NOTES FOR FOUNDATION

1. FOR CENTER LINE DIMENSION REFER TO ARCH. DRG. NO. _____ OF JOB NO.
______
2. DIMENSIONS ARE TO BE READ AND NOT TO BE SCALED OUT
3. THE NET SAFE BEARING CAPACITY OF SOIL HAS BEEN TAKEN AS 10.8.( 1
TON/ SQFT) . ALL FOOTINGS SHOULD REST ON FIRM & CONSOLIDATED SOIL.
INCASE ANY LOOSE/ SOFT STRATA IS ENCOUNTERED, SUITABLE REMEDIAL
MEASURES BE TAKEN UNDER INTIMATION TO THIS OFFICE.
4. USE CEMENT CONCRETE OF GRADE NOT LESS THAN M-20 HAVING CUBE
CRUSHING STRENGTH ( FIELD STRENGTH OF 15 CM. CUBE) AS 265 KG/SQ. CM
AFTER 28 DAYS OF CURING.
5. USE HIGH TENSILE STRENGTH DEFORMED BARS (TOR STEEL) CONFORMING
TO I.S.1786-1985 HAVING YIELD STRENGTH OF 4150 KG/ SQ.CM
6. WATER TO BE USED SHALL CONFIRM TO IS 456-2000.
7. CLEAR COVER OF CONCRETE TO REINFORCEMENT (INCLUDING LINKS) SHALL
BE AS FOLLOWS: COLUMN (VERT. REINF.)
=
1 (40MM)
FLOOR BEAM
=
1 (30 MM)
FOUNDATION SLAB
=
2 (50MM)
FOUNDATION BEAM
=
2 (65 MM)
8. LAPS IN REINFORCING BARS SHALL BE DULY STAGGERED AND AVOIDED
NEAR MID SPAN.
9. IN CASE BARS OF SPECIFIED DIA ARE NOT AVAILABLE, USE EQUIVALENT AREA
IF BARS OF SMALLER DIA ARE USED & EQUIVALENT PERIMETER IF BARS OF
BIGGER DIA ARE USED.
10.NO RAINWATER PIPES IS TO BE EMBEDDED IN PILLARS/ COLUMNS OR BEAMS
AND SUITABLE DRAINAGE ARRANGEMENTS BE FINALIZED BEFORE STARTING
WORK.
11.PLINTH BAND SHALL BE AS DETAILED BELOW AT FINISHED NATURAL GROUND
LEVEL.

12.NOMINAL TOE WALL WITH PLINTH BEAM SHALL BE PROVIDED WHEREVER


NECESSARY AS PER ARCHITECTURAL DRAWINGS.
13.SEISMIC STRENGTHENING MEASURES OF MASONRY BUILDINGS AS PER
IS:4326(1993) SUCH AS VERTICAL REINFORCEMENT AT CORNERS/JUNCTIONS,
AROUND OPENINGS AND PROVISION OF DOWEL BARS ETC. SHALL BE
ADOPTED AT SITE IN ACCORDANCE WITH TYPICAL SEISMIC DETAILING SHEET
ISSUED VIDE DRG. NO.1 OF JOB NO. 510.
14.FOR GENERAL DETAILING OF SLAB REINFORCEMENT, LAP SPLICES IN BEAMS,
DETAIL OF SHEAR REINFORCEMENT IN BEAMS, TYPICAL BEAMS/COLUMN
JUNCTION ETC. REFER TO DRG. NO. 3 OF JOB NO.510
FOR MASONRY STRUCTURE
1. ALL JAMBS IN BRICK MASONRY ADJOINING OPENINGS IN BRICK WALLS SHALL
BE CONSTRUCTED IN CEMENT SAND MORTAR 1:3 NOT WITHSTANDING USE
OF LEANER MIX IN WALL ITSELF
2. SEISMIC STRENGTHENING MEASURES OF MASONRY BUILDINGS AS PER
IS:4326(1993) SUCH AS VERTICAL REINFORCEMENT AT CORNERS/JUNCTIONS,
AROUND OPENINGS AND PROVISION OF DOWEL BARS ETC. SHALL BE

ADOPTED AT SITE IN ACCORDANCE WITH TYPICAL SEISMIC DETAILING SHEET


ISSUED VIDE DRG. NO.2 OF JOB NO. 510.
3. PROVIDE VERTICAL & HORIZONTAL D.P.C. FOR ALL MASONRY WALLS &
PILLARS AS PER P.W.D. SPECIFICATIONS WITH THE LEVELS AS APPROVED BY
THE ENGINEER-IN-CHARGE.

NOTES FOR BEAM/ SLAB 1ST FLOOR


1. FOR CENTER LINE DIMENSION REFER TO ARCH. DRG. NO. _____ OF JOB NO.
______
2. DIMENSIONS ARE TO BE READ AND NOT TO BE SCALED OUT
3. USE CEMENT CONCRETE OF GRADE NOT LESS THAN M-20 HAVING CUBE
CRUSHING STRENGTH ( FIELD STRENGTH OF 15 CM. CUBE) AS 265 KG/SQ. CM
AFTER 28 DAYS OF CURING.
4. USE HIGH TENSILE STRENGTH DEFORMED BARS (TOR STEEL) CONFORMING
TO I.S.1786-1985 HAVING YIELD STRENGTH OF 4150 KG/ SQ.CM
5. WATER TO BE USED SHALL CONFIRM TO IS 456-2000.
6. CLEAR COVER OF CONCRETE TO REINFORCEMENT (INCLUDING LINKS) SHALL
BE AS FOLLOWS: COLUMN (VERT. REINF.)
=
1 (40MM)
FLOOR BEAM
=
1 (30 MM)
FOUNDATION BEAM
=
2 (65 MM)
7. LAPS IN REINFORCING BARS SHALL BE DULY STAGGERED AND AVOIDED
NEAR MID SPAN.
8. PROVIDE NOMINAL LINTELS OVER DOOR, WINDOW AND VENTILATOR
OPENINGS UNLESS DETAILS ARE INCLUDED IN STRUCTURAL DRAWINGS.
9. TYPICAL CONTINUOUS LINTEL BAND SHALL BE PROVIDED AS DETAILED
BELOW OVER ALL BRICK WALLS/ COLUMNS AT LINTEL LEVEL EXCEPT
SPECIFIED OTHERWISE.

10.IN CASE BARS OF SPECIFIED DIA ARE NOT AVAILABLE, USE EQUIVALENT AREA
IF BARS OF SMALLER DIA ARE USED & EQUIVALENT PERIMETER IF BARS OF
BIGGER DIA ARE USED.
11.ALL JAMBS IN BRICK MASONRY ADJOINING OPENINGS IN BRICK WALLS SHALL
BE CONSTRUCTED IN CEMENT SAND MORTAR 1:3 NOT WITHSTANDING USE
OF LEANER MIX IN WALL ITSELF.
12.NO RAINWATER PIPES IS TO BE EMBEDDED IN PILLARS/ COLUMNS OR BEAMS
AND SUITABLE DRAINAGE ARRANGEMENTS BE FINALIZED BEFORE STARTING
WORK.
13.SEISMIC STRENGTHENING MEASURES OF MASONRY BUILDINGS AS PER
IS:4326(1993) SUCH AS VERTICAL REINFORCEMENT AT CORNERS/JUNCTIONS,
AROUND OPENINGS AND PROVISION OF DOWEL BARS ETC. SHALL BE
ADOPTED AT SITE IN ACCORDANCE WITH TYPICAL SEISMIC DETAILING SHEET
ISSUED VIDE DRG. NO.1 OF JOB NO. 510.
14.FOR GENERAL DETAILING OF SLAB REINFORCEMENT, LAP SPLICES IN BEAMS,
DETAIL OF SHEAR REINFORCEMENT IN BEAMS, TYPICAL BEAMS/COLUMN
JUNCTION ETC. REFER TO DRG. NO. 3 OF JOB NO.510
FOR MASONRY STRUCTURE

1. ALL JAMBS IN BRICK MASONRY ADJOINING OPENINGS IN BRICK WALLS SHALL


BE CONSTRUCTED IN CEMENT SAND MORTAR 1:3 NOT WITHSTANDING USE
OF LEANER MIX IN WALL ITSELF
2. SEISMIC STRENGTHENING MEASURES OF MASONRY BUILDINGS AS PER
IS:4326(1993) SUCH AS VERTICAL REINFORCEMENT AT CORNERS/JUNCTIONS,
AROUND OPENINGS AND PROVISION OF DOWEL BARS ETC. SHALL BE
ADOPTED AT SITE IN ACCORDANCE WITH TYPICAL SEISMIC DETAILING SHEET
ISSUED VIDE DRG. NO.2 OF JOB NO. 510.

NOTES FOR 2ND FLOOR ONWARDS DRGS BEAMS & SLAB

1. FOR CENTRE LINE DIMENSION REFER TO ARCH. DRG. NO. _______ OF


JOB NO._____
2. FOR OTHER STRUCTURAL NOTES REFER TO DRG. NO. __________ OF
JOB NO.______
NOTES FOR DRGS BEAMS & SLAB AT ROOF LEVEL

1. FOR CENTRE LINE DIMENSION REFER TO ARCH. DRG. NO. _______ OF


JOB NO._____
2. FOR OTHER STRUCTURAL NOTES REFER TO DRG. NO. __________ OF
JOB NO.______
3. NO WATER TANK SHOULD REST DIRECTLY ON THE ROOF SLAB
SUITABLE ARRANGEMENT OF RSJS SHOULD BE MADE FOR THOSE
RESTING DIRECTLY ON LOAD BEARING WALLS/ COLUMNS OF THE
STRUCTURE.