AIM: To perform parallel operation and polarity test of two single phase transformer.
APPARATURS:
Sr.
No.
Apparatus
Range
Quantity
Wattmeter
300V, 10A
01
Voltmeter
0-300 Volt
02
Ammeter
05 A
02
Ammeter
10 A
01
Lamp load
1phase 5KW,230V
01
THEORY:
The two transformers to be connected in parallel should be connected in a manner that their
primary and secondary have the same polarities. This can be accomplished by conducting a
polarity test.
PROCEDURE:
1. Polarity check:
The two transformers to be connected in parallel should be connected in a manner that their
primary and secondary have the same polarities. This can be accomplished by conducting a
polarity test -for which the transformers should be connected as shown in Fig.:1
The test is conducted as follows:
1. Connect the circuit as shown in Fig.:1
2. Switch on the supply.
3. Note the reading in the voltmeter connected on the secondary side. It may be either zero
or twice the secondary terminal voltage.
4. If the volt meter reads double the secondary voltage, then in the secondary opposite
polarities have been connected. Then the terminal S1 should be connected to S'2 and S'1
should be connected to S2.
CIRCUIT DIAGRAM:
Fig.:-1
Fig.:-2
OBSERVATIONS:
The observations made above should be recorded in a tabular form as shown below:
Sr.
VL
IL
No.
Volt
Ampere
Measured Values
I1 (Amp.)
I2 (Amp.)
Calculated Values
I1 (Amp.)
I2 (Amp.)
1.
2.
3.
4.
5.
CALCULATION:
Z2
I1 I l *
Z1 Z 2
Here,
Z1&Z2 are the secondary impedances of the two transformers.
Z1
I 2 Il *
Z1 Z 2
Z2
S1 Sl *
Z1 Z 2
Load shared by 2nd transformer is
Z1
S 2 Sl *
Z1 Z 2
Where
Sl
Sl V2 I l
GRAPH:
Plot the graph of IL versus I1 and I2.
Conclusion: