Sei sulla pagina 1di 3

Tanner Wareham

CI 317
Aspen Task 1

Aspen Task 1
Tanner Wareham 17662168
S1
COMPRESS
S4
VALVE

S2

EVAP

S3
CONDENSE

Refrigerant R12:
Cooling load: 1.934 kW
T(K)
P(Pa)

S1
258.2
183184

S2
319.8
837039

Refrigerant flow rate = 0.0175kg/s


Vapour fraction stream 4 = 0.2991
Qcond = 2452 W to environment
Qevap = 1934 W
Wcomp = 518 W
Co-efficient of performance = 3.733

S3
308.2
837039

S4
258.2
183184

S1
COMPRESS
S4
VALVE

S2

EVAP

S3
CONDENSE

Propane:
Cooling load: 1.934 kW
T(K)
P(Pa)

S1
245.4
183184

S2
302
837039

S3
293.2
837039

S4
245.4
183184

Refrigerant flow rate = 0.0063kg/s


Vapour fraction stream 4 = 0.2917
Qcond = 2285 W to environment
Qevap = 1920 W
Wcomp = 355.6 W
Co-efficient of performance = 4.004
Replacement of R12 with propane possible?
No as the pressure increase as well as the work input increase from R12 to
propane is more than 25%.