CALCULATION

TEMPORARY FACILITY TANAJ IB



DOC.#FP-006




DOC#FP006
PAGE01OF05

HYDRAULICANALYSISBASIS:
Followingarethebasisofcalculations:

a. PressuredropcalculationshavebeenperformedusingHazenWilliamssformulae.

b. Cfactorhasbeentaken:

RTRPIPEC=135.

c. Equivalent length of pipe fittings has been taken and calculated from Crane
handbook.

d. 10%safetyfactorhasbeenconsideredonthefrictionlossesofpipe&fittings.

e. PipinglengthsindrawingPL008ANDPL009areconsideredtotalof205METERand
theelevationdifferenceisconsidered1.524METER.

Hydraulicanalysishasbeenperformedwithaflowof1,500GPM.

f. AllowableflowvelocityforRTRPIPEis05m/s.

5.0 HYDRAULICANALYSISSUMMARY:

Sr.No. PumpTag Flow
description
GPM
TOTAL
HEAD
(ft)
PIPESIZE
(in)
NPS
FLOW
VELOCITY
(ft/s)

FIREWATERPUMP

1500GPM

177

9.08
(2.76m/s)

Proj. Title: Calc. by:


J RM
BI/EWO- No.: Date:
20/10/13
Proj. No.: Chkd. by:
J M
Subject: Date:
21/10/13
Pipe Int.
Dia
Nominal
Pipe Size
(GPM) (in) fps m/s m/s fps (in) (in)
Required Flow
1500 7.67 10.42 3.18 194.19 638.80 0.98 1
82.89 272.67 1.50 1 1/2
42.29 139.12 2.10 2
17.99 59.17 3.22 3
10.88 35.79 4.14 4
4.76 15.66 6.26 6
Calc.Fluid Velocity
Flow
Rate (Q)
Min. Int. Dia
Reqd. (d)
RTR STD PIPE DATA
Velocity
DOC. # FP-006
TEMPORARY CAMP FACILITY TANAJIB
SATECH J.O. #215
JB-215
FIRE WATER LINE SIZE CALCULATION
FIRE WATER LINE SIZE.xls
SHT 02 OF 05
2.76 9.08 8.22 8
1.74 5.73 10.35 10
1.22 4.02 12.35 12
1.01 3.34 13.56 14
0.78 2.55 15.50 16 S
e
l
e
c
t
e
d

P
i
p
e

S
i
z
e
FIRE WATER LINE SIZE.xls
SHT 02 OF 05
Proj. Title: Calc. by:
J RM
BI/EWO- No.: Date:
20/10/13
Proj. No.: Chkd. by:
J M
Subject: Date:
21/10/13
LINE SIZE CALCULATIONS
Refering to AWWA Manual M45 :
Diameter for Pressure Pipe Service
d =0.321 Q
0.434
(SG)
2
Where :
d = Internal Pipe Dia (in.)
Q = Flow Rate (in GPM)
SG = Fluid Specific Gravity (For Water SG =1)
Required Dia for Village Air Strip:
TEMPORARY CAMP FACILITY TANAJIB
SATECH J.O. #215
JB-215
FIRE WATER LINE SIZE CALCULATION
DOC. # FP-006
FIRE WATER LINE SIZE.xls
SHT 03 OF 05
d =0.321 1500
0.434
(1)
2
= 7.67 in
Fluid Velocity For this Calculated Dia:
Using the relation
v =0.409 Q
(d)
2
=0.409 1500
(7.67 )2
= 10.42 ft/s
= 3.18 m/s
=1500.00 GPM Flow Rate Q
ft/sec.
FIRE WATER LINE SIZE.xls
SHT 03 OF 05
Calc. by: J RM
Date: 21/10/2013
Chkd. by: J KM
Date: 21/10/2013
PIPE
NOMINAL
PIPE SIZE
(I.D.)
WATER
DEMAND
VELOCITY
PIPE &
FITTINGS
HEAD LOSS
(in) (in) (gpm) (ft/sec) (m) (ft) Type
Eq. Length
(FT)
Qty.
Total Eq.
Length (ft)
Total Eq.
Length (ft)
ft H2O/100 ft (ft) (psi)
8 5-10 8.22 1500 9.08 5.00 16.40 ELB 90 20.00 1 20.00 36.40 3.16 1.15 0.50 61.24
8.22 1500 9.08 0.00 0.00 CV 33.3 1 33.30 33.30 3.16 1.05 0.46
8.22 1500 9.08 0.00 0.00 GV 5.32 1 5.32 5.32 3.16 0.17 0.07
8.22 1500 9.08 0.00 0.00 TEE BR 13.3 1 13.30 13.30 3.16 0.42 0.18
8 10-15 8.22 1500 9.08 196.00 642.88 ELB 90 20.00 8 160.00 802.88 3.16 25.40 11.00 73.73
8.22 1500 9.08 0.0 0.00 GV 5.32 4 21.28 21.28 3.16 0.67 0.29
8.22 1500 9.08 0.0 0.00 TEE BR 13.30 7 93.10 93.10 3.16 2.95 1.28
6 15-20 6.22 1500 15.86 4.0 13.12 ELB 90 15.20 1 15.20 28.32 12.30 3.48 1.51 61.57
TOTAL 205.00 672.40 1033.90 35.30 15.28
STATIC HEAD (Elevation Diffrence) = 2.16 PSI = 5.00 FT
PRESSURE DROP DUE TO FRICTION LOSS = 15.28 PSI = 35.30 FT
PRESSURE REQUIRED AT THE FARTHEST HYDRANT OUTLET = 50.00 PSI = 115.50 FT
TOTAL HEAD = 67.44 PSI = 155.80 FT
SAFETY FACTOR 10 % = 6.74 PSI = 15.58 FT
TOTAL HEAD WITH SAFETY FACTOR = 76.72 PSI = 177.22 FT
NOTES:
FLOW(GPM) X HEAD(FT) X SG " AS PER REQUIREMENT OF LPD, SMG 007-005-2012
MAXIMUM STATIC PRESSURE OF THE PUMP AT ALL
POINTS OF FIRE WATER SYSTEM SHALL BE 80 PSI
MINIMUM RESUDUAL PRESSUERE AT ALL POINTS
ASSUMING PUMP EFFCY OF 75% = 89.50 HP OF THE FIRE WATERS SYSTEM IS 20 PSI"
PAGE 04 OF 05
FIRE WATER PUMPING SYSTEM HYDRAULIC CALCULATION
PIPE LENGTH
PRESSURE @
NODAL
POINTS
(psi)
Proj. Title:
HYDRAULIC AND PRESSURE DROP CALCULATIONS FOR FIRE WATER PUMP
I NPUT DATA OUTPUT DATA
DOC. # FP - 006
TEMPORARY CAMP FACILITY TANAJIB
SATECH J.O. #215
JB-215
PUMP CAPACITY
TOTAL HEAD LOSS FITTINGS
N
O
D
E
S
BI/EWO- No.:
Proj. No.:
Subject:
TWO (2) FIRE WATER PUMP 1500 GPM EACH (1 ELECTRIC PUMP-DUTY+ 1 DIESEL PUMP STAND BY)
3960 X EFFICIENCY
REQUIRED PUMP HORSE POWER =
STATIC HEAD (Elevation Diffrence) = 2.16 PSI 5.00 FT
PRESSURE DROP DUE TO FRICTION LOSS = 1.21 PSI 2.79 FT
PRESSURE REQUIRED AT THE FARTHEST HYDRANT = 50.00 PSI 115.50 FT
SAFETY FACTOR 10 % = 5.34 PSI 12.33 FT
TOTAL = 3.37 PSI 7.79 FT
REQUIRED PRESURE AT HYDRANT OUTLET = 50.00 PSI 115.50 FT
THEREFORE PUMP DISCHARGE HEAD = 58.71 PSI 135.62 FT
= 61.24 PSI 141.47 FT
STATIC HEAD (Elevation Diffrence) = 2.16 PSI 5.00 FT
PRESSURE DROP DUE TO FRICTION LOSS = 12.56 PSI 29.02 FT
PRESSURE REQUIRED AT THE FARTHEST HYDRANT = 50.00 PSI 115.50 FT
SAFETY FACTOR 10 % = 6.47 PSI 14.95 FT
TOTAL = 14.73 PSI 34.02 FT
REQUIRED PRESURE AT HYDRANT OUTLET = 50.00 PSI 115.50 FT
THEREFORE PUMP DISCHARGE HEAD = 71.20 PSI 164.47 FT
= 73.73 PSI 170.32 FT
STATIC HEAD (Elevation Diffrence) = 2.16 PSI 5.00 FT
PRESSURE DROP DUE TO FRICTION LOSS = 1.51 PSI 3.48 FT
PRESSURE REQUIRED AT THE FARTHEST HYDRANT OULET = 50.00 PSI 115.50 FT
SAFETY FACTOR 10 % = 5.37 PSI 12.40 FT
TOTAL = 3.67 PSI 8.48 FT
REQUIRED PRESURE AT HYDRANT OUTLET = 50.00 PSI 115.50 FT
THEREFORE PUMP DISCHARGE HEAD = 59.04 PSI 136.38 FT
= 61.57 PSI 142.23 FT
PAGE 05 OF 05
FARTHEST POINT OF THE FIRE WATER SYSTEM = NODE (15-20)
NODE (5-10)
NODE (10-15)
PRESSURE AT NODAL POINTS