Zone Sizing Summary for Audio Visual Room & CR

Project Name: Shining star


Prepared by: CEC

12/16/2014
03:30PM

Air System Information


Air System Name
Equipment Class
Air System Type

Number of zones
Floor Area
Location

Audio Visual Room & CR


TERM
2P-FC

1
698.9 ft
Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM
Space CFM

Calculation Months
Sizing Data

Sum of space airflow rates


Individual peak space loads

Jan to Dec
Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
22.5

Design
Air
Flow
(CFM)
1025

Minimum
Air
Flow
(CFM)
1025

Time
of
Peak
Load
Jul 1500

Maximum
Heating
Load
(MBH)
1.9

Total
Coil
Load
(MBH)
27.5

Sens
Coil
Load
(MBH)
23.2

Coil
Entering
DB / WB
(F)
75.6 / 62.9

Coil
Leaving
DB / WB
(F)
54.7 / 53.5

Water
Flow
@ 10.0 F
(gpm)
5.50

Heating
Coil
Ent/Lvg
DB
(F)
-1.0 / -1.0

Htg Coil
Water
Flow
@20.0 F
(gpm)
0.00

Fan
Design
Airflow
(CFM)
1025

Fan
Motor
(BHP)
0.323

Zone
Floor
Area
(ft)
698.9

Zone
CFM/ft
1.47

Terminal Unit Sizing Data - Cooling

Zone Name
Zone 1

Time
of
Peak
Load
Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Zone Name
Zone 1

Heating
Coil
Load
(MBH)
0.0

Fan
Motor
(kW)
0.241

OA Vent
Design
Airflow
(CFM)
0

Space Loads and Airflows


Zone Name /
Space Name
Zone 1
Audio Visual Room & CR

Hourly Analysis Program v4.50

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

22.5

Jul 1500

1025

1.9

698.9

1.47

Page 1 of 1