4KV AC MOTOR TEST REPORT


Usage purpose

Regeneration water pump A

Installation location

Chemical system

1.Nameplate:
Type

Y2-160M1-2TH

Rated capacity

11KW

Rated voltage

380V

Rated current

21.3A

Frequency

50HZ

LWdB

Connection Symbol

Ex-factory date

2007.12

Revr/min

2930

Equipment Code

27109805

Manufacturer

WANNAN ELECTRIC MACHINE CO.LTD

2. Test Polarity:
U1 V1 W1 Same polarity
Applied instrument: MF14 Multimeter operation
3. Test Insulation Resistance:
Windings

Insulation ResistanceM
R15

R60

U-V W & G

100000

V-U W & G

100000

W-U V & G

100000

Applied instrument: UT512/1000V


4. Test Resistance:
Windings

U1-U2

V1-V2

W1-W2

Resistance ()

0.777

0.773

0.774

Applied instrument: QJ44 DC. resistance bridge


5.Test Conclusion:
OK
Tested Date
Date:
Tested By:

PT.TRUBA JAYA ENGINEERING

2008.09.26
Date:
Approved By:

CHENGDA ENG. CORP.OF CHINA

Page 1of 1