LTD, Secunderabad GENERATOR PROTECTION RELAY Make : SCHNEIDER Model : SEPAM G87 DATE: 08-02-2014 Sheet No.1 of 5 CUSTOMER : M/S MICROSOFT PROJECT : INFOSYS CAMPUS, HYDERABAD Substation : DG CONTROL ROOM
Tested By
Witness By
1. Equipment Details : Make : SCHNEIDER ELECTRIC Model : SEPAM 1000-G87 Sl. No. : 0516035 Phase CT Ratio : 150/5 Earth CT Ratio : 150/5 PT Ratio : 11KV / 110 V Ib : 105 Amp
2. Location & Feeder Name : FEEDER NO.52-1, From DG-1 3. General Inspection : OK 4. Secondary injection test: PONOVO NUMERICAL SECONDARY INJECTION TEST KIT. Make: PONOVO RELAY TEST KIT.
67 - 1 Directional Over Current 105 IEC-EIT/C 0.40 0.40 Operation Mode Phase Applied Current(A) Measured Current (A) Applied Voltage(V) Measured Voltage (V) Ia 0.5 15 110 10.980KV Ib 0.5 15 110 10.980KV Ic 0.5 15 110 10.980KV IN 0.5 15 EPROSYS ENGINEERING CONSULTANTS INDIA PVT LTD, Secunderabad GENERATOR PROTECTION RELAY Make : SCHNEIDER Model : SEPAM G87 DATE: 08-02-2014 Sheet No.2 of 5 CUSTOMER : M/S MICROSOFT PROJECT : INFOSYS CAMPUS, HYDERABAD Substation : DG CONTROL ROOM
Tested By
Witness By
In/Is 67 - 2 300 DMT 0.12 0.12 Operation Mode
Name IEC Code Description Setting in KW Characteri stic Curve Setting Time Status Delay in Sec TIME in Sec P 32 P - 1 Reverse Power 160 DMT 6.0 Operation Mode U < 1
27
Under Voltage 9240 Volts 84% DMT 13.0 Operation Mode
Unp / Vs0
59 N
NDV 25.4 Volts 40% DMT 4.0 Operation Mode f >
81 H Over Frequency 53 DMT 10.0 Operation Mode
f <
81 L Under Frequency 47 DMT 10.0 Operation Mode Name IEC Code Description Setting Current Characteri stic Curve Setting Time Status In Amps In % Delay in Sec TIME in Sec
EPROSYS ENGINEERING CONSULTANTS INDIA PVT LTD, Secunderabad GENERATOR PROTECTION RELAY Make : SCHNEIDER Model : SEPAM G87 DATE: 08-02-2014 Sheet No.3 of 5 CUSTOMER : M/S MICROSOFT PROJECT : INFOSYS CAMPUS, HYDERABAD Substation : DG CONTROL ROOM
Tested By
Witness By
7. Pickup Test:
Setting Changed to 1A for 50/51-1, 3&4 for Testing
NON DIRECTIONAL OVER CURRENT & EARTH FAULT Device Code Plug Setting in Amps TL / DT Setting (Sec) Pick up Current in Amps Hiset Current in Amps Hiset Time in Sec Pick up Current in Amps Pick up Time in Sec 50/51R 1A 0.49 1.120 315 Amp (10.5Amp) 0.20 10.520 0.2176 50/51Y 1.12-120 10.52-120 50/51B 1.12120 10.52120 50/51R - - - 115 Amp (3.8 Amp) 0.10 3.90 0.1111 50/51Y - 3.9-120 50/51B - 3.9120 50/51R - - - 315 Amp (10.5Amp) 0.75 10.60 0.7672 50/51Y - 10.6-120 50/51B - 10.6120 50N/51N (Unit-1) 20 Amp (0.5 Amp) 1.33 0.5280 - - - - 50N/51N (Unit-2) 20 Amp (0.5 Amp) 1.78 0.530 - - - - 50N/51N (Unit-3) 20 Amp (0.5 Amp) 2.07 0.5260 - - - - 50N/51N (Unit-4) - - - 100 Amp (2.5 Amp) 0.300 2.530 0.3282 UNBALANCE CURRENT TEST Device Code Plug Setting in Amps TL / DT Setting (Sec) Pick up Current in Amps Pick up Time in Sec Pick up Current in Amps Hiset Time in Sec Pick up Time in Sec I (46) 0.7875 Amp 0.800 0.7875 0.8152 - - - DIRECTIONAL OVER CURRENT & EARTH FAULT Setting Value Changed to 20 Amp for 67-1 for testing Device Code Plug Setting in Amps TL / DT Setting (Sec) Pick up Current in Amps Hiset Current in Amps Hiset Time in Sec Pick up Current in Amps Pick up Time in Sec 671 & 2 R 30 Amp (1.0 Amp) 0.4 1.10 10 A 0.120 10.030 0.1231 671 & 2 Y 1.1-120 10 A 0.120 10.03-120 0.1231 671 & 2 B 1.1120 10 A 0.120 10.03120 0.1231 67-1 &2 (R,Y,B) Trip Zone Angel : -43 deg to +138 Deg on Setting MTA : +45 Deg, with +/- 90 deg trip zone EPROSYS ENGINEERING CONSULTANTS INDIA PVT LTD, Secunderabad GENERATOR PROTECTION RELAY Make : SCHNEIDER Model : SEPAM G87 DATE: 08-02-2014 Sheet No.4 of 5 CUSTOMER : M/S MICROSOFT PROJECT : INFOSYS CAMPUS, HYDERABAD Substation : DG CONTROL ROOM
Tested By
Witness By
VOLTAGE RESTRAIN OVER CURRENT Setting Changed to 75 Amp for Testing Device Code Plug Setting in Amps TL / DT Setting (Sec) Pick up Current in Amps Hiset Current in Amps Pick up Current in Amps Hiset Time in Sec Pick up Time in Sec 51V - R 2.5 0.590 2.550 - - - - 51V - Y 2.5 0.590 2.55-120 - - - - 51V - B 2.5 0.590 2.55120 - - - - ACTIVE POWER Device Code Plug Setting in KW TL / DT Setting (Sec) Voltage in Volts Pick up Power in Watt Pick up Time in Sec Direction 32P-1 160 6.0 110 V 165 6.0498 Reverse Direction OVER & UNDER VOLTAGE Device Code Plug Setting in Volts TL / DT Setting (Sec) Pick up Voltage in Volts Plug Setting in Volts Time in Sec Pick up Voltage in Volts Pick up Time in Sec 27-1 - - - 92.38 13.0 92.14 13.0181 59 - - - 121 12.0 121.24 12.0166 59N - - - 15.4 4.0 26.9 4.0483 OVER & UNDER FREQUENCY Device Code Plug Setting in HZ TL / DT Setting (Sec) Pick up in Hz Plug Setting in HZ Time in Sec Pick up in Hz Pick up Time in Sec 81H - - - 53 10.0 53.1 10.2024 81L - - - 47.0 10.0 46.94 9.9898 EPROSYS ENGINEERING CONSULTANTS INDIA PVT LTD, Secunderabad GENERATOR PROTECTION RELAY Make : SCHNEIDER Model : SEPAM G87 DATE: 08-02-2014 Sheet No.5 of 5 CUSTOMER : M/S MICROSOFT PROJECT : INFOSYS CAMPUS, HYDERABAD Substation : DG CONTROL ROOM
Tested By
Witness By
8. Characteristic Check:
Device Code Plug Setting in Amps TL / DT Setting (Sec) Graph Time for multiple of Plug Setting Actual Operating Time In Seconds 2 5 10 2 5 10 Non-Directional Over Current 50/51 Unit-1 1 0.49 16.0 2.0 0.5 16.2010 2.0365 0.4946 Earth Fault 50/51N Unit-1 0.53 0.89 3.0 1.3 0.90 3.0600 1.3022 0.8992 50/51N Unit-3 0.5 1.78 6.0 2.6 1.8 6.0804 2.5825 1.8206 Directional Over Current 67-1 1 0.4 13.1 1.7 0.4 13.2497 1.6556 0.4006 Voltage Restrain Over Current 51V-1 With Voltage 2.5 0.89 3.0 0.89 - 3.0105 0.8875 - 51V-1 Without Voltage 2.5 0.89 1.30 0.69 - 1.2898 0.6882 -