AIR OUTLETS:
1. AIR OUTLETS LOCATIONS ARE INDICATIVE. FINAL LOCATIONS ARE TO BE
COORDINATED BY THE CONTRACTOR WITH THE LATEST ARCHITECTURAL,
ELECTRICAL AND INTERIOR DECORATOR DRAWINGS.
2. FINAL LOCATION OF LOUVERS TO BE CO-ORDINATED WITH ARCH'S AT SITE.
COLOUR SUBJECT TO ARCH'S APPROVAL.
3. ALL SUPPLY AND RETURN OUTLETS PLENUM BOXES SHALL BE INTERNALLY
LINED AND PAINTED BLACK.
4. ALL FRESH AIR LOUVERS SHALL HAVE SAND TRAPS WITH 2" WASHABLE
FILTER.
5. ALL DIFFUSERS AND GRILLES SHALL HAVE BUILT-IN V.C.D EXCEPT WHEN
THERE IS ONLY ONE DIFFUSER OR GRILLE CONNECTED TO THE F.C.U.
6. NON RETURN DAMPERS (NRD) SHALL BE PROVIDED FOR EACH DUCTED
EXTRACT FAN.
7. ALL OUTLET SIZES ARE IN MM, AREA IN SQ.M AND THE FLOW RATE IN CFM.
8. ALL SLOTS SHALL BE 20mm SLOT WIDTH AND LINEAR GRILLES 15-2WAY-12mm
SPACING OR AS PER DRAWINGS.
9. GRAVITY LOUVERS SHALL HAVE FREE AREA NOT LESS THAN 82% OF FACE
AREA AND SAND TRAP LOUVER SHALL HAVE EFFICIENCY NOT LESS THAN 60%
AND FREE AREA NOT LESS THAN 32% OF FACE AREA.
10. AIR OUTLETS THROW SELECTION SHALL BE BASED ON AT 0.5 M/S TERMINAL
VELOCITY.
NOISE CONTROL:
1. CONTRACTOR TO ENSURE THAT THE SPECIFIED ROOM NOISE LEVEL
SHALL BE BELOW THE NOISE CRITERIA.