Sei sulla pagina 1di 2

Date:

Enquiry dated:
Project:
Quotation-no.:
Item:
Reference:
Drycooler coil
Capacity:
Surface:
Surface reserve:
Air
Volume flow:
Temperature:
Rel. humidity:
Velocity:
Pressure drop:
Tube volume:
Fin pitch:
Dry weight:
Finned length:
Finned height:
Total length:
Frame length:
Frame height:
Frame depth:

G?ntner Product Calculator Customer, 2006.1/2005-11-08, PL 1/2006

(1)

Re-Heating Coil
2015-01-26
4Rows 2Pass

GCO F/4/18/2.40/1050/A/C/S/ /015032


24.5 kW
73.8 m?
0.4 %
Inlet
7275 m?/h
10.0 ?C
100 %

Outlet
7527 m?/h
19.8 ?C
53 %
2.2 m/s
45 Pa

12.0 l
2.40 mm
41.3 kg
1050 mm
900 mm
1232 mm
1150 mm
1000 mm
200 mm

Fluid group 2 according to directive 67/548/EWG

Construction for:
Connections:
Tube pattern:
Heating medium:
Inlet:
Outlet:
Volume flow:
Pressure drop:
Tubes:
Fins:
Header:
Frame:
Circuits:
Passes:
Distributions:
Inlet:
Outlet:
Support tubes:

Casing
right side
staggered
Water (R718)(1)
27.0 ?C
24.0 ?C
7.00 m?/h
0.013 bar
Copper
Aluminum
Copper
Galv. Steel
1N
2
36
42.0 * 1.60 mm
42.0 * 1.60 mm
6

Drycooler coil
F/4/18/2.40/1050/A/C/S/ /015032
Construction for casing
Without varnishing

Quotation-no.:
Item:

4Rows 2Pass

GL
T
R

BL

BH

BT

Bottom sheet without drain hole

G?ntner Product Calculator Customer, 2006.1/2005-11-08, PL 1/2006

GL
T
BH
c
f

1232 mm
200 mm
900 mm
50 mm
50 mm

L
BT
a
d
h

1150 mm
100 mm
50 mm
50 mm
150 mm

BL
H
b
e
R

1050 mm
1000 mm
50 mm
50 mm
1/2"

Headers:
Connections:

42.0 * 1.60 mm
42.0 * 1.60 mm

Tube volume:
Heating medium:
Dry weight:
Surface:
Distributions:
Passes:

12.0 l
Water (R718)
41.3 kg
73.8 m?
36
2

Potrebbero piacerti anche