Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Emergency Standby
Engine Generators
Kenneth L. Box P.E.
Regional Sales
Manager Power
Electronics
Cummins Power
Generation
TIME (SECONDS)
10
0.1
0.05
10
AMPS (TIMES RATED)
Engine Generators
Control
Monitoring & Alarms
Engine Protection
System Protection
Paralleling
Applications
Alternator Protection
Devices
27
59
Device
32
Device
40
Device
46
Device
51V
Device
51G
Device
60
Differential Protection
For rapid detection of
generator to or
-G faults.
When NGRs are
used, 87G should be
used.
Used for protection of
larger generators
Zone protection
Device
87
Temperature Protection
Resistance
temperature detectors
are used to sense
winding temperatures.
A long term
monitoring philosophy
that is not readily
detected by other
protective devices
RTDs
MEDIUM MACHINES
1000kW to 12,500
kVA regardless of
voltage
LARGE MACHINES
Up to 50,000 kVA
regardless of voltage
Any recommendation
based entirely on
machine size is not
entirely adequate.
The importance of the
machine to the
system or process it
serves & the reliability
required are the
important factors
SW
KW
VM
VM
KWH
SW
SW
PF
HZ
HZ
40
27
46
32
81
25C
GOV
51V
59
86
25
AVR
SURGE SUPPRESSORS
AM
GENSET
SS
TRIP
CLOSE
NFPA70 - NEC
445.12(A) Overload Protection
Generators, except AC generator exciters, shall be protected from
overloads by inherent design, circuit breakers, fuses, or other
acceptable overcurrent protective means suitable for the conditions of
use.
240.15(A)
Overcurrent Device Required. A fuse or an overcurrent trip unit of a
circuit breaker shall be connected in series with each ungrounded
conductor. A combination of a current transformer and overcurrent
relay shall be considered equivalent to an overcurrent trip unit.
240.21(G) Conductors from Generator Terminals
Conductors from generator terminals that meet the size requirements of
445.13 shall be permitted to be protected against overload by the
generator overload devices) required by 445.12
100
GENERATOR
GENERATOR
THERMAL
THERMAL
DAMAGE
DAMAGE
CURVE
CURVE
10
10
10
TIME (SECONDS)
TIME
TIME(SECONDS)
(SECONDS)
PROTECTIVE RELAY
CURVE
1
1
1
0.1
0.1
0.1
GENERATOR
THERMAL DAMAGE
CURVE
0.05
0.05
11
333
10
10
10
AMPS
AMPS(TIMES
(TIMESRATED)
RATED)
AMPS
(TIMES
RATED)
100
100
100
GEN FLA
Time
800A
INSULATED
CASE CB
800A
MOLDED
CASE CB
GENSET
DAMAGE
CURVE
Gen Relay
Current
GENSET
CONTROL
ENG
,
SHUTDOWN
87
51
86
TRIP
SWITCHGEAR
52
Recommendations
Use the IEEE Recommended protection schemes with a dose of common sense.
Always carefully consider the balance of protection versus reliability, especially when
the protection is for equipment that is operating for very few hours.
With some mfrs. the alternator current sensing function monitors faults inside the
machine. When the machine incorporates protection for the alternator from
overcurrent conditions based on an I2t function, and regulates single phase faults
differential protection is optional.
On 15kV class machines, the alternator stator is expensive enough that it would
probably be repaired rather than replaced, so it will make more sense to try to limit
damage in the machine and have it repaired, in the general case.
In cases where it is decided to use differential protection, it is desirable to minimize
the zone of protection and use properly sized and matched CTs so that the
probability of nuisance tripping is reduced. Since the generator set provides
overcurrent protection from the alternator out, differential protection can be applied
with matched CTs provided and mounted at the wye side and alternator output,
preferably in the terminal cabinet. The differential relay can be mounted in the vicinity
of the generator set or in the switchgear.
Recommendations
A good standardized design is
superior to an optimized custom
design.
Custom designs breed custom
problems
Questions?
%Current
500
400
300
Regulates at 3X Rated
Shuts down before damage
200
100
0
0
10
time, sec
15
20
600
Alt %Standby L1 Current
500
Percent Current
300
200
100
0
0
tim e, sec
120
100
80
60
40
20
0
0
4
tim e, sec