This document provides calculations for storm drainage for a villa project in Qatar. It summarizes the methodology for determining rainfall intensity using curves from a 1991 paper on rainfall characterization in Qatar. For high cost housing, the design rainfall intensity is specified as 25.4 mm/hr for a 10-year, 1-hour storm. The total stormwater discharge is then calculated using the rational method equation of Q=CIA, where C is the runoff coefficient of 0.85, I is the design rainfall intensity of 25.4 mm/hr, and A is the total horizontal area of 1,782 square meters. This results in a required stormwater tank capacity of 61.1 cubic meters, rounded up to 62 cubic meters.
Descrizione originale:
design the irrigation tank capacity versus the required capacity
This document provides calculations for storm drainage for a villa project in Qatar. It summarizes the methodology for determining rainfall intensity using curves from a 1991 paper on rainfall characterization in Qatar. For high cost housing, the design rainfall intensity is specified as 25.4 mm/hr for a 10-year, 1-hour storm. The total stormwater discharge is then calculated using the rational method equation of Q=CIA, where C is the runoff coefficient of 0.85, I is the design rainfall intensity of 25.4 mm/hr, and A is the total horizontal area of 1,782 square meters. This results in a required stormwater tank capacity of 61.1 cubic meters, rounded up to 62 cubic meters.
This document provides calculations for storm drainage for a villa project in Qatar. It summarizes the methodology for determining rainfall intensity using curves from a 1991 paper on rainfall characterization in Qatar. For high cost housing, the design rainfall intensity is specified as 25.4 mm/hr for a 10-year, 1-hour storm. The total stormwater discharge is then calculated using the rational method equation of Q=CIA, where C is the runoff coefficient of 0.85, I is the design rainfall intensity of 25.4 mm/hr, and A is the total horizontal area of 1,782 square meters. This results in a required stormwater tank capacity of 61.1 cubic meters, rounded up to 62 cubic meters.
Storm water calculation Rainfall I ntensity Rainfall intensity shall be calculated using the rainfall intensity curves presented by AS Bazaraa & S Ahmed in the paper Rainfall Characterization in an Arid Area, Dept of Civil Engineering, Qatar Univ. Doha, Qatar, Vol. 4 1991. The intensity duration frequency curves (IDF) are presented in the figure below. As per Qatar sewage and drainage manual volume 3 surface water drainage page10
0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140 I n t e n s i t y
( m m / h r )
Duration (minutes) Tr=2years Tr=5years Tr=10years Tr=25years Tr=50years Tr=100years As per Qatar sewage and drainage manual volume 3 surface water drainage page 9
As per Qatar sewage and drainage manual volume 3 surface water drainage page 2
For high cost housing it will be 10 year and 1in Peak Rain fall Intensity = 25.4 mm / hr for 10years and 1hour
Total discharge Q = CIA Where: C Runoff Coefficient as per As per Qatar sewage and drainage manual volume 3 surface water drainage page 14
I: Rain fall Intensity = 25.4 A: Total horizontal
Space Area(m2) Seating area 54 Main building 1495 Substation 123 Cabana 54 Driver's Room 28 Guard Room 28 Total 1782
Total horizontal area = 1782m2 Total discharge Q = CIA Where: C Runoff Coefficient = 0.85 I Rain fall Intensity = 25.4 A Total horizontal Q = 0.90x 1782 x 0.0254 Q = 40.73 m3/hr By consider 50% safety factor Storm tank capacity = 40.73x1.5 = 61.1 m3 Taken storm tank capacity =62 m3