Technical Particular of Aluminum Conductor XLPE Insulated and PVC Sheathed (Compact Circular and Non-Compact Circular) Cable

As per IEC: 60502-1

SL NOMINAL CROSS No & Maximum Nominal Nominal Approximate Approximate Current Rating
# SECTIONAL AREA Approximate Conductor D.C Thickness of Thickness Outer Outer 30˚C 30˚C
OF CONDUCTOR Diameter of Resistance at Insulation of Sheath Diameter Diameter ambient ambient
Wire 20˚C (C.C) (N.C) temp. under temp. in air
ground
mm2 mm ohm/km mm mm mm mm amp amp
01 1x300 rm 61/2.52 0.100 1.80 1.90 28.10 30.00 390 460
02 1x400 rm 61/2.89 0.0778 2.00 2.20 31.80 34.40 450 555
03 1x500 rm 61/3.23 0.0605 2.20 2.20 35.00 37.90 458 770