SPD
Rectifier
AC Input
Non-Priority Load
4
L
C16
C16
C16
C16
230/400V
IEC60947-2
GB14048.2
230/400V
IEC60947-2
GB14048.2
230/400V
IEC60947-2
GB14048.2
230/400V
IEC60947-2
GB14048.2
6000A
6000A
6000A
6000A
PUTIAN
PUTIAN
Surge Arrester
Surge Arrester
Uc:
In:
255VAC
Uc:
20kA(8/20us)
In:
Imax: 40kA(8/20us)
Up:
N-PE
Battery
Priority Load
1
C50
C63
C63
C10
C10
C6
C6
C125
230/400V
IEC60947-2
GB14048.2
230/400V
230/400V
230/400V
230/400V
IEC60947-2
GB14048.2
IEC60947-2
GB14048.2
IEC60947-2
GB14048.2
IEC60947-2
GB14048.2
230/400V
IEC60947-2
GB14048.2
230/400V
IEC60947-2
GB14048.2
230/400V
IEC60947-2
GB14048.2
6000A
6000A
6000A
6000A
6000A
6000A
6000A
6000A
255VAC
20kA(8/20us)
Imax: 40kA(8/20us)
1.6kV
Up:
1.6kV
AC INPUT
85-300Vac
Rectronic
Rectronic
Rectronic
Rectronic
RM2048A
RM2048A
RM2048A
RM2048A
AC Input
Nominal Input Voltage: 220V .
Input Voltage Range: 90-300V.
Maximum Input Current: 12.3A;
Frequency Range: 45 65 Hz;
Power Factor:
0.99;
Efficiency: >93%;
AC input circuit breaker: 50A/2P x 1;
DC Output
Nominal Output Voltage: 48V;
Output Voltage Range: 42-60V;
Maximum Current: 41.7A;
Maximum Output Power 2kW
DC Distribution:
Priority Load circuit breakers: 63A /1P x 2;
Non-Priority Load circuit breakers: 10A /1P x 2,6A /1P x 2;
Battery: 1x 125A/1P battery circuit breakers;
Battery temperature sensor 8m x 1;
BLVD: 200A battery LVD fitted
LLVD: 100A load LVD fitted
Rectifier RM2048A 4;
Controller SM12 x 1 ;
Mechanical
Dimensions, W, H, D: