SECTION 16370

IDENTIFICATION

PART 1.00 – GENERAL:

1.01 WORK INCLUDED:

A. With the exception of apartment loadcenters, all electrical equipment, including bolted pressure
switch, switchboard, main distribution panelboards, switches, panelboards, cabinets, main
breakers, etc. shall have micarta laminate plates with 1/2-inch high letters indicating designation
and voltage, screwed to door trim.

B. Starters, pushbuttons, disconnect switches and branch circuits of Main Distribution Panelboard
shall have micarta laminate plates with 3/8-inch high letters indicating name of item controlled.

C. All panels, in addition to the above, shall have a micarta laminate plate with 1/2-inch high letters
indicating where the source of power is being fed from.

D. All panels, in addition to the above, shall have a micarta laminate plate with 1/2-inch high letters
indicating where the source of power is being fed from.

PART 2.00 - PRODUCTS (NOT APPLICABLE):

PART 3.00 - EXECUTION (NOT APPLICABLE):

END OF SECTION