Single Pole Trip Disabled or Enabled Enabled V< Thres. 10 - 70V step 5V 55 Trip Time Delay 0 - 1.0s step 0.002s 0.2
Loss of Load
Mode Status Disabled or Enabled Disabled Chan. Fail Disabled or Enabled Disabled I< 0.05 - 1.0 In step 0.05 In 0.5In Window 0.01 - 1.0s step 0.01s 0.04
POWER SWING BLOCKING Delta R 0 - 400/In W step 0.01/In W 0.81 Delta X 0 - 400/In W step 0.01/In W 0.81 IN > Status Disabled or Enabled Enabled IN > (% Imax) 10% - 100% step 1% 40 I2> Status Disabled or Enabled Enabled I2> (% Imax) 10% - 100% step 1% 30 Imax Line > Status Disabled or Enabled Enabled Imax Line > 1.0 In - 20 In step 0.01 In 2.0 Unblock. Delay 0 - 30s step 0.1s 0.0
Blocked Zones Bit 0 : Z1&Z1X Block 00001111
Bit 1 : Z2 Block
Bit 2 : Z3 Block
Bit 3 : Zp Block
DIRECTIONAL AND NON-DIRECTIONAL OVERCURRENT PROTECTION
I>1 Function Disabled IEC S Inverse
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
I>1 Direction Non-Directional Directional Fwd
Directional Fwd
Directional Rev
I>1 VTS Block Block or Non-Directional Non-Directional I>1 Current Set 0.08 In - 4.0 In step 0.01 In 2.4 I>1 Time Delay 0 - 100s step 0.01s
IN>2 VTS Block Block or Non-Directional Non-Directional IN>2 Current Set 0.08 In - 32 In step 0.01In 3.0 IN>2 Time Delay 0 - 200s step 0.01s 0.3 IN>2 Time Delay VTS 0 - 200s step 0.01s 0.3
IN> Directional
IN> Char. Angle -950 - +950 step 10 - 600 Polarisation Zero Sequence or Negative Sequence Zero Sequence
CHANNEL AIDED DIRECTIONAL EARTH FAULT PROTECTION
Aided DEF Status Disabled or Enabled Disabled Polarisation Zero Sequence or Negative Sequence Zero Sequence V> Voltage Set 0.05 - 20V step 0.05V 2V IN Forward> 0.05 In - 4.0 In step 0.01In 0.1 Time Delay 0 - 10s step 0.1s 0.2 Scheme Logic Shared, Blocking or Permissive Permissive Tripping Three Phase or Single Phase 3-Phase
VOLTAGE PROTECTION V< & V> Mode Bit 0 : V<1 Trip 00000100
Bit 1 : V<2 Trip
Bit 2 : V>1 Trip
Bit 3 : V>2 Trip
Undervoltage
V< Measur't Mode Phase-Phase or Phase-Neutral Phase-Phase V<1 Function Disabled, DT or IDMT Disabled V<1 Voltage Set 10 - 120V step 1.0V
V<1 Time Delay 0 - 100s step 0.01s
V<1 TMS 0.5 - 100 step 0.5
V<2 Status Enabled or Disabled Disabled V<2 Voltage Set 10 - 120V step 1.0V
V<2 Time Delay 0 - 100s step 0.01s
V<2 Poledead Inh Enabled or Disabled
Overvoltage
V> Measur't Mode Phase-Phase or Phase-Neutral Phase-Phase V>1 Function Disabled, DT or IDMT DT V>1 Voltage Set 60 - 185V step 1.0V 128V V>1 Time Delay 0 - 100s step 0.01s 1.0s V>1 TMS 0.5 - 100 step 0.5
V>2 Status Enabled or Disabled Disabled V>2 Voltage Set 60 - 185V step 1.0V
V>2 Time Delay 0 - 100s step 0.01s
CIRCUIT BREAKER FAILURE Breaker Fail
CB Fail 1 Status Enabled, Disabled Enabled CB Fail 1 Time 0 - 10s step 0.01s 0.15s CB Fail 2 Status Enabled, Disabled Enabled CB Fail 2 Time 0 - 10s step 0.01s 0.3s
CBF Non I Reset I< Only Prot Reset & I<
CB Open & I<
Prot Reset & I<
CBF Ext Reset I< Only I< Only
CB Open & I<
Prot Reset & I<
Undercurrent
I< Current Set 0.05 In - 3.2 In step 0.01 In 0.2 In
secondary Circuit Breaker Status Monitoring None/52A/52B/52A and 52B 52A and 52B
Circuit Breaker
Control CB control by Disabled/Local/Remote/Local+Remote/Opto/ Opto+Local
Opto+Local/Opto+Remote/Opto+Local+Remot e
Manual close pulse time 0.1s - 10s 0.2s Trip pulse time 0.1s - 5s 0.2s Man close delay 0.01s - 600s 2s Healthy window 0.01s - 9999s 5.0s C/S window 0.01s - 9999s 5.0s A/R Single pole Disabled/Enabled Disabled A/R Three pole Disabled/Enabled Disabled
Circuit Breaker Condition Monitoring
Lockout reset by None/CB close/User interface CB close Manual close reset delay 0.01s - 600s 5s
INPUTS
Circuit Breaker Position VT'S Line MCB Position Breaker Fail Init
Signal Received
Chanel Out of Service
OUTPUTS
Tripping coil A
Tripping coil B
Tripping coil C
Trip and Lockout - Tripping 1 Trip and Lockout - Tripping 2 Auto Reclose Init
Phase A Auto Reclose Init Phase B Auto Reclose Init Phase C Block Auto Reclose
Signal send
GHI CH:
_Tn hiu trip 1, 3 pha vng 1, vng 2 t b Backup protection c a vo b Main protection