BULETIN VERIFICARE Nr. : 4/1 Data : 12.05.

2014
la cablu pt. cel.: LEA FACAENI
Denumirea lucrarii: STAIA GURA IALOMITEI 400 kV
Nr
crt

Destinatie cabluri

Marca
Cablu

Tip
Cablu

Continuitate

la

de la

Rezistenta
Izolatie
[MOhm]

Lungime
[m]

=C00+NE91 =C00+NE1

+C00-NE1-W014

NYCY 4x16

da

410

185

=C00+NE91 =C00+NE7

+C00-NE2-W024

NYCY 4x16

da

427

185

=C00+NE91 =C09+S1

+C00-NE91-W401

NYCY 5x2,5

da

3280

25

=C00+NE91 =C08+S1

+C00-NE91-W402

NYCY 5x2,5

da

3510

25

=C00+NE91 =C00+NE92 +C00-NE91-W403

NYCY 5x2,5

da

5418

15

=C00+NE91 =Vestas

+C00-NE91-W404

NYCY 5x2,5

da

5270

15

=C00+NK91 =C00+NK1

+C00-NK1-W105

NYCY 2x16

da

460

185

=C00+NK91 =C00+NK4

+C00-NK4-W155

NYCY 2x16

da

418

185

=C00+NK91 =C09+S1

+C00-NK91-W401

NYCY 7x1,5

da

2850

25

10

=C00+NK91 =C08+S1

+C00-NK91-W402

NYCY 7x1,5

da

2796

25

11

=C00+NK91 =C00+NE91 +C00-NK91-W403

CSYEcY-F 24x1,5

da

7350

12

=C00+NK91 =C09+S1

+C00-NK91-W405

NYCY 7x1,5

da

2480

25

13

=C00+NK91 =C08+S1

+C00-NK91-W406

DV204/3 2x6

da

2618

25

14

=C00+NK91 =C00+NE91 +C00-NK91-W407

CSYEcY-F 24x1,5

da

6492

15

=C08+S1

=C08+S01

+C08-W101

CSYEcY-F 24x1,5

da

3269

25

16

=C08+S01

=C08+S1

+C08-W201

CSYEcY-F 24x1,5

da

2963

25

17

=C08+S01

=C08+S1

+C08-W202

CSYEcY-F 14x1,5

da

3218

25

18

=C08+S01

=C08+S1

+C08-W221

CSYEcY-F 24x1,5

da

3267

25

19

=C08+S01

=C08+S1

+C08-W222

CSYEcY-F 24x1,5

da

2848

25

20

=C00+NK91 =C08+S01

+C08-W260

NYCY 14x1,5

da

5628

21

=C08+S01

+C08-W261

NYCY 9x1,5

da

6103

22

=C09+SW1 =C09+S1

+C09-W100

CSYEcY-F 14x1,5

da

3047

25

23

=C09+SW1 =C09+S1

+C09-W101

CSYEcY-F 24x1,5

da

3182

25

24

=C09+SW1 =C09+S1

+C09-W102

CSYEcY-F 14x1,5

da

2745

25

25

=C09+SR2

=C09+S1

+C09-W103

CSYEcY-F 14x1,5

da

2940

25

26

=C09+SW1 =C09+S1

+C09-W104

CSYEcY-F 14x1,5

da

3018

25

27

=C09+SR2

=C09+SW1

+C09-W105

CSYEcY-F 7x1,5

da

6200

28

=C09+SR2

=C09+S1

+C09-W110

CSYEcY-F 7x1,5

da

2870

25

29

=C09+SR2

=C09+S1

+C09-W111

NYCY 4x6

da

3001

25

30

=C09+SW1 =C09+S1

+C09-W112

NYCY 4x6

da

3378

25

31

=C09+SW1 =C09+S1

+C09-W113

NYCY 4x6

da

2906

25

32

=C09+SW1 =C09+S1

+C09-W114

NYCY 4x6

da

2982

25

33

=C09+SW1 =C09+S1

+C09-W115

NYCY 4x6

da

2709

25

34

=C09+SW1 =C08+S01

+C09-W118

NYCY 4x6

da

5699

35

=C09+SR2

=C09+S1

+C09-W151

NYCY 4x4

da

2595

25

36

=C09+SR2

=C09+S1

+C09-W152

NYCY 4x4

da

2833

25

37

=C09+SR2

=C09+S1

+C09-W153

NYCY 4x4

da

2941

25

38

=C09+SW1 =C09+S1

+C09-W154

NYCY 4x4

da

2717

25

39

=C09+S1

=C08+S1

+C09-W155

NYCY 4x4

da

3003

25

40

=C09+S1

=Vestas

+C09-W156

NYCY 4x4

da

3106

25

=C09+SR2

Aparate utilizate: Continuitate: multimetru APPA 82 , Nr 75300329.


Rez. Izolatie: Megometru BM11D , Nr 0296.
Concluzie: Masuratorile s-au efectuat in conformitate cu normativul NTE 002/03/00 si normativul PE 116/94.
Valoarea minima a rezistentei de izolatie corectata la 1km si 20C trebuie sa fie de minim 3 100M x km.
Din punct de vedere al masuratorilor cablurile corespund, sunt bune pentru exploatare.
Verificat:

Controlat: