SECTION 16265

HANGERS AND SUPPORTS

PART 1.00 – GENERAL:

1.01 WORK INCLUDED:

A. Provide all required hangers, supports, channels, sleeves, clamps, etc., as required.

PART 2.00 – PRODUCTS:

2.01 MECHANICAL SUSPENSION CHANNEL:

A. Mechanical suspension channel shall be furnished and installed to support electrical equipment
in main electrical rooms and sub-meter rooms.

B. Channel shall be Unistrut Type P3000 or approved equal. All fasteners and fittings shall be
supplied to provide a complete installation as required.

C. All channel and fittings shall be furnished with the manufacturer’s standard rust proofed finish.

D. Channel shall be manufactured by one of the following: Unistrut Products Company, B-Line,
Power-Strut or Steel City Electric Company.

PART 3.00 – EXECUTION:

3.01 CONDUIT AND FUTURE SUPPORTS:

A. All horizontal runs of conduits shall be properly grouped, aligned, using substantial hangers,
straps, etc. Hangers and supports shall be installed at intervals not exceeding
recommendations per NEC.

B. Supporting rods shall be threaded at ends with allowance for adjustments. Wire and strap
hangers will not be permitted. All conduit and fittings shall be supported by hangers, straps, etc.,
using bolts, and/or lead expansion sleeves.

C. Lighting fixtures shall be supported and hung from building structure, independent of the ceiling
construction using minimum #12 hanging wire.

END OF SECTION