POWER WIRING BY E.C.

PREPARE & PAINT ALL EXPOSED


SURFACES "DURAN 0012 BRONZE"
COLOR TO MATCH EXISTING.
SEE DETAIL OF
CONDENSATE TRAP 1 1/2" FIBERGLASS INSULATION DROP FROM MAIN
WITH CONTINUOUS VAPOR
FAN HOUSING ROOF TOP AIR BARRIER.
BRANCH DUCT INLET DUCT PER VAV BOX SCHEDULE
CONDITIONING UNIT
MAXIMUM FLEXIBLE DUCT 4'-0" LONG.
FAN MOTOR CONDENSATE DRAIN LINE. SEE SCHEDULE FOR SIZE.
TRAP DISCHARGE TO ROOF DRAIN. VOLUME DAMPER
CD
FAN FLASH WATERTIGHT
FACTORY ROOF CURB BUILT TO
COPPER COUNTER FLASHING DRAIN LEVEL PITCHED ROOF. FLEX CONNECTOR
MAINTAIN ACCESS
BY MECH. CONT.
TO FILTER.
LOW PRESSURE
ROOF FLASHING BY 12" MIN. FLEX DUCT DUCTWORK -
ROOFING CONT. ROOF EXCEPT IN ROUND DUCT TO DIFFUSER ACOUSTICALLY
SEALANT EXPOSED AREAS UNLESS INDICATED OTHERWISE
SMOKE DETECTORS LINED
FAN CURB BY FAN 2" MIN. FLEXIBLE CONNECTION (SEE PLANS FOR SIZE)
MOTORIZED ON ALL UNITS OVER
MANUF. DAMPER SD
2000 CFM
SHEETMETAL DIFFUSER PLENUM
DUCT CONNECTION SUPPLY AIR RETURN AIR
ACCESS
DOOR SUPPLY TO
DIFFUSERS
PLENUM SIZE CEILING
LINED DUCTWORK NOTE:
AS PER PLAN SLOT DIFFUSER SUPPORT UNIT ON WAFFLE PAD
CEILING INSULATE DUCTWORK MAINTAIN 4" CLEARANCE TO W/TRIM TO MATCH CEILING
TURNING VANES OR USE NEOPRENE VIBRATION
ALL OBSTRUCTIONS.
ISOLATION HANGERS.
LINEAR
ROOF EXHAUST FAN (UPBLAST) ROOF TOP A/C UNIT DETAIL DIFFUSER DETAIL VAV BOX INSTALLATION DETAIL
NO SCALE NO SCALE NO SCALE
NO SCALE

CONDENSATE DRAIN

HOT GAS &


MOUNT AS HIGH
LIQUID LINES
AS POSSIBLE
CC
CRAC

1/2" ---
INSTALL LEVEL EACH WAY

AIR
(1) SETS OF REFRIGERANT URN SECURE TO
RET FLOOR STAND WITH TURNING VANE
SUCTION AND LIQUID LINES. EQUIPMENT
TO MATCH RAISED FLOOR HEIGHT. DRAWBAND AND
SEE MANUFACTURERS RAIL
SILICONE SEALANT AT
RECOMMENDATIONS FOR
EACH PENETRATION
SIZES.
NEOPRENE
2" HIGH 16 GAUGE WAFFLE
GALVANIZED AUXILLARY PATE "PIPE
PATE PAD
DRAIN PAN. EXTEND 4" PORTAL"
PREFABRICATED
BEYOND UNIT 3 SIZE. PREMOLDED
EQUIPMENT RAIL
EXTEND AT PIPE CURB CAP
CONNECTION END. FLASH
PATE UP
PREFABRICATED CURB
ROOF CURB

CONDENSATE PUMP - HARTEL MODEL A-2. VOLTAGE


TO SUIT CRAC UNIT LOCATED IN AC BASE
PROVIDE
SUPPLEMENTARY LOCATE
PROVIDE REMOTE MOISTURE DETECTORS AT BOTH
STEEL AS REQUIRED UNDER
ENDS OF DRAIN PAN. WIRE TO AC UNIT ALARM.
CONDENSER
NO SCALE
NOTE: SET HEIGHT OF PREFABRICATED EQUIPMENT
COMPUTER ROOM AIR CONDITIONING UNIT INSTALLATION DETAIL RAIL TO ALLOW FOR ROOF PITCH TO SUPPORT
NO SCALE EQUIPMENT LEVEL EACH WAY.

COMPUTER ROOM CONDENSER DETAIL


MAIN DUCT

SHEET METAL
COLLAR AROUND SHEET METAL
DUCT PERIMETER PIPE SLEEVE AIR MINIMUM 5' BETWEEN TAKEOFFS
FLOW
1/2" MAX MAIN DUCT
(TYPICAL) AIR HANDLING UNIT
(1) X DUCT HEIGHT
DUCT PENETRATION CUSHION HEAD TAPERED CONNECTION 45º ANGLE
24 x 24 GR UNLESS
SHOWN IS WHERE BELL MOUTH DUCT (IF MAIN DUCT IS RECTANGULAR) OR
OTHERWISE NOTED
FIRE DAMPER IS NOT CONNECTION SEALANT CONICAL CONNECTION (IF MAIN DUCT
NOTE #1 26 x 12 UNLESS
REQUIRED BY CODE. OR 45º BOOT IS ROUND) L = 1/4 W; 4" MIN
PLUG OTHERWISE NOTED
1/2" MAX 1 1/2" FOR DRAW
(TYPICAL) THRU UNITS
PARTITION VOLUME
TYPE "L" COPPER DAMPER CLAMP W
OR SCH 40 PVC
PARTITION
NOTES: LOW PRESSURE 1" ACOUSTICAL LINING L
EXTEND & 36 x 18 GRILLE UNLESS
SPILL TO IWR FLEXIBLE ROUND BRANCH DUCT
1. AT FIRE RATED PARTITIONS, ADD ADDITIONAL LAYER OF FIRE SAFING OTHERWISE NOTED
DUCT (6'-0" MAX.)
INSULATION AROUND PENETRATION SO AS TO FILL CAVITY. SUPPLY AIR
OR SHEET METAL
2. DUCT AND PIPE PENETRATIONS THRU CORRIDOR WALLS ABOVE THE PLUG DUCT TAKE-OFF RETURN/ EXHAUST AIR
DUCT.
CEILING ARE TO BE FIRE STOPPED AROUND THE PENETRATION.

DUCT AND PIPE PENETRATIONS DETAIL OF CONDENSATE TRAP BRANCH DUCT DETAIL TRANSFER DUCT DETAIL BRANCH TAKE-OFFS
NO SCALE NO SCALE NO SCALE NO SCALE
NO SCALE