244606215.xls.

ms_office
Calculations for Recommended Flue Gas temperature to avoid S-dew point corrosion.
INPUTS
SO2 in flue gas ppm v/v 220 ppm v/v as given by EMS Lab/Online analyser
FD Fan outlet air temperture 150 deg.c. Site Reading
Flue gas pressure-Air preheater outlet 5100 mm WC Site Reading
H2O in flue gas 11.92 % vol Lab analysis
CALCULATION(Please do not change the formulae)
SO2 in flue gas vol % 0.022
H2O in flue gas vol % 5
Flue gas pressure 5100 mm WC
200.79 inch WG
1.4933 ata

P
H20
84.742 mm Hg
Ln(P
H2O
) 4.4396
SO2 to SO3 2% wt. basis
P
SO3
0.004 mm Hg
Ln(P
SO3
) -5.523
1000/T
dp
2.467309
Tdp 405.2999 deg K
132.2999 Deg C
tw recomm. 132.2999
hi/(hi+ho) = 0.4

tI = 150
tw= 132.2999
tg = 120.4999
RESULTS
S-Dew Point Temperature 132.3 Deg.c.
Recommended Flue gas Temp 120.5 Deg.c.
Issued by Technical Services
TCL Mithapur
tw=tg-(tg-ti)xhi/(hi+ho)
tw=average tube wall temperature
tg,ti= flue gas and air inlet temperatures
hi,ho= tube side and gas side heat transfer
coefficients
In an air preheater ,hi and ho=10 & 15 Btu/ft2hF
Dew Point of Acid Vapors
Sulfurous acid
1000/T
dp
=2.276-0.0294 ln(P
H2O
)-.0858 ln(PSO3)+0.0062 ln(P
H2O
)ln(PSO3)
The dew points are in deg K and partial pressures in mm Hg.