Date: 11-06-13

From
A.Mohamed Nishar,
Camp@ M/s.Baldev alloys Pvt.ltd.
M/s. Veesons Energy Systems Pvt.Ltd.
Raipur.
To
The Sr.Manager(E&I)
M/s.Veesons energy systems (P) Ltd.
Trichy
Subject: PA Fan Motor Feeder problem reg
Dear Sir,
With reference to the subject, as per the Supplied PA fan feeder Design
for 55KW motor. But we are Provide 75KW motor for PA fan and 100 A fuse , This
Feeder and fuse rating is not sufficient, So We are inform to our H.O by mail. Our
design departments approve and change the fuse only by 160A instead of 100A and
same material sent to site. So we are taken the PA fan No Load trails is successfully
completed. So we are going to commission the PA fan with motor on 11-06-13 while
SFU had busted and feeder line cables get more heat. Hence we are requesting you
to consider the design and send the feeder for 75 KW motor on urgent basis,
because of PA commission depending with this matter. Feeders detail on given
below.
1.
2.
3.
4.
5.
6.
7.

SFU rating-160/160 A
CT ratio -150/5A
Main contactor-110A
Delta Contactor-110A
Star Contact-63A
OLR Rating -63-100A
Feeder Line Cables-16sq.mm Copper cable

Thanking You,

With best regards,


A.Mohamed Nishar