RET 54_
Protectie, Monitorizare
si Control
1 MRS750500-MUM EN
Issued 23.12.1997
Version C
Checked S.H.
Approved T.K.
RET 54_
Operators Manual
Station
Automation
Data subject to change without notice
1 Instructiuni de siguranta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2 Releul de protectie RET 54_ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3 Caracteristici grafice MMI/MIMIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Ecran mod idle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1.1 Ecran backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1.2 Display contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1.3 Selectarea limbii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1.4 Fereastra principala . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1.5 Fereastra de asistare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1.6 Testare ecran la alimentare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.2 Introducere butoane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.3 Butoane control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.3.1 Controlul obiectelor in MIMIC . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Programare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Nivele de operare MMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 Nivel utilizator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.1 Imaginea MIMIC(Configurarea imaginii). . . . . . . . . . . . . . . . . . . 13
4.1.2 Imagine masura . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
4.1.3 Fereastra de evenimente (EVENT view) . . . . . . . . . . . . . . . . . . . . .13
4.1.4 Alarme control (ALARM view) . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2 Parole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3 Nivelul tehnic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.3.1 Sistemul meniu al parametrilor. . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.3.2 Situatii speciale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.3 Meniuri. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.4 Meniu parametri . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
4.3.5 Deplasare intre meniuri . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.4 Setare parametrii . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.5 Salvare parametrii . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.6 Confirmarea si resetarea indicatorilor, iesirilor si registrelor. . . . 19
5 Indicatiile releului de protectie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
5.1 Prioritatea indicatiilor si mesajelor de ajutor . . . . . . . . . . . . . . . . . . . . . .20
5.1.1 Mesaje de ajutor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
5.1.2 Mesaje de indicare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
5.2 Indicatii de protectie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.3 Autosupraveghere (IRF). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.4 Indicarea supervizarii . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.5 Moduri de testare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.5.1 Testare functii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5.2 Test Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5.3 MIMIC test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.5.4 I/O test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.6 LED indicator verde . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
5.7 LED indicator galben . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.8 LED indicator rosu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.9 Interblocaje . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1MRS750500-MUM
1. Instructiuni de siguranta
!
!
!
Page 3
1MRS750500-MUM
2. RET 54_ Releu Releul de protectie RET 54_ este proiectat pentru protectie, control, masura si
supervizare a retelelor de medie tensiune. Poate fi folosit cu orice tip de celule
de Protectie
in sistem cu bara simpla, bara dubla si in sisteme duplex. Releul de protectie
include intrari energizate pentru transformatoare de curent si tensiune si pentru
senzori de curent si tensiune.
Releul de protectie RET 54_ se bazeaza pe un multiprocesor ce mareste performantele
acestuia. Semnalele digitale in combinatie cu un puternic CPU si comanda I/O faciliteaza
operarile in paralel si imbunatateste timpul de raspuns si corectitudinea. Interfata MMI
incluzand un LCD display cu diferite imagini face ca utilizarea locala a RET 54_ sa fie
sigura si foarte usoara. Interfata MMI instruieste utilizatorul in modul de folosire a releului.
Releul de protectie RET 54_ este o parte a automatizarilor statiilor PYRAMID pentru
Automatizarile din Reteaua de Distributie si extinde cu mult inainte functionalitatea si
flexibilitatea. Aceasta este posibila datorita tehnologiei state-of-the-art folosita in PYRAMID.
Page 4
1MRS750500-MUM
grafice MMI/MIMIC
un LCD display grafic, cu rezolutia de 128 x 160 pixeli, consta in 19 linii impartite
in doua ferestre
o fereastra principala (17 linii) in care sunt prevazute informatii detaliate
asupra obiectelor, evenimentelor, masurii,alarme si parametrii releului de protectie .
o fereastra de asistare (2 linii) pentru protectie, indicatori/alarme si mesaje
de avertizare
trei butoane pentru controlul obiectelor
opt LEDuri pentru alarme configurabile de diferite culori in concordanta cu configuratia
(off, verde, galben, rosu)
un LED de indicare pentru interblocaj si modul test
trei LEDuri de indicare a protectiei
un buton format din patru butoane cu sageti si butoane pentru Clear si Enter
un port serial de comunicatie izolat optic
backlight si control contrast
un buton programabil (F)
un buton de control distanta/local (buton de control pozitie)
LEDuri programabile
REF 541
21 kV
CB OK
AROFF
RF
L
R
Conector optic cu PC
E
1MRS xxxxxx
Uaux = 80...265 Vdc/ac Ion = 1/5 A (Io)
fn = 50 Hz
Un = 100/110 V (U) 98150
Uon = 100/110 V (Uo) 9509
In = 1/5 A (I)
3.1. Ecran
mod idle
3.1.1.
Ecranul este normal off. La apasarea unui buton de pe MMI, automat se deschide.
Dupa un timp (timpul de backlight),ecranul devine negru daca pe panou nu a fost
nici o activitate. La intreruperea alimentarii, ecranul se innegreste si apoi
reporneste dupa o pauza (durata de time-out).
Ecran
backlight
Page 5
1MRS750500-MUM
Ecranul poate fi activat printr-o intrare digitala a RET 54_. Cand intrarea digitala este
activata, se activeaza si ecranul. Pentru acest tip de functionare, trebuie inclusa
functia MMIWAKE in configuratia releului.
3.1.2.
Display
contrast
Pentru a avea o vedere optima se poate regla contrastul de pe MIMIC la nivel utilizator
si in Main Menu la nivel tehnic.
Prin apasarea butonului E si a butonului sageata SUS se mareste contrastul
sau a butonului sageata JOS se micsoreaza contrastul.
creste
Apasa E
si
scade
Fig. 3.1.2-1. Reglarea contrastului ecranului
Valoarea de contrast este stocata in memoria non-volatila si de aceea dupa
repornirea releului, contrastul este automat reglat in concordanta cu valoarea setata.
3.1.3
Selectare
limba
MAIN MENU
GROUP MENU
CONFIGURATION
MAIN MENU
Languages
Status
Protection lib.
Control lib.
Cond. Monit. lib
Measurements lib.
Communic. lib
Standard lib.
Tests
Information
Configuration
PARAMETER MENU
LANGUAGES
English
Suomi
Confirm
Cancel
Page 6
1MRS750500-MUM
3.1.4
Fereastra Fereastra principala informeaza utilizatorul de diferitele meniuri si stari ale obiectelor:
principala
configurare MIMIC , stare intreruptor, separator, etc.
evenimente
masura
alarme
setare perametrii
21 kV
CB OK
Ecran
LCD
Fereastra principala
17 linii
Fereastra de asistare
2 linii
AROFF
Fereastra principala
Informatii detaliate asupra:
- obiectelor
- evenimentelor
- masurilor
- alarmelor
- parametrilor
Fereastra de asistare
Informatii asupra:
- indicatorilor
- mesaje de ajutor
3.1.5
de
Fereastra
Fereastra de asistare asista utilizatorul. Indica doua tipuri de mesaje cu date detaliate
asistare ale releului de protectie, functiilor de protectie, etc.:
1. mesaje de ajutare a utilizatorului din timpul operarii
2. mesaje de indicare
3.1.6
Display test
Daca releul de protectie este conectat la tensiune auxiliara, ecranul este inactiv
at power up si este pornita testarea ecranului. Acest test include si LEDurile:
Primele 9 LEDuri de alarma sunt activate simultan cu diferite culori (rosu --> verde -> galben - OFF). In acelasi timp sunt testate si LEDurile indicatoare de protectie si cele
distanta/local/inactiv/logic sunt activate simultan pe o periada scurta (3 cicluri pentru
LEDurile de indicare).
Ecranul LCD este testat prin inchidere pentru scurt timp.
Page 7
1MRS750500-MUM
3.2. Button intro- MMI contine butoane pentru utilizarea releului de protectie.
duction
O atingere rapida a butonului sageata 'sus' sau 'jos' (mai putin de o secunda) este
interpretata ca un pas in sus sau in jos in meniu si ca pas minim sus sau jos in modul
de setare a parametrilor (digit, caracter, enumerator etc.).
Daca pozitia cursorului este pe prima linie, apasand sageata sus cursorul se va muta pe ultima linie
Daca pozitia cursoruluieste pe ultima linie, apasand sageata jos cursorul se muta pe prima linie
Butoane de navigare
sus
clear/cancel
enter/return
dreapta
stanga
jos
Sus/Jos
Stanga/Dreapta
Clear/Cancel
Page 8
1MRS750500-MUM
Enter
3.3. Buton de
control
LOCAL
L
R
REMOTE
L
R
INACTIV
L
R
Modul INACTIV
(LOGIC)
L
R
Page 9
1MRS750500-MUM
Modul LOCAL
(LOGIC)
L
R
Modul REMOTE
(LOGIC )
L
R
Configuratia releului de protectie trebuie sa contina functia de control pozitie element (COLOCAT) pentru a permite ca pozitia LOGIC sa fie selectata cu butonul
de control pozitie.
Local
R
Remote
Disabled
Logic
R
Fig. 3.3.-1. Secventa de control pozitie, cand este selectat modul LOGIC
(functia COLOCAT folosita in configuratie).
Local
R
Remote
R
Disabled
Fig. 3.3.-2. Secventa de control pozitie, cand nu este selectat moduul LOGIC
(functia COLOCAT nu este folosita in configuratie).
Page 10
1MRS750500-MUM
3.3.1.
Controlul
obiectelor
in MIMIC
Select
Close
I
Open
Freely programmable
3.4. Programare In partea din fata a releului de protectie este prevazut un conector de comunicare
seriala pentru conectarea la PC cu fibra optica prin RS 232 , tip 1MKC950001-1.
Aditional, este necesar un program pe PC pentru comunicare intre calculator
si releul de protectie.
Page 11
1MRS750500-MUM
4. Nivele de
operare MMI
MMI/MIMIC are doua nivele principale: nivelul utilizatorului si nivelul tehnic. Nivelul
utilizatorului este pentru masuri si monitorizare pe cand nivelul tehnic este folosit
programare releu de protectie si parametrizare.
M EASUREMENT
IL1-A
IL2-A
IL3-A
I0
I0b
U12 kV
U23 kV
U31 kV
U1 kV
U2 kV
U3 kV
U0-Volts
kW L1
kW L2
21 kV
CB OK
AROFF
EVENTS
800
803
800
0
0
20
20
20
11.5
11.5
11.5
0
7360
7360
2 Sec
CB spring ready
NOC3Low: Start
95-12-24
18:35:12;230
NOC3Low: StartRES
95-12-24
18:35:12;330
NOC3High: Start
95-12-24
14:25:52;720
NOC3High: Trip
95-12-24
14:25:52;760
U p d a t i n g v a l u e s
M I M I C E V E N T
Note!
Parola 3
poate fi folosita, daca
se doreste, cand
se acceseaza
Main Menu
ALARME
EVENIMENTE
MASURI
MIMIC
Event list
MEAS
Temperature
Interlocking
C clears Alarms
EVENT
MIMIC
ALARM
1 Sec
Meniu principal
GROUP MENU
PROTECTION
SUBGROUP MENU
PARAMETER MENU
NOC3Low
Actual settings
Setting group 1
Setting group 2
Control settings
Input data
Output data
Recorded data 1
Recorded data 2
Recorded data 3
SETTING GROUP 1
Operation mode
= Definite time
Start current
=3.1 x In
Operation time
= 041.03 s
Ti m e m u l t i p l i e r
= 0.78
menupict
MAIN MENU
Status
Disturb. record.
Protection lib.
Control lib.
Cond. Monit. lib
Measurements lib.
Communic. lib
Standard lib.
Tests
Information
Configuration
CUB3Low
DEF2Low
DEF2High
DEF2Inst
Freq1
Freq2
Freq3
Freq4
Freq5
Inrush3
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3High
NOC3Inst
4.1.Nivel utilizator La nivel utilizator, datele sunt primite in patru vederi diferite:
1.
2.
3.
4.
MIMIC
MASURI
EVENIMENTE
ALARME
Page 12
1MRS750500-MUM
CB OK
AROFF
RF
C
E
IL1-A
IL2-A
IL3-A
I0
I0b
U12 kV
U23 kV
U31 kV
U1 kV
U2 kV
U3 kV
U0-V
kW L1
kW L2
kW L3
800
803
800
0
0
20
20
20
11.5
11.5
11.5
0
7360
7360
7360
Updating values
EVENT
L
R
C
E
loadview
MIMIC
Fereastra de evenimente contine numele aplicatiei, numarul canalului, codul, data si durata
ultimelor 100 evenimente. Cel mai recent eveniment inregistrat este primul din lista de evenimente.
Page 13
1MRS750500-MUM
Events
NOC3Low:
31/E1
NOC3Low:
31/E0
NOC3High:
32/E1
NOC3High:
32/E3
95-12-24
18:35:12:230
95-12-24
18:35:12:330
95-12-24
14:25:52:720
95-12-24
14:25:52:760
Event list
MEAS
ALARM
L
R
eventvie
C
E
In fereastra de alarme sunt aratate toate alarmele prezentand si textele acestora. Alarmele de
control active se deosebesc de alarmele inactive prin LEDuri si textul alarmelor definit de
utilizator.
CB spring ready
SF6 gas density
Temperature
Interlocking
C clears alarms
EVENT
MIMIC
C
E
alarmvie
Cand se foloseste butonul de control pozitie trebuie data parola de acces 1 (daca
este activa). Pentru a intra in modul de setare, este necesara parola 2. Aceasta parola
se foloseste cat timp utilizatorul ramane la nivelul tehnic.
Page 14
1MRS750500-MUM
Setting group 1
Setting group 1
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
= 041.03 s
Time multiplier
= 0.78
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
= 041.03 s
Time multiplier
= 0.78
ENTER PASSWORD
ENTER PASSWORD
ENTER PASSWORD
_____H
******
******
Confirm
Apasati butonul E.
Sistemul cere cheia de
acces
sau
Cancel
C
pasword
Setting group 1
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
= 041.03 s
Time multiplier
= 0.78
4.3. Nivelul
tehnic
Meniurile din nivelul tehnic contin informatii pentru programarea releului de protectie.
Nivelul tehnic este accesat din MIMIC nivel utilizator prin apasarea butonului E
timp de 2s si prin cheia de acces daca este ceruta. Pentru a reveni la nivelul
utilizatorului, apasati butonul E timp de 1s in meniul principal.
Page 15
1MRS750500-MUM
MIMIC view
21 kV
CB OK
AROFF
Schimbare nivel
Nivel utilizator
Nota ! Password 3
poate fi folosita, daca se
doreste, la accesare
meniu principal
(vezi capitolul 4.2)
2 Sec
Main menu
1 Sec
MAINMENU
Status
Protection lib.
Control lib.
Cond. Monit. lib
Measurements lib.
Communic. lib
Standard lib.
Tests
Information
Configuration
Nivel tehnic
4.3.1.
Sistemul
Comunicarea interactiva intre operator si MMI se bazeaza pe meniuri. Pentru a activa
MAIN MENU se apasa butonul E timp de 2s.
meniu al
parametrilor Imaginile sunt folosite pentru citire parametrii setati, valori inregistrate, etc. Sistemul meniu
este divizat in trei sau patru nivele (depinzand de nivelul de acces):
MAIN menu
GROUP menu
SUBGROUP menu
PARAMETER menu.
Page 16
1MRS750500-MUM
SUBGROUP MENU
CUB3Low
DEF2Low
DEF2High
DEF2Inst
Freq1
Freq2
Freq3
Freq4
Freq5
Inrush3
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3High
NOC3Inst
PARAMETER MENU
NOC3Lo w
Actual settings
Setting group 1
Setting group 2
Control settings
Input data
Output data
Recorded data 1
Recorded data 2
Recorded data 3
SETTING GROUP 1
Operation mode
= Definite time
Start current
=3.1 x In
Operation time
= 041.03 s
Ti m e m u l t i p l i e r
= 0.78
Navigare
techlev
MAIN MENU
4.3.2.
Situatii
speciale
Meniuri
Meniul principal este primul din nivelul tehnic, iar prima linie este pentru header-ul
nivelului principal. Meniul principal este urmat de group menu si subgroup menu
care formeaza structura ierarhica.
4.3.4.
Parameter
menu
Page 17
1MRS750500-MUM
4.3.5.
Navigarea
printre meniuri
Butoanele sageata sus sau jos se folosesc la navigare in meniul parametru. Cand un
parametru clipeste, prin apasarea butonului E modul de setare este activat.
4.4. Setari
parametri
La activarea modului de setare prin apasarea butonului E, primul digit sau caracter al
valorii/textului de setare al parametrului clipeste (in cazul unei enumerari, intregul text
clipeste). In acest moment digitul/caracterul poate fi setat prin folosirea butoanelor sus/jos.
Urmatorul digit/caracter ce trebuie setat este activat prin apasarea butoanelor dreapta
sau stanga(la setare parametru de tip enumerator, sagetile stanga, dreapta nu au nici o functie).
Select parameter
G
i
v
e
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
p
a
s
s
w
o
r
d
s
e
l
e
c
t
i
o
n
2
i
f
n
e
e
d
Setting group 1
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
= 041.03 s
Time multiplier
= 0.78
Scroll for
wanted value
for digit
Confirm
E
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
Operation mode
= Definite time
Start current
= 4.1 x In
Operation time
OR
I f t e x t p a r a m e t e r,
select texttype
Setting group 1
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
= 041.03 s
Time multiplier
= 0.78
Cancel
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
parames
Setting group 1
Operation mode
= Definite time
Start current
= 3.1 x In
Operation time
= 041.03 s
Time multiplier
= 0.78
C
o
n
f
i
r
m E
If parameter with
numeric value select
digit
Page 18
1MRS750500-MUM
4.5. Salvarea
Parametrii pot fi salvati in trei moduri diferite:
parametrilor 1. prin executarea urmatoarelor secvente
2 sec.
Indicatii
neresetate
C 2 sec.
E
Resetare iesiri
si indicatori
C
5 sec. tot
Indicatii
resetate
E
Resetare registre,iesiri,
indicatii si memorie
View dependent
reset
C 2 sec.
Stergere mesaje
pentru ferestrele
MIMIC, MEAS,
EVENT, ALARM,
Main Menu
kuitsequ
4.6. Confirmare
si resetare
indicatori,
iesiri si
registre
.
.
1MRS750500-MUM
5. Indicatiile
Sunt doua tipuri diferite de mesaje de indicare disponibile in fereastra de asistare:
releului de protectie
informatii asupra functiilor releului de protectie si conditia acestuia (autodiagnosticare)
Use C-button to
clear Events
RF
L
R
Fereastra de asistare
C
E
1MRS xxxxxx
Uaux = 80...265 Vdc/ac Ion = 1/5 A (Io)
98150
fn = 50 Hz
Un = 100/110 V (U)
Uon = 100/110 V (Uo) 9509
In = 1/5 A (I)
5.1. Prioritatea
indicatiilor
si mesajelor
de ajutor
Mesajele din fereastra de asistare au o oarecare prioritate. Daca sunt activate simultan diferite
tipuri de indicatii, mesajul cu cea mai mare prioritate va apare pe ecran.
Prioritatea mesajelor:
1.
2.
3.
4.
5.1.1.
Mesaje
de ajutor
C clears alarms
EVENT MIMIC
assistvi
Page 20
1MRS750500-MUM
5.1.2.
Mesaje
de indicare
5.2. Indicatii de
protectie
Cand una din functiile de protectie ale releului porneste, numele functiei de protectie
corespunzatoare si textul ":START" este afisat in fereastra de asistare.
In cazul functiilor de protectie trifazate si bifazate , sunt afisate chiar fazele defecte
Un LED galben va clipi.
NOC3Low:START
L1, L2, L3
N O C 3 L o w : B LOCK
NOC3Low:TRIP
L1, L2, L3
NOC3Low:TRIP
L1, L2, L3
Page 21
1MRS750500-MUM
5.3. AutoRET 54_ este prevazut cu un sistem de autosupraveghere . Acest sistem din RET 54_
informeaza
supraveghere (IRF) LON/SPA. utilizatorul asupra existentei unui defect in MMI si magistralei de comunicatie
Indicatorul verde READY incepe sa clipeasca la detectarea unui defect. In acelasi timp
releul de protectie da un semnal de defect la iesirea de autosupraveghere a releului RET
54_. In plus, apare un text de indicare a defectului pe MMI al RET 54_. Un eveniment
E57 este generat pe comunicatia seriala (canal 0).
Textul de indicare defect de pe MMI consta din 2 linii cum se arata in urmatorul exemplu
.
SELF SUPERVISION
* I N T E R N A L FA U LT *
assisupv
Indicarea defectelor pe MMI are cea mai mare prioritate. Celelalte indicatii pe MMI nu se
suprapun peste IRF. Cand este primita o indicare a defectului, textul de indicare a defectului
ramane pe MMI. Prin apasarea butonului C timp de 2s textul de indicare a defectului
este sters de pe ecran, dar LED-ul verde clipeste in continuare. Acest mod de avertizare
prin indicator verde READY clipind nu poate fi anulat.
In cazul disparitiei defectului intern, textul de indicare a defectului ramane pe ecran,daca nu
a fost sters prin butonul C. Indicatorul verde READY nu mai clipeste si iesirea de alarma IRF
revine la stadiul normal. De altfel, un eveniment E56 este generat prin comunicatia seriala
(canal 0).
Codul defectului este stocat si poate fi citit din meniul principal al releului de protectie
Status/General/IRF code. Codul IRF include codul primului defect intern detectat de sistemul
de autosupraveghere.
Codul defectului descrie tipul defectului intern din RET 54_. La aparitia unui defect, codul
trebuie inregistrat si este dat personalului autorizat cand se face revizia.
5.4. Indicarea
monitorizarii
.
CMTCS1:SUPERV
Trip circuit sup
assisupi
Page 22
1MRS750500-MUM
5.5.Moduri de testare
Sunt multe moduri de testare pentru fiecare din urmatoarele patru categorii:
5.5.1.
Testare
functii
Functii
Control
MIMIC
I/O test
Este posibila activarea iesirilor, local de pe MMI sau extern prin comunicatia seriala.
Iesirile sunt activate prin folosirea parametrilor de control ai functiei
.
Pentru mai multe detalii, cititi manualul Technical Description of Functions.
5.5.2. Testare control Sistemul prevede o interblocare generala bypass mode (parameter Control/General/Inter/
bypass) ce se suprapune peste toate semnalele de interblocare. Activarea interblocarii bypass mode
activeaza semnalele active de interblocare ale tuturor obiectelor. De aceea toate actiunile de control sunt
posibile si semnalele active ale obiectelor controlabile nu sunt verificate cat timp obiectele sunt
comandate. Cat timp modul este activ LED-ul de interblocare de pe MMI este rosu si
clipeste. In plus fereastra de asistare a MIMIC va indica conditia speciala.
.
5.5.3
MIMIC tes
5.5.4.
I/O test
Modul de testare al MIMIC este accesat prin setare parametru Panel test start (1) in directorul
Main menu/ Tests/ Mimic [17]. Testul poate fi intrerupt prin apasarea oricarui buton. In concordanta,
se face acelasi Panel test ca la alimentarea releului (vezi capitolul Display test at power up).
Modul test este pentru testari intrarisi iesiri binare si efectul lor asupra functionarii releului.
Accesarea modului test pentru intrari sau iesiri se face prin setarea parametrului
Test mode
in Active din Tests/General la nivel tehnic. Utilizatorul trebuie sa accesezeh
modul test inainte de testare altfel schimbarile nu vor fi valide. Modul test poate fi anulat
prin setarea parametrului Test mode in Not Active sau prin punerea in functiune.
Nota! Daca utilizatorul uita sa anuleze modul test, acesta ramane activ si LED-ul READY
clipeste.
5.6. LED-ul
indicator verde
Page 23
1MRS750500-MUM
1MRS750500-MUM
5.8.LED-ul indicator
rosu
LED: OFF inactiv
LED: TRIP (CBFP) clipeste Daca declansarea se datoreza CBFP (circuit breaker failure protection),LEDul indicator rosu clipeste. Indicarea
este resetata prin apasarea butonului C pentru 2s.
.
5.9. Interblocaje
Page 25
1MRS750500-MUM
Page 26
Information
Management
Network
Management
Station
Automation
Communications
ABB Transmit Oy
Relays and Network Control
P.O. Box 699
FIN-65101 Vaasa
Finland
Tel. +358 10 22 4000
Fax. +358 10 224 1094