RTC048200405U

SPD

Rectifier

AC Input

Non-Priority Load

4
L

C16

C16

C16

C16

230/400V
IEC60947-2
GB14048.2

230/400V
IEC60947-2
GB14048.2

230/400V
IEC60947-2
GB14048.2

230/400V
IEC60947-2
GB14048.2

6000A

6000A

6000A

6000A

PUTIAN

PUTIAN

Surge Arrester

Surge Arrester

Uc:
In:

255VAC
Uc:

20kA(8/20us)

In:

Imax: 40kA(8/20us)
Up:

N-PE

Battery

Priority Load
1

C50

C63

C63

C10

C10

C6

C6

C125

230/400V
IEC60947-2
GB14048.2

230/400V

230/400V

230/400V

230/400V

IEC60947-2
GB14048.2

IEC60947-2
GB14048.2

IEC60947-2
GB14048.2

IEC60947-2
GB14048.2

230/400V
IEC60947-2
GB14048.2

230/400V
IEC60947-2
GB14048.2

230/400V
IEC60947-2
GB14048.2

6000A

6000A

6000A

6000A

6000A

6000A

6000A

6000A

255VAC
20kA(8/20us)

Imax: 40kA(8/20us)

1.6kV

Up:

1.6kV

AC INPUT
85-300Vac

Rectronic

Rectronic

Rectronic

Rectronic

RM2048A

RM2048A

RM2048A

RM2048A

AC Input
Nominal Input Voltage: 220V .
Input Voltage Range: 90-300V.
Maximum Input Current: 12.3A;
Frequency Range: 45 65 Hz;
Power Factor:

0.99;

Efficiency: >93%;
AC input circuit breaker: 50A/2P x 1;
DC Output
Nominal Output Voltage: 48V;
Output Voltage Range: 42-60V;
Maximum Current: 41.7A;
Maximum Output Power 2kW

DC Distribution:
Priority Load circuit breakers: 63A /1P x 2;
Non-Priority Load circuit breakers: 10A /1P x 2,6A /1P x 2;
Battery: 1x 125A/1P battery circuit breakers;
Battery temperature sensor 8m x 1;
BLVD: 200A battery LVD fitted
LLVD: 100A load LVD fitted
Rectifier RM2048A 4;
Controller SM12 x 1 ;
Mechanical
Dimensions, W, H, D:

482mm(standard 19" rack) , 222.5mm (5U), 300mm