132 kV

TEST REPORT S/S-NHZP

ISOLATORS. Sheet 1 of 2

Customer : HZL Consultant : UHDE INDIA


Station : 132 kV Switch Yard. Feeder/Location : Transformer # 1(Bay-1)
Manufacturer : ABB Supplier : ABB
Isolator Type : MT 50 Year of manufacture : 2004
Order No. : EPC – 7A Date of Test : 20-08-04

Serial No. : 306924-40-001 / MM1

Name Plate Details of Isolator & Motor : -

Motor Make / Rating Make : Rotomac / Rating : 0.63HP / RPM : 4000


Aux. Volt / Duty 220V, AC, / S2
Motor Current / Serial No. 2.8 Amps. / 4190404
Isolator Rating 145KV
Isolator Designation 89A

10 Visual inspection : -
1.1 Supporting structure  O.K.

1.2 Control wiring Check  O.K.

1.3 Earthing  O.K.

2.0 Insulation Resistance Measurement :- ( 5000 Volts Megger )


( Values in Mega Ohms )

Reference Pole & Earth Across Pole Remarks


Isolator Closed Isolator Open
R - Phase 50K 50K OK

Y - Phase 50K 50K OK


B - Phase 50K 40K OK

Contractor Wittnessed - Consultant Wittnessed - Client


Tested by UHDE- INDIA HZL
Name Mr. R.MUTHU MAMUNDI Mr. PATHAK Mr.C.M.TRIPATHI
Signature
Date
132 kV
TEST REPORT S/S-NHZP

ISOLATORS. Sheet 2 of 2

3.0 Contact Resistance Measurement : -

Current Injected in Amps Resistance measured in


Micro Ohms
R- Phase Y – Phase B - Phase

100 Amps. DC
16.21 16.28 15.18

4.0 Operational Check : -

Sl.No. Operation Local Remote Result


1 Manual Close Checked OK OK
2 Manual Open Checked OK OK
3 Electrical Close Checked OK Checked OK OK
4 Electrical Open Checked OK Checked OK OK
5 Heating & Lighting Checked OK OK

5.0 Test Equipment Details : -

Sl. No. Test Instrument Make Serial No.


1 Digital Multimeter Rishab 013851
2 Tong Tester Lutron WA70530
3 Micro Ohm Meter – 100A, Eltel 20043503
DC
4 Megger Riken 012 /M0184

Contractor Wittnessed - Consultant Wittnessed - Client


Tested by UHDE- INDIA HZL
Name Mr. R.MUTHU MAMUNDI Mr. PATHAK Mr.C.M.TRIPATHI
Signature
Date