Sei sulla pagina 1di 2

Project :

Client :

Contractor :

OIL METERING
STATIONS

Designer:

IMTECH INDUSTRY B.V.

OIL METERING STATIONS


TANK GAUGING SYSTEM
MS No. 31 SATUC

PROJECT NO. 2281013

CABLE LIST SIGNAL CABLES

DOCUMENT NO.: 2281013-031-01-0125

1.0
0.1
Rev.

28.06.11
28.03.11
Date

Issued for approval


Issued for approval
Description

Costea A.
Costea A.
Designed

Olaru C.
Olaru C.
Checked

Olaru D.
Olaru D.
Project manager

Dimitriu R.
Dimitriu R.
Approved

No.

Cable Tag No.

From

To

Cable/Wire Type

No. of cores x sqmm


per conductor

Voltage
Level/Signal

Length
(m)

Remarks

1
2

K-RDU-R1

RDU-R1

LT-R1

RE-2X(st)YSWBY-fl IS

2x2x1,3

MFR'S STD.

25

1, 2, 3, 5

K-MST-R1

MST-R1

8 wire x 1sqmm/wire

MFR'S STD.

1, 2, 3, 4, 5

3
4
5

K-LT-R1

LT-R1

LT-R1
FCU-2160(FIELD
BUS PORT 1)

RE-2X(st)YSWBY-fl

1x2x1,3

TRL/2 field bus.

130

1, 2, 3, 5

K-RDU-R3

RDU-R3

LT-R3

RE-2X(st)YSWBY-fl IS

2x2x1,3

MFR'S STD.

25

1, 2, 3, 5

K-MST-R3

MST-R3

8 wire x 1sqmm/wire

MFR'S STD.

1, 2, 3, 4, 5

K-LT-R3

LT-R3

LT-R3
FCU-2160(FIELD
BUS PORT 2)

RE-2X(st)YSWBY-fl

1x2x1,3

TRL/2 field bus.

95

1, 2, 3, 5

7
8
9
10
11
12
13
14
15

Remarks: 1. Cable acc. Project Spec. no. 2281013-0-01-058


2. The length stated on cable list shall be used for general guidance. Cable lengths are estimated.
3. Before cutting the cables from the cable drum, the actual route length shall be measured and checked against the cable length stated on the instrumentation
cable list.
4. Wires will be delivered in complete with MST. Wires shall be protected in flexible tube, UV resistant, fire-resisting, hydrocarbons resisting.
1m flexible tube length shall be provided for each MST.
5. Homologated for zone 1G IIB T4.
Document number:
2281013-031-01-0125

File :
2281013-031-01-0125_Cable list Signal cables

Project No.:
2281013/2011

Sheet