Sei sulla pagina 1di 2

Client:

PUMA ENERGY

Site location:

Project:

REVERSE ENGINEERING - TYPICAL BITUMEN TERMINAL

Document n:

167.04.12 LE601

Client Reference:

P-AGLBTT-LS-167.04.12-EL601

General Typical Power Consumption List

DISCIPLINE: PROCESS/ EQUIPMENT/ PIPPING/ CIVIL/ ARQUITECTURE/ ELECTRICITY/ INSTRUMENTATION/ AUTOMATION


PROJECT MANAGER: Jos Silva

10-09-12

FOR APPROVAL

NM

GS

HM

Revision:

Date:

Issued for:

Executed by:

Checked by:

Approved by:

Approved by (Client):

This document and all its content are property of Projecto.Detalhe, Lda. Copies and reproductions are not allowed without proper authorization. Consult site www.projectodetalhe.com for more information.
Model 40 - Revision 2

Model 40

General Typical Power Consumption List

Revision 2

CLIENT:

PUMA ENERGY

SITE LOCATION:

PROJECT:

ELECTRICITY

REVERSE ENGINEERING - TYPICAL BITUMEN TERMINAL

Document :
LOAD IND.

TAG

NAME

167.04.12-LE-601/ P-AGLBTT-LS-167.04.12-EL601
LOAD

C-Continuous Load

P- Priority

I- Intermitt. Load

NP-Not
Priority

POWER

ISSUE FOR APPROVAL

10-09-2012

NM

GS

HM

REVISION

DESCRIPTION

DATE

ISSUED

CHECKED

APROVED

STANDARD
CONNECTION
DIAGRAM

BOARD

NOTES:

Absorbed Power:
-pumps: Shaft power
-others: consumption in normal operation

CONSUMED POWER

ABSORBED

RATED

LOAD

[kW]

[kW]

[%]

FACTOR

cos

CONTINUE

INTERMITTENT

BUSBAR
STAND-BY

VOLTAGE

P-PROCESS
U-UTILITY

[kW]

[kVA]

[kW]

[kVA]

[kW]

[kVA]

[V]

P-2xx

BITUMEN PUMP

30,00

30,00

1,00

0,92

0,8

32,6

40,8

400

VFD

MCC

P-2xx

BITUMEN PUMP

30,00

30,00

1,00

0,92

0,8

32,6

40,8

400

VFD

MCC

P-7xx

FIRE FIGHTING JOCKEY PUMP

15,00

15,00

1,00

0,92

0,8

16,3

20,4

400

SS

MCC

P-9xx

POTABLE WATER PUMP SET

5,50

5,50

1,00

0,92

0,8

7,5

400

DOL

MCC

CP-1xx

COMPRESSOR

5,00

5,00

1,00

0,92

0,8

5,4

6,8

400

FEEDER

SB2.1

SB-xx

ADMINISTRATIVE BUILDING AND CONTROL


SWITCHBOARD

30,00

30,00

1,00

0,8

30

37,5

400

FEEDER

MCC

SB-xx

WHAREHOUSE SWITCHBOARD

25,00

25,00

1,00

0,8

25

31,3

400

FEEDER

MCC

SB-xx

COMPRESSOR'S SWITCHBOARDS

10,00

10,00

1,00

0,8

10

12,5

400

FEEDER

MCC

SB-xx

GATE HOUSE SWITCHBOARD

3,00

3,00

1,00

0,8

3,8

230

FEEDER

MCC

10

SB-xx

INSTRUMENTATION SWITCHBOARD

5,00

5,00

1,00

0,8

6,3

400

FEEDER

MCC

11

SB-xx

UTILITIES SWITCHBOARD

26,00

26,00

1,00

0,8

26

32,5

400

FEEDER

MCC

12

SB-xx

BOILER UNIT SWITCHBOARD

75,00

75,00

1,00

0,8

75

93,8

400

FEEDER

MCC

13

HOP-xxx

HOT-OIL PUMP

5,50

5,50

1,00

0,92

0,8

7,5

400

DOL

MCC

14

HOP-xxx

HOT-OIL PUMP

St

5,50

5,50

1,00

0,92

0,8

7,5

400

DOL

MCC

15

HOP-xxx

HOT-OIL PUMP

55,00

55,00

1,00

0,92

0,8

59,8

74,8

400

SS

MCC

16

HOP-xxx

HOT-OIL PUMP

St

55,00

55,00

1,00

0,92

0,8

59,8

74,8

400

SS

MCC

17

HOP-xxx

HOT-OIL PUMP

11,00

11,00

1,00

0,92

0,8

12

15

400

DOL

MCC

18

HOP-xxx

HOT-OIL PUMP

St

11,00

11,00

1,00

0,92

0,8

12

15

400

DOL

MCC

205,2

148,1

185,3

77,8

97,3

ST-Standby Load

NOTES

R
E
V

Future

LOAD BALANCE
TOTAL BT
FUTURE - TOTAL BT
TOTAL BT
NORMAL OPERATION

kW

kVAr

kVA

(100% Continuous Load + 100% Intermittent Load)

312,1

234,70

390,5

FUTURE - (100% Continuous Load + 100% Intermittent Load)

32,6

24,53

40,8

TOTAL - (100% Continuous Load + 100% Intermittent Load)

344,7

259,23

431,3

164
0

32,6

40,8

164

205,2

180,7

226,1

77,8

97,3

NOTES:
All consumers values and considerations presented should be considered as typical examples