0 valutazioniIl 0% ha trovato utile questo documento (0 voti)
42 visualizzazioni2 pagine
This document provides specifications for a 370RT water-cooled screw chiller unit with a cooling capacity of 1355.8 kW and heating capacity of 1787.5 kW. Key details include its model number, dimensions, operating temperatures and fluid flows for the evaporator and condenser, electrical specifications, sound levels, and accessories. The unit was manufactured in Shanghai, China for a project in Singapore and has a cooling efficiency of 2.84 kW/kW and heating efficiency of 3.75 kW/kW.
This document provides specifications for a 370RT water-cooled screw chiller unit with a cooling capacity of 1355.8 kW and heating capacity of 1787.5 kW. Key details include its model number, dimensions, operating temperatures and fluid flows for the evaporator and condenser, electrical specifications, sound levels, and accessories. The unit was manufactured in Shanghai, China for a project in Singapore and has a cooling efficiency of 2.84 kW/kW and heating efficiency of 3.75 kW/kW.
This document provides specifications for a 370RT water-cooled screw chiller unit with a cooling capacity of 1355.8 kW and heating capacity of 1787.5 kW. Key details include its model number, dimensions, operating temperatures and fluid flows for the evaporator and condenser, electrical specifications, sound levels, and accessories. The unit was manufactured in Shanghai, China for a project in Singapore and has a cooling efficiency of 2.84 kW/kW and heating efficiency of 3.75 kW/kW.
Prepared By: 06:52PM AquaForce TM Water Cooled Screw Chiller Unit Information Tag Name: 370RT Model Number: 30XW1602P Quantity: 1 Manufacturing Source: Shanghai, China Shipping Weight: 11288 kg Operating Weight: 11388 kg Unit Length: 4827 mm Unit Width: 2160 mm Unit Height: 1586 mm
Evaporator Information Fluid Type: Fresh Water Fouling Factor: 0.0180 (sqm-K)/kW Leaving Temperature: 7.5 C Entering Temperature: 13.0 C Fluid Flow: 58.79 L/s Pressure Drop: 30.8 kPa
Condenser Information Fluid Type: Fresh Water Fouling Factor: 0.0440 (sqm-K)/kW Leaving Temperature: 60.0 C Entering Temperature: 49.0 C Fluid Flow: 39.37 L/s Pressure Drop: 15.0 kPa
Accessories and Installed Options Opt. 150 High Condensing Temperature Unit (up to 63C leaving condenser water temperature)
Electrical Information Unit Voltage: 400-3-50 V-Ph-Hz Standby Power: 0.1 kW Minimum Voltage: 360 Volts Maximum Voltage: 440 Volts Power Factor: 0.86 Electrical Electrical Amps (Un) Circuit 1 Circuit 2 Max Unit Current Draw (RLA) 430.0 430.0 Max Start Up Current (ICF) 772.0 772.0 Nominal Unit Current Draw (A) 243.0 243.0
Packaged Chiller Builder China Export 3.39a Page 1 of 2 Summary Performance Report For 370RT Project: Surbana - SGH Selections 07/14/2014 Prepared By: 06:52PM Note: Performance is at nominal voltage. Chiller may unload if job site voltage is lower than 400 volts. Sound pressure level measured in accordance with AHRIStandard 575. Sound pressure level is the free field sound data (the unit isplaced in free field over a reflecting plane). Unit is outside of the scope of AHRI Water-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P). Packaged Chiller Builder China Export 3.39a Page 2 of 2