.58
Page 20 of 81
10-30-2015
06:14PM
FCU-1F-21
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.9
Design
Air
Flow
(L/s)
232
Minimum
Air
Flow
(L/s)
232
Time
of
Peak
Load
Jul 1700
Maximum
Heating
Load
(kW)
0.4
Total
Coil
Load
(kW)
3.0
Sens
Coil
Load
(kW)
2.9
Coil
Entering
DB / WB
(C)
23.7 / 16.8
Coil
Leaving
DB / WB
(C)
13.4 / 12.8
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
232
Fan
Motor
(BHP)
0.058
Zone
Floor
Area
(m)
18.5
Zone
L/(s-m)
12.53
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.046
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEA-MASTR BED ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.9
Jul 1700
232
0.4
18.5
12.53
Page 21 of 81
10-30-2015
06:14PM
FCU-1F-22
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.6
Design
Air
Flow
(L/s)
204
Minimum
Air
Flow
(L/s)
204
Time
of
Peak
Load
Jul 1700
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.6
Sens
Coil
Load
(kW)
2.5
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
204
Fan
Motor
(BHP)
0.051
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
14.05
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.041
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEA- BED ROOM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.6
Jul 1700
204
0.3
14.5
14.05
Page 22 of 81
10-30-2015
06:14PM
FCU-1F-23
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
49.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.3
Design
Air
Flow
(L/s)
503
Minimum
Air
Flow
(L/s)
503
Time
of
Peak
Load
Jul 1600
Maximum
Heating
Load
(kW)
0.9
Total
Coil
Load
(kW)
6.8
Sens
Coil
Load
(kW)
6.3
Coil
Entering
DB / WB
(C)
23.5 / 16.7
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
503
Fan
Motor
(BHP)
0.127
Zone
Floor
Area
(m)
49.5
Zone
L/(s-m)
10.16
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.101
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEA- LIVING R0OM-1
FF-TYPEA-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
5.1
1.3
Jul 1600
Sep 1600
403
100
0.7
0.1
41.5
8.0
9.71
12.51
Page 23 of 81
10-30-2015
06:14PM
FCU-1F-24
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
49.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.3
Design
Air
Flow
(L/s)
496
Minimum
Air
Flow
(L/s)
496
Time
of
Peak
Load
Jul 1600
Maximum
Heating
Load
(kW)
0.9
Total
Coil
Load
(kW)
6.6
Sens
Coil
Load
(kW)
6.2
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
496
Fan
Motor
(BHP)
0.125
Zone
Floor
Area
(m)
49.5
Zone
L/(s-m)
10.02
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.099
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEA- LIVING R0OM-2
FF-TYPEA-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
5.0
1.3
Jul 1600
Jul 1500
391
105
0.7
0.1
41.5
8.0
9.42
13.15
Page 24 of 81
10-30-2015
06:14PM
FCU-1F-25
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.6
Design
Air
Flow
(L/s)
204
Minimum
Air
Flow
(L/s)
204
Time
of
Peak
Load
Jul 1700
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.6
Sens
Coil
Load
(kW)
2.5
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
204
Fan
Motor
(BHP)
0.051
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
14.05
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.041
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEA- BED ROOM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.6
Jul 1700
204
0.3
14.5
14.05
Page 25 of 81
10-30-2015
06:14PM
FCU-1F-26
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.9
Design
Air
Flow
(L/s)
232
Minimum
Air
Flow
(L/s)
232
Time
of
Peak
Load
Jul 1700
Maximum
Heating
Load
(kW)
0.4
Total
Coil
Load
(kW)
3.0
Sens
Coil
Load
(kW)
2.9
Coil
Entering
DB / WB
(C)
23.7 / 16.8
Coil
Leaving
DB / WB
(C)
13.4 / 12.8
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
232
Fan
Motor
(BHP)
0.058
Zone
Floor
Area
(m)
18.5
Zone
L/(s-m)
12.53
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.046
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FF-TYPEA-MASTR BED ROM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.9
Jul 1700
232
0.4
18.5
12.53
Page 26 of 81
10-30-2015
06:14PM
FCU-4F-01
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.8
Design
Air
Flow
(L/s)
141
Minimum
Air
Flow
(L/s)
141
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.9
Sens
Coil
Load
(kW)
1.8
Coil
Entering
DB / WB
(C)
23.4 / 16.5
Coil
Leaving
DB / WB
(C)
12.9 / 12.2
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
141
Fan
Motor
(BHP)
0.036
Zone
Floor
Area
(m)
18.0
Zone
L/(s-m)
7.85
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.028
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEB- BEDROOM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.8
Aug 1500
141
0.1
18.0
7.85
Page 27 of 81
10-30-2015
06:14PM
FCU-4F-02
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.8
Design
Air
Flow
(L/s)
143
Minimum
Air
Flow
(L/s)
143
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.9
Sens
Coil
Load
(kW)
1.8
Coil
Entering
DB / WB
(C)
23.4 / 16.6
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
143
Fan
Motor
(BHP)
0.036
Zone
Floor
Area
(m)
19.0
Zone
L/(s-m)
7.55
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.029
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEB- BEDROOM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.8
Aug 1500
143
0.1
19.0
7.55
Page 28 of 81
10-30-2015
06:14PM
FCU-4F-03
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
54.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.3
Design
Air
Flow
(L/s)
511
Minimum
Air
Flow
(L/s)
511
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.5
Total
Coil
Load
(kW)
6.6
Sens
Coil
Load
(kW)
6.3
Coil
Entering
DB / WB
(C)
23.5 / 16.7
Coil
Leaving
DB / WB
(C)
13.3 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
511
Fan
Motor
(BHP)
0.129
Zone
Floor
Area
(m)
54.0
Zone
L/(s-m)
9.47
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.102
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-LVNG-1
FOURTHF-TYPB-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
5.2
1.3
Oct 1500
Jun 1600
408
103
0.4
0.1
40.3
13.7
10.12
7.54
Page 29 of 81
10-30-2015
06:14PM
FCU-4F-04
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.7
Design
Air
Flow
(L/s)
133
Minimum
Air
Flow
(L/s)
133
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.0
Total
Coil
Load
(kW)
1.9
Sens
Coil
Load
(kW)
1.7
Coil
Entering
DB / WB
(C)
23.4 / 17.0
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
133
Fan
Motor
(BHP)
0.034
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
5.44
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.027
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-LOBBY
FOURTHF-TYPEB-TELE ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.2
0.5
Jul 1500
Jul 1400
94
40
0.0
0.0
20.0
4.5
4.68
8.81
Page 30 of 81
10-30-2015
06:14PM
FCU-4F-05
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.8 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
216
Minimum
Air
Flow
(L/s)
216
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.8
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.8 / 12.2
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
216
Fan
Motor
(BHP)
0.055
Zone
Floor
Area
(m)
18.8
Zone
L/(s-m)
11.51
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Jun 1700
216
0.2
18.8
11.51
Page 31 of 81
10-30-2015
06:14PM
FCU-4F-06
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.8
Design
Air
Flow
(L/s)
143
Minimum
Air
Flow
(L/s)
143
Time
of
Peak
Load
Aug 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.9
Sens
Coil
Load
(kW)
1.8
Coil
Entering
DB / WB
(C)
23.4 / 16.6
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
143
Fan
Motor
(BHP)
0.036
Zone
Floor
Area
(m)
19.0
Zone
L/(s-m)
7.55
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.029
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEB- BEDROOM-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.8
Aug 1500
143
0.1
19.0
7.55
Page 32 of 81
10-30-2015
06:14PM
FCU-4F-07
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
54.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
5.8
Design
Air
Flow
(L/s)
458
Minimum
Air
Flow
(L/s)
458
Time
of
Peak
Load
Jun 1400
Maximum
Heating
Load
(kW)
0.5
Total
Coil
Load
(kW)
6.1
Sens
Coil
Load
(kW)
5.8
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
458
Fan
Motor
(BHP)
0.115
Zone
Floor
Area
(m)
54.0
Zone
L/(s-m)
8.48
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.092
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-LVNG-2
FOURTHF-TYPB-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
4.5
1.3
Jun 1400
Jun 1600
355
103
0.4
0.1
40.3
13.7
8.80
7.54
Page 33 of 81
10-30-2015
06:14PM
FCU-4F-08
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
23.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.6
Design
Air
Flow
(L/s)
208
Minimum
Air
Flow
(L/s)
208
Time
of
Peak
Load
Sep 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.7
Sens
Coil
Load
(kW)
2.6
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
208
Fan
Motor
(BHP)
0.052
Zone
Floor
Area
(m)
23.0
Zone
L/(s-m)
9.03
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.042
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-MSTR BDRM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.6
Sep 1500
208
0.2
23.0
9.03
Page 34 of 81
10-30-2015
06:14PM
FCU-4F-09
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
23.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.6
Design
Air
Flow
(L/s)
208
Minimum
Air
Flow
(L/s)
208
Time
of
Peak
Load
Sep 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.7
Sens
Coil
Load
(kW)
2.6
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
208
Fan
Motor
(BHP)
0.052
Zone
Floor
Area
(m)
23.0
Zone
L/(s-m)
9.03
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.042
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-MSTR BDRM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.6
Sep 1500
208
0.2
23.0
9.03
Page 35 of 81
10-30-2015
06:14PM
FCU-4F-10
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
23.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.5
Design
Air
Flow
(L/s)
195
Minimum
Air
Flow
(L/s)
195
Time
of
Peak
Load
Jun 1400
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.6
Sens
Coil
Load
(kW)
2.5
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
195
Fan
Motor
(BHP)
0.049
Zone
Floor
Area
(m)
23.0
Zone
L/(s-m)
8.48
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.039
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPB-MSTR BDRM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.5
Jun 1400
195
0.2
23.0
8.48
Page 36 of 81
10-30-2015
06:14PM
FCU-4F-11
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
23.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.5
Design
Air
Flow
(L/s)
195
Minimum
Air
Flow
(L/s)
195
Time
of
Peak
Load
Jun 1400
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.6
Sens
Coil
Load
(kW)
2.5
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
195
Fan
Motor
(BHP)
0.049
Zone
Floor
Area
(m)
23.0
Zone
L/(s-m)
8.48
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.039
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-MSTR BDRM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.5
Jun 1400
195
0.2
23.0
8.48
Page 37 of 81
10-30-2015
06:14PM
FCU-4F-12
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
54.1 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
7.2
Design
Air
Flow
(L/s)
570
Minimum
Air
Flow
(L/s)
570
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.6
Total
Coil
Load
(kW)
7.5
Sens
Coil
Load
(kW)
7.1
Coil
Entering
DB / WB
(C)
23.6 / 16.8
Coil
Leaving
DB / WB
(C)
13.3 / 12.7
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
570
Fan
Motor
(BHP)
0.144
Zone
Floor
Area
(m)
54.1
Zone
L/(s-m)
10.54
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.114
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-LVNG-1
FOURTHF-TYPA-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
5.9
1.3
Oct 1500
Sep 1400
467
104
0.5
0.1
40.3
13.8
11.58
7.53
Page 38 of 81
10-30-2015
06:14PM
FCU-4F-13
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.9
Design
Air
Flow
(L/s)
152
Minimum
Air
Flow
(L/s)
152
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.0
Total
Coil
Load
(kW)
2.2
Sens
Coil
Load
(kW)
1.9
Coil
Entering
DB / WB
(C)
23.5 / 17.0
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
152
Fan
Motor
(BHP)
0.038
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
6.20
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.030
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-LOBBY
FOURTHF-TYPEA- ELEC ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.2
0.7
Jul 1500
Jul 1500
94
58
0.0
0.0
20.0
4.5
4.68
12.93
Page 39 of 81
10-30-2015
06:14PM
FCU-4F-14
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
54.1 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
7.2
Design
Air
Flow
(L/s)
570
Minimum
Air
Flow
(L/s)
570
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.6
Total
Coil
Load
(kW)
7.5
Sens
Coil
Load
(kW)
7.1
Coil
Entering
DB / WB
(C)
23.6 / 16.8
Coil
Leaving
DB / WB
(C)
13.3 / 12.7
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
570
Fan
Motor
(BHP)
0.144
Zone
Floor
Area
(m)
54.1
Zone
L/(s-m)
10.54
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.114
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPA-LVNG-2
FOURTHF-TYPA-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
5.9
1.3
Oct 1500
Sep 1400
467
104
0.5
0.1
40.3
13.8
11.58
7.53
Page 40 of 81
10-30-2015
06:14PM
FCU-4F-15
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.8 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
216
Minimum
Air
Flow
(L/s)
216
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.8
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.8 / 12.2
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
216
Fan
Motor
(BHP)
0.055
Zone
Floor
Area
(m)
18.8
Zone
L/(s-m)
11.51
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Jun 1700
216
0.2
18.8
11.51
Page 41 of 81
10-30-2015
06:14PM
FCU-4F-16
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.7
Design
Air
Flow
(L/s)
138
Minimum
Air
Flow
(L/s)
138
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.8
Sens
Coil
Load
(kW)
1.7
Coil
Entering
DB / WB
(C)
23.4 / 16.4
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
138
Fan
Motor
(BHP)
0.035
Zone
Floor
Area
(m)
18.0
Zone
L/(s-m)
7.64
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.028
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.7
Jul 1500
138
0.1
18.0
7.64
Page 42 of 81
10-30-2015
06:14PM
FCU-4F-17
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.8 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
216
Minimum
Air
Flow
(L/s)
216
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.8
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.8 / 12.2
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
216
Fan
Motor
(BHP)
0.055
Zone
Floor
Area
(m)
18.8
Zone
L/(s-m)
11.51
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Jun 1700
216
0.2
18.8
11.51
Page 43 of 81
10-30-2015
06:14PM
FCU-4F-18
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.7
Design
Air
Flow
(L/s)
138
Minimum
Air
Flow
(L/s)
138
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.8
Sens
Coil
Load
(kW)
1.7
Coil
Entering
DB / WB
(C)
23.4 / 16.4
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
138
Fan
Motor
(BHP)
0.035
Zone
Floor
Area
(m)
18.0
Zone
L/(s-m)
7.64
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.028
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
FOURTHF-TYPEA- BEDROOM-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.7
Jul 1500
138
0.1
18.0
7.64
Page 44 of 81
10-30-2015
06:14PM
FCU-GF-01
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
42.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
5.9
Design
Air
Flow
(L/s)
464
Minimum
Air
Flow
(L/s)
464
Time
of
Peak
Load
Aug 1900
Maximum
Heating
Load
(kW)
0.7
Total
Coil
Load
(kW)
6.1
Sens
Coil
Load
(kW)
5.8
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
464
Fan
Motor
(BHP)
0.117
Zone
Floor
Area
(m)
42.6
Zone
L/(s-m)
10.90
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.093
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-SHOP-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
5.9
Aug 1900
464
0.7
42.6
10.90
Page 45 of 81
10-30-2015
06:14PM
FCU-GF-02
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
58.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.4
Design
Air
Flow
(L/s)
506
Minimum
Air
Flow
(L/s)
506
Time
of
Peak
Load
Sep 1100
Maximum
Heating
Load
(kW)
0.6
Total
Coil
Load
(kW)
7.4
Sens
Coil
Load
(kW)
6.5
Coil
Entering
DB / WB
(C)
23.5 / 16.9
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
506
Fan
Motor
(BHP)
0.128
Zone
Floor
Area
(m)
58.6
Zone
L/(s-m)
8.64
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1100
Zone Name
Zone 1
Fan
Motor
(kW)
0.101
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-SHOP-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
6.4
Sep 1100
506
0.6
58.6
8.64
Page 46 of 81
10-30-2015
06:14PM
FCU-GF-03
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
58.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
6.3
Design
Air
Flow
(L/s)
496
Minimum
Air
Flow
(L/s)
496
Time
of
Peak
Load
Oct 1100
Maximum
Heating
Load
(kW)
0.5
Total
Coil
Load
(kW)
7.3
Sens
Coil
Load
(kW)
6.3
Coil
Entering
DB / WB
(C)
23.5 / 16.9
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
496
Fan
Motor
(BHP)
0.125
Zone
Floor
Area
(m)
58.6
Zone
L/(s-m)
8.47
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1100
Zone Name
Zone 1
Fan
Motor
(kW)
0.099
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-SHOP-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
6.3
Oct 1100
496
0.5
58.6
8.47
Page 47 of 81
10-30-2015
06:14PM
FCU-GF-04
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
6.1 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.1
Design
Air
Flow
(L/s)
86
Minimum
Air
Flow
(L/s)
86
Time
of
Peak
Load
Aug 1600
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.1
Sens
Coil
Load
(kW)
1.1
Coil
Entering
DB / WB
(C)
23.4 / 16.5
Coil
Leaving
DB / WB
(C)
13.1 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
86
Fan
Motor
(BHP)
0.022
Zone
Floor
Area
(m)
6.1
Zone
L/(s-m)
14.10
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.017
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-WATCHMAN ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.1
Aug 1600
86
0.1
6.1
14.10
Page 48 of 81
10-30-2015
06:14PM
FCU-GF-05
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
12.7 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.1
Design
Air
Flow
(L/s)
88
Minimum
Air
Flow
(L/s)
88
Time
of
Peak
Load
Aug 1900
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
1.2
Sens
Coil
Load
(kW)
1.1
Coil
Entering
DB / WB
(C)
23.4 / 16.9
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
88
Fan
Motor
(BHP)
0.022
Zone
Floor
Area
(m)
12.7
Zone
L/(s-m)
6.95
Zone Name
Zone 1
Time
of
Peak
Load
Aug 2000
Zone Name
Zone 1
Fan
Motor
(kW)
0.018
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-GARBAGE ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.1
Aug 1900
88
0.2
12.7
6.95
Page 49 of 81
10-30-2015
06:14PM
FCU-GF-06
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
23.8 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
3.9
Design
Air
Flow
(L/s)
309
Minimum
Air
Flow
(L/s)
309
Time
of
Peak
Load
Jul 1600
Maximum
Heating
Load
(kW)
0.6
Total
Coil
Load
(kW)
4.0
Sens
Coil
Load
(kW)
3.9
Coil
Entering
DB / WB
(C)
23.7 / 16.7
Coil
Leaving
DB / WB
(C)
13.3 / 12.7
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
309
Fan
Motor
(BHP)
0.078
Zone
Floor
Area
(m)
23.8
Zone
L/(s-m)
12.99
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.062
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-LV ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
3.9
Jul 1600
309
0.6
23.8
12.99
Page 50 of 81
10-30-2015
06:14PM
FCU-GF-07+08
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
72.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
9.6
Design
Air
Flow
(L/s)
757
Minimum
Air
Flow
(L/s)
757
Time
of
Peak
Load
Aug 1600
Maximum
Heating
Load
(kW)
1.3
Total
Coil
Load
(kW)
10.4
Sens
Coil
Load
(kW)
9.5
Coil
Entering
DB / WB
(C)
23.5 / 16.8
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
757
Fan
Motor
(BHP)
0.191
Zone
Floor
Area
(m)
72.0
Zone
L/(s-m)
10.51
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.151
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-ENTRANCE LOBBY
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
9.6
Aug 1600
757
1.3
72.0
10.51
Page 51 of 81
10-30-2015
06:14PM
FCU-GF-09
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
7.1 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.8
Design
Air
Flow
(L/s)
143
Minimum
Air
Flow
(L/s)
143
Time
of
Peak
Load
Aug 2000
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
1.8
Sens
Coil
Load
(kW)
1.8
Coil
Entering
DB / WB
(C)
23.7 / 7.6
Coil
Leaving
DB / WB
(C)
13.3 / 2.2
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
143
Fan
Motor
(BHP)
0.036
Zone
Floor
Area
(m)
7.1
Zone
L/(s-m)
20.16
Zone Name
Zone 1
Time
of
Peak
Load
Aug 2000
Zone Name
Zone 1
Fan
Motor
(kW)
0.029
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
GF-TELECOM ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.8
Aug 2000
143
0.1
7.1
20.16
Page 52 of 81
10-30-2015
06:14PM
FCU-RF-01
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.5
Design
Air
Flow
(L/s)
204
Minimum
Air
Flow
(L/s)
204
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
2.6
Sens
Coil
Load
(kW)
2.5
Coil
Entering
DB / WB
(C)
23.4 / 16.6
Coil
Leaving
DB / WB
(C)
13.3 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
204
Fan
Motor
(BHP)
0.051
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
8.34
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.041
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
ROOF-LOBBY
ROOF FLOOR-ELC ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.5
1.1
Jul 1500
Aug 2000
118
86
0.1
0.1
20.0
4.5
5.90
19.17
Page 53 of 81
10-30-2015
06:14PM
FCU-RF-02+03
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
68.0 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
15.4
Design
Air
Flow
(L/s)
1212
Minimum
Air
Flow
(L/s)
1212
Time
of
Peak
Load
Jul 1600
Maximum
Heating
Load
(kW)
1.6
Total
Coil
Load
(kW)
21.0
Sens
Coil
Load
(kW)
15.2
Coil
Entering
DB / WB
(C)
23.7 / 18.0
Coil
Leaving
DB / WB
(C)
13.3 / 12.8
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
1212
Fan
Motor
(BHP)
0.306
Zone
Floor
Area
(m)
68.0
Zone
L/(s-m)
17.82
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.242
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
ROOF FLOOR GYM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
15.4
Jul 1600
1212
1.6
68.0
17.82
Page 54 of 81
10-30-2015
06:14PM
FCU-TF-01
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
16.3 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.2
Design
Air
Flow
(L/s)
170
Minimum
Air
Flow
(L/s)
170
Time
of
Peak
Load
Oct 1200
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.3
Sens
Coil
Load
(kW)
2.1
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
170
Fan
Motor
(BHP)
0.043
Zone
Floor
Area
(m)
16.3
Zone
L/(s-m)
10.44
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.034
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEC-MASTR BED RM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.2
Oct 1200
170
0.1
16.3
10.44
Page 55 of 81
10-30-2015
06:14PM
FCU-TF-02
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
51.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.6
Design
Air
Flow
(L/s)
371
Minimum
Air
Flow
(L/s)
371
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.0
Sens
Coil
Load
(kW)
4.6
Coil
Entering
DB / WB
(C)
23.4 / 16.7
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
371
Fan
Motor
(BHP)
0.093
Zone
Floor
Area
(m)
51.5
Zone
L/(s-m)
7.20
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.074
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEC- LIVING ROOM-1
TYP-TYPEC-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.6
1.1
Oct 1100
Oct 1600
283
88
0.2
0.1
43.0
8.5
6.57
10.36
Page 56 of 81
10-30-2015
06:14PM
FCU-TF-03
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
13.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.9
Design
Air
Flow
(L/s)
152
Minimum
Air
Flow
(L/s)
152
Time
of
Peak
Load
Oct 1100
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.0
Sens
Coil
Load
(kW)
1.9
Coil
Entering
DB / WB
(C)
23.4 / 16.4
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
152
Fan
Motor
(BHP)
0.038
Zone
Floor
Area
(m)
13.5
Zone
L/(s-m)
11.27
Zone Name
Zone 1
Time
of
Peak
Load
Nov 1200
Zone Name
Zone 1
Fan
Motor
(kW)
0.030
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEC- BED R0OM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.9
Oct 1100
152
0.1
13.5
11.27
Page 57 of 81
10-30-2015
06:14PM
FCU-TF-04
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
51.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.6
Design
Air
Flow
(L/s)
371
Minimum
Air
Flow
(L/s)
371
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.0
Sens
Coil
Load
(kW)
4.6
Coil
Entering
DB / WB
(C)
23.4 / 16.7
Coil
Leaving
DB / WB
(C)
13.1 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
371
Fan
Motor
(BHP)
0.093
Zone
Floor
Area
(m)
51.5
Zone
L/(s-m)
7.20
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1400
Zone Name
Zone 1
Fan
Motor
(kW)
0.074
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEC- LIVING ROOM-2
TYP-TYPEC-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.6
1.1
Oct 1100
Oct 1600
283
88
0.2
0.1
43.0
8.5
6.57
10.36
Page 58 of 81
10-30-2015
06:14PM
FCU-TF-05
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
13.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.9
Design
Air
Flow
(L/s)
152
Minimum
Air
Flow
(L/s)
152
Time
of
Peak
Load
Oct 1100
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.0
Sens
Coil
Load
(kW)
1.9
Coil
Entering
DB / WB
(C)
23.4 / 16.4
Coil
Leaving
DB / WB
(C)
13.0 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
152
Fan
Motor
(BHP)
0.038
Zone
Floor
Area
(m)
13.5
Zone
L/(s-m)
11.27
Zone Name
Zone 1
Time
of
Peak
Load
Nov 1200
Zone Name
Zone 1
Fan
Motor
(kW)
0.030
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEC- BED R0OM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1.9
Oct 1100
152
0.1
13.5
11.27
Page 59 of 81
10-30-2015
06:14PM
FCU-TF-06
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
16.3 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.2
Design
Air
Flow
(L/s)
170
Minimum
Air
Flow
(L/s)
170
Time
of
Peak
Load
Oct 1200
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.3
Sens
Coil
Load
(kW)
2.1
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
170
Fan
Motor
(BHP)
0.043
Zone
Floor
Area
(m)
16.3
Zone
L/(s-m)
10.44
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.034
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEC-MASTR BED RM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.2
Oct 1200
170
0.1
16.3
10.44
Page 60 of 81
10-30-2015
06:14PM
FCU-TF-07
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.9
Design
Air
Flow
(L/s)
391
Minimum
Air
Flow
(L/s)
391
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.2
Sens
Coil
Load
(kW)
4.9
Coil
Entering
DB / WB
(C)
23.5 / 16.7
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
391
Fan
Motor
(BHP)
0.098
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
8.98
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.078
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-1
TYP-TYPEB-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.9
1.1
Oct 1500
Jun 1700
305
85
0.2
0.1
35.0
8.5
8.72
10.04
Page 61 of 81
10-30-2015
06:14PM
FCU-TF-08
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
161
Minimum
Air
Flow
(L/s)
161
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.1
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.7 / 12.1
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
161
Fan
Motor
(BHP)
0.041
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
11.13
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Oct 1500
161
0.1
14.5
11.13
Page 62 of 81
10-30-2015
06:14PM
FCU-TF-09
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.6
Design
Air
Flow
(L/s)
128
Minimum
Air
Flow
(L/s)
128
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.0
Total
Coil
Load
(kW)
1.9
Sens
Coil
Load
(kW)
1.6
Coil
Entering
DB / WB
(C)
23.5 / 17.1
Coil
Leaving
DB / WB
(C)
13.2 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
128
Fan
Motor
(BHP)
0.032
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
5.22
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.026
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-LOBBY
TYP-TYPEB- TELE. ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.2
0.4
Jul 1500
Jan 2300
94
34
0.0
0.0
20.0
4.5
4.68
7.58
Page 63 of 81
10-30-2015
06:14PM
FCU-TF-10
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
161
Minimum
Air
Flow
(L/s)
161
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.1
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.7 / 12.1
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
161
Fan
Motor
(BHP)
0.041
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
11.13
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Oct 1500
161
0.1
14.5
11.13
Page 64 of 81
10-30-2015
06:14PM
FCU-TF-11
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.9
Design
Air
Flow
(L/s)
391
Minimum
Air
Flow
(L/s)
391
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.2
Sens
Coil
Load
(kW)
4.9
Coil
Entering
DB / WB
(C)
23.5 / 16.7
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
391
Fan
Motor
(BHP)
0.098
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
8.98
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.078
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-2
TYP-TYPEB-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.9
1.1
Oct 1500
Jun 1700
305
85
0.2
0.1
35.0
8.5
8.72
10.04
Page 65 of 81
10-30-2015
06:14PM
FCU-TF-12
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
214
Minimum
Air
Flow
(L/s)
214
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.7
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
214
Fan
Motor
(BHP)
0.054
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
10.94
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Sep 1600
214
0.1
19.6
10.94
Page 66 of 81
10-30-2015
06:14PM
FCU-TF-13
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
214
Minimum
Air
Flow
(L/s)
214
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.7
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
214
Fan
Motor
(BHP)
0.054
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
10.94
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Sep 1600
214
0.1
19.6
10.94
Page 67 of 81
10-30-2015
06:14PM
FCU-TF-14
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
214
Minimum
Air
Flow
(L/s)
214
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.7
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
214
Fan
Motor
(BHP)
0.054
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
10.94
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Sep 1600
214
0.1
19.6
10.94
Page 68 of 81
10-30-2015
06:14PM
FCU-TF-15
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
19.6 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.7
Design
Air
Flow
(L/s)
214
Minimum
Air
Flow
(L/s)
214
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.8
Sens
Coil
Load
(kW)
2.7
Coil
Entering
DB / WB
(C)
23.5 / 16.6
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
214
Fan
Motor
(BHP)
0.054
Zone
Floor
Area
(m)
19.6
Zone
L/(s-m)
10.94
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.043
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB-MASTR BD ROM-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.7
Sep 1600
214
0.1
19.6
10.94
Page 69 of 81
10-30-2015
06:14PM
FCU-TF-16
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.9
Design
Air
Flow
(L/s)
391
Minimum
Air
Flow
(L/s)
391
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.2
Sens
Coil
Load
(kW)
4.9
Coil
Entering
DB / WB
(C)
23.5 / 16.7
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
391
Fan
Motor
(BHP)
0.098
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
8.98
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.078
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-4
TYP-TYPEB-KITCHEN-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.9
1.1
Oct 1500
Jun 1700
305
85
0.2
0.1
35.0
8.5
8.72
10.04
Page 70 of 81
10-30-2015
06:14PM
FCU-TF-17
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
161
Minimum
Air
Flow
(L/s)
161
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.1
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.7 / 12.1
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
161
Fan
Motor
(BHP)
0.041
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
11.13
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-4
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Oct 1500
161
0.1
14.5
11.13
Page 71 of 81
10-30-2015
06:14PM
FCU-TF-18
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
43.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.9
Design
Air
Flow
(L/s)
391
Minimum
Air
Flow
(L/s)
391
Time
of
Peak
Load
Sep 1600
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.2
Sens
Coil
Load
(kW)
4.9
Coil
Entering
DB / WB
(C)
23.5 / 16.7
Coil
Leaving
DB / WB
(C)
13.2 / 12.5
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
391
Fan
Motor
(BHP)
0.098
Zone
Floor
Area
(m)
43.5
Zone
L/(s-m)
8.98
Zone Name
Zone 1
Time
of
Peak
Load
Sep 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.078
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- LIVING R0OM-3
TYP-TYPEB-KITCHEN-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.9
1.1
Oct 1500
Jun 1700
305
85
0.2
0.1
35.0
8.5
8.72
10.04
Page 72 of 81
10-30-2015
06:14PM
FCU-TF-19
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
161
Minimum
Air
Flow
(L/s)
161
Time
of
Peak
Load
Oct 1500
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.1
Coil
Entering
DB / WB
(C)
23.4 / 16.3
Coil
Leaving
DB / WB
(C)
12.7 / 12.1
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
161
Fan
Motor
(BHP)
0.041
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
11.13
Zone Name
Zone 1
Time
of
Peak
Load
Oct 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEB- BED ROOM-3
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Oct 1500
161
0.1
14.5
11.13
Page 73 of 81
10-30-2015
06:14PM
FCU-TF-20
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
24.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
1.7
Design
Air
Flow
(L/s)
136
Minimum
Air
Flow
(L/s)
136
Time
of
Peak
Load
Jul 1500
Maximum
Heating
Load
(kW)
0.0
Total
Coil
Load
(kW)
2.0
Sens
Coil
Load
(kW)
1.7
Coil
Entering
DB / WB
(C)
23.4 / 16.9
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
136
Fan
Motor
(BHP)
0.034
Zone
Floor
Area
(m)
24.5
Zone
L/(s-m)
5.57
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1600
Zone Name
Zone 1
Fan
Motor
(kW)
0.027
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-LOBBY
TYP-TYPEB- ELECT. ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
1.2
0.5
Jul 1500
Jan 2300
94
43
0.0
0.0
20.0
4.5
4.68
9.51
Page 74 of 81
10-30-2015
06:14PM
FCU-TF-21
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.3
Design
Air
Flow
(L/s)
180
Minimum
Air
Flow
(L/s)
180
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.4
Sens
Coil
Load
(kW)
2.3
Coil
Entering
DB / WB
(C)
23.6 / 16.7
Coil
Leaving
DB / WB
(C)
13.3 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
180
Fan
Motor
(BHP)
0.045
Zone
Floor
Area
(m)
18.5
Zone
L/(s-m)
9.73
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.036
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEA-MASTR BD ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.3
Jun 1700
180
0.1
18.5
9.73
Page 75 of 81
10-30-2015
06:14PM
FCU-TF-22
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
159
Minimum
Air
Flow
(L/s)
159
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.0
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
159
Fan
Motor
(BHP)
0.040
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
10.95
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEA- BED ROOM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Jun 1700
159
0.1
14.5
10.95
Page 76 of 81
10-30-2015
06:14PM
FCU-TF-23
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
49.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.6
Design
Air
Flow
(L/s)
364
Minimum
Air
Flow
(L/s)
364
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.2
Sens
Coil
Load
(kW)
4.6
Coil
Entering
DB / WB
(C)
23.4 / 16.7
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
364
Fan
Motor
(BHP)
0.092
Zone
Floor
Area
(m)
49.5
Zone
L/(s-m)
7.35
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.073
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEA- LIVING R0OM-1
TYP-TYPEA-KITCHEN-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.6
1.0
Jun 1700
Oct 1600
286
79
0.2
0.0
41.5
8.0
6.88
9.82
Page 77 of 81
10-30-2015
06:14PM
FCU-TF-24
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
49.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
4.6
Design
Air
Flow
(L/s)
364
Minimum
Air
Flow
(L/s)
364
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.2
Total
Coil
Load
(kW)
5.2
Sens
Coil
Load
(kW)
4.6
Coil
Entering
DB / WB
(C)
23.4 / 16.7
Coil
Leaving
DB / WB
(C)
12.9 / 12.3
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
364
Fan
Motor
(BHP)
0.092
Zone
Floor
Area
(m)
49.5
Zone
L/(s-m)
7.35
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.073
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEA- LIVING R0OM-2
TYP-TYPEA-KITCHEN-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
1
1
3.6
1.0
Jun 1700
Oct 1600
286
79
0.2
0.0
41.5
8.0
6.88
9.82
Page 78 of 81
10-30-2015
06:14PM
FCU-TF-25
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
14.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.0
Design
Air
Flow
(L/s)
159
Minimum
Air
Flow
(L/s)
159
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.1
Sens
Coil
Load
(kW)
2.0
Coil
Entering
DB / WB
(C)
23.5 / 16.5
Coil
Leaving
DB / WB
(C)
13.0 / 12.4
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
159
Fan
Motor
(BHP)
0.040
Zone
Floor
Area
(m)
14.5
Zone
L/(s-m)
10.95
Zone Name
Zone 1
Time
of
Peak
Load
Jul 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.032
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEA- BED ROOM-2
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.0
Jun 1700
159
0.1
14.5
10.95
Page 79 of 81
10-30-2015
06:14PM
FCU-TF-26
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
18.5 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.3
Design
Air
Flow
(L/s)
180
Minimum
Air
Flow
(L/s)
180
Time
of
Peak
Load
Jun 1700
Maximum
Heating
Load
(kW)
0.1
Total
Coil
Load
(kW)
2.4
Sens
Coil
Load
(kW)
2.3
Coil
Entering
DB / WB
(C)
23.6 / 16.7
Coil
Leaving
DB / WB
(C)
13.3 / 12.6
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
180
Fan
Motor
(BHP)
0.045
Zone
Floor
Area
(m)
18.5
Zone
L/(s-m)
9.73
Zone Name
Zone 1
Time
of
Peak
Load
Jun 1700
Zone Name
Zone 1
Fan
Motor
(kW)
0.036
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
TYP-TYPEA-MASTR BD ROM-1
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.3
Jun 1700
180
0.1
18.5
9.73
Page 80 of 81
10-30-2015
06:14PM
FCU-UG-01
TERM
SPLT-FC
Number of zones
Floor Area
Location
1
44.4 m
Dubai, United Arab Emirates
Calculation Months
Sizing Data
Jan to Dec
Calculated
Zone Name
Zone 1
Maximum
Cooling
Sensible
(kW)
2.4
Design
Air
Flow
(L/s)
190
Minimum
Air
Flow
(L/s)
190
Time
of
Peak
Load
Jul 1400
Maximum
Heating
Load
(kW)
0.3
Total
Coil
Load
(kW)
2.4
Sens
Coil
Load
(kW)
2.4
Coil
Entering
DB / WB
(C)
23.4 / 7.5
Coil
Leaving
DB / WB
(C)
12.8 / 2.0
Water
Flow
@ 5.6 K
(L/s)
-
Heating
Heating
Coil
Coil
Ent/Lvg
Load
DB
(kW)
(C)
0.0 -18.3 / -18.3
Htg Coil
Water
Flow
@11.1 K
(L/s)
0.00
Fan
Design
AirFlow
(L/s)
190
Fan
Motor
(BHP)
0.048
Zone
Floor
Area
(m)
44.4
Zone
L/(s-m)
4.28
Zone Name
Zone 1
Time
of
Peak
Load
Aug 1500
Zone Name
Zone 1
Fan
Motor
(kW)
0.038
OA Vent
Design
AirFlow
(L/s)
0
Zone Name /
Space Name
Zone 1
UG - PUMP ROOM
Mult.
Cooling
Sensible
(kW)
Time
of
Load
Air
Flow
(L/s)
Heating
Load
(kW)
Floor
Area
(m)
Space
L/(s-m)
2.4
Jul 1400
190
0.3
44.4
4.28
Page 81 of 81