QATAR ELECTROMECNICAL GROUP AL MANA

Storm drainage calculation


DESIGN & BUILD OFVILLA NO.02 AT AL
MESSILA




Storm water calculation
Rainfall I ntensity
Rainfall intensity shall be calculated using the rainfall intensity curves presented by
AS Bazaraa &
S Ahmed in the paper Rainfall Characterization in an Arid Area, Dept of Civil
Engineering, Qatar
Univ. Doha, Qatar, Vol. 4 1991. The intensity duration frequency curves (IDF) are
presented in the figure below.
As per Qatar sewage and drainage manual volume 3 surface water drainage
page10






0
20
40
60
80
100
120
140
0 20 40 60 80 100 120 140
I
n
t
e
n
s
i
t
y

(
m
m
/
h
r
)

Duration (minutes)
Tr=2years
Tr=5years
Tr=10years
Tr=25years
Tr=50years
Tr=100years
As per Qatar sewage and drainage manual volume 3 surface water
drainage page 9



As per Qatar sewage and drainage manual volume 3 surface water drainage
page 2

For high cost housing it will be 10 year and 1in
Peak Rain fall Intensity = 25.4 mm / hr for 10years and 1hour

Total discharge Q = CIA
Where:
C Runoff Coefficient as per As per Qatar sewage and drainage manual volume 3
surface water drainage page 14






I: Rain fall Intensity = 25.4
A: Total horizontal

Space Area(m2)
Seating area 54
Main building 1495
Substation 123
Cabana 54
Driver's Room 28
Guard Room 28
Total 1782

Total horizontal area = 1782m2
Total discharge Q = CIA
Where:
C Runoff Coefficient = 0.85
I Rain fall Intensity = 25.4
A Total horizontal
Q = 0.90x 1782 x 0.0254
Q = 40.73 m3/hr
By consider 50% safety factor
Storm tank capacity = 40.73x1.5 = 61.1 m3