SETTING CALCULATION FOR RED&REL 670 RELAYS

CT PRIM

2500

VT PRIM

CT SEC
CTR

1
2500

VT SEC
VTR

Z1

SETTING PARAMETERS
RFPE
RFPP
X1
XO

30
17.5
8.75
29.28

Z2

SETTING PARAMETERS
RFPE
RFPP
X1
XO

36
47.1
23.55
76.64

Z3

SETTING PARAMETERS
RFPE
RFPP
X1
XO

43.2
56.52
54.59
188.15

Z4

SETTING PARAMETERS
RFPE
RFPP
X1
XO

43.2
56.52
54.59
188.15

Z5

SETTING PARAMETERS
RFPE
RFPP
X1
XO

0
0
0
0

RFRVPE
RFRvPP
X1
XO
RFFwPE
RFFwPP

380000

CTR/VTR

100
3800
SECONDARY EXPECTED VALUES ACCORDING TO
CHARACTARISTIC
R-N
R1
19.7368
0.44
X-N
R0
10.2588
5.37
R P-P
(PH-E)
5.7566
82.357
XP-P
(PH-PH)
5.7566
87.086
SECONDARY EXPECTED VALUES ACCORDING TO
CHARACTARISTIC
R1
R-N
23.6842
1.29
R0
X-N
27.1360
15.75
(PH-E)
R P-P
15.4934
81.541
(PH-PH)
XP-P
15.4934
86.830
SECONDARY EXPECTED VALUES ACCORDING TO
CHARACTARISTIC
R-N
R1
2.84
28.4211
X-N
R0
35.25
65.2039
R P-P
(PH-E)
18.5921
82.129
XP-P
(PH-PH)
35.9145
86.987
SECONDARY EXPECTED VALUES ACCORDING TO
CHARACTARISTIC
R-N
R1
2.84
28.4211
X-N
R0
35.25
65.2039
R P-P
(PH-E)
18.5921
82.129
XP-P
(PH-PH)
35.9145
86.987
SECONDARY EXPECTED VALUES ACCORDING TO
CHARACTARISTIC
R-N
R1
1
0.0000
X-N
R0
1
0.0000
R P-P
(PH-E)
0.0000
0.000
XP-P
(PH-PH)
0.0000
0.000
PHASE SELECTION
PH-E
PH-PH
3-PH
RFw
28.4211
18.5921
24.7895
XFw
39.0746
22.3092
29.7456
RRv
28.4211
18.5921
24.7895
XRv
39.0746
22.3092
29.7456

FLO

PSD

PHS

43.2
56.52
33.91
110.36
43.2
56.52
POWER SWING CALCULATION
R1FINFW
RInFw
62.17
40.9013
R1FINRv
RInRv
62.17
40.9013
X1FINFW
XInFw
60
39.4737
X1FINRv
XInRv
60
39.4737
KLDRFW
ROutFw
0.75
52.3322
KLDRRv
ROutRv
0.75
52.3322
RLdOutFw
69.500
XOutFw
50.9046
RLdOutRv
69.500
XOutRv
50.9046
PSD CALCULATION AT RLdOutFw=RLdOutRv
F: DIFFRANCE BETWEEN INNER &OUTER ZONES

X1L

10.294

X0L

34.452

R1L
R0L
X0M

0.521

LINE LENGTH
Zx inj 1-ph
Zx inj ph-ph

6.322
0
29
4
3.35

0.6578947

FAULT LOCATOR
12.070

XL(ph-e)sec
XL(ph-ph)sec
XL(M)sec
Z
Z
P(1-PH)
P(PH-PH)
P(1-PH)MUTUAL

THE

THE

THE

THE

THE

F(FW)
17.3750
F(Rv)
17.3750
AT OPERATION OF LdCh=ON
ROutFw
45.724
RInFw
34.293
ROutRv
45.724
RInRv
34.293

FOR 1-PH FAULTS

6.77236842 FOR 3-PH &2-PH FAULTS


7.555
82.379
87.103
9.610
14.345
0.000

FOR 1- PH FAULTS WITH MUTUAL

TEST ANGLE FOR 1-PH


TEST ANGLE FOR 2-PH
FAULT LENGTH

Zx inj-mutual

INJECT HEALTHY CONDITION MORE THAN 2 SEC THEN APPLY FAULT CONDITION WITH I ZxI AND

L3D

P= THE EXPECTED FAULT DISTANCE

Idmin
End Section1
End Section2
Slop Section2
Slop Section3
Ibase
IBias section1
IBias section2
IBias section3

Section 1
Slop section 2
Slop section 3

DIFFRENTIAL PROTECTION
Id section 1
0.2
Id section 2
0.34
Id section 3
1.7

0.2
1.25
3
0.4
0.8
1
1.1
1.6
4
0 IBias End Section1*IBase
Endsection1*IBase IBias Endsection2*IBase
IBias End section2*IBase

CONSTANTS

TOC

IEC CURVE TYPE


NORMAL INVERSE
VERY INVERSE
INVERSE
EXTREMLY INVERSE
SHORT TIME INVERSE
LONG TIME INVERSE
K1(TMS) set
I1> (set)
I(inj)
I(inj)/I1> (set)

TIME (sec)

0.14
13.5
0.14
80
0.05
120
1
1
3
3

0.02
1
0.02
2
0.04
1

6.302
6.750
6.302
10.000
1.113
60.000

t=

A
K
I 1
P

TOC: TIME OVER CURRENT

PREPARED BY

ENG/ EHAB SHAWKAT


AT&C