CLIENT: CONTRACTOR: CONSULTANT: PREPARED BY: Project name: Project description:

MOI Saudi Binladen Groups Dar Al Riyadh Consultant

Saudi Building & Constraction Management


TSF12-09-02-HAIL-1150-P3 MCC PANEL FOR AHU-03

Input Entry : Enclosures Size : Power supply :

BOTTOM ENTRY 1000 X 800 X 300 MM 380 VAC, 3Ph&N&G 220VAC OUTDOOR WITH COVER SHEET IP 41

Drawing number: DESIGN BY : Type :


Created on Edit date

TS12-09-02-HP3 MOAAZ MCC

Control voltage : Installation Location: IP protection :

4/16/2013 4/16/2013

11

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

PROJECT TITLE PAGE

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

1 11

SYMBOLS

DESCRIPTION

SYMBOLS

DESCRIPTION
OFF DELAY TIMER CONTACT NO.NC

SYMBOLS

DESCRIPTION

SYMBOLS

DESCRIPTION
PROXIMITY SWITCH CHANG OVER CONTACT

3P CIRCUIT BREAKER

BUZZER

DRAW-OUT

ON DELAY TIMER CONTACT NO.NC

CURRENT TRANSFORMER

BATTARY

ISOLATOR

PRESSURE SWITCH CONTACT NO.NC

LED
3

TRANSFORMER

MOTOR CIRCUIT BREAKER I> I> I>

FLOW SWITCH CONTACT NO.NC

CAPACITOR

POWER SUPPLY

FUSE SWITCH

COIL FOR CONTACTOR COIL FOR RELAY

HEATING RESISTOR

M 1~
PE

1PHASE MOTOR

3P CONTACTOR

RELAY.ON DELAY TIMER

EARTH

1P CIRCUIT BREAKER

OVERLOAD

RELAY.OFF DELAY TIMER

TERMINAL

2P CIRCUIT BREAKER

A-0-H

3P SELECTOR SWITCH

ELECTRONIC PROGRAMMABLE TIMER

3 PHASE BUSBAR/CABLE

3P HEATER

PUSHBOTTON NO.NC

INDICATION LAMP

WAY OF INCOMING CABLE WAY OF OUTGOING CABLE

1P HEATER

CONTROL CONTACT NO.NC

VOLTMETER INCOMING/OUTGOING CABLE 3 WIRE SENSOR

CHANEGOVER CONTACT

AMMETER

INTERLOCK

OUT OF PANEL DEVICE

OVERLOAD CONTACT NO.NC

HOURS RUN METER

M 3~

3 PHASE MOTOR

EMERGENCY STOP

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

PROJECT LEGEND

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

2 11

POWER SUPPLY -SOURCE QTY : -SOURCE VOLTAGE : NO PARALLEL OPERATION PARALLEL OPERATION OF INCOMERS ONLY DURING ON-LOAD CHANGEOVER Isc = KA/1Sec -NEUTRAL SYSTEM DIRECT TO EARTH (TT) ISOLATED (IT) SEPERATE (TN-S) --------------------TO EARTH ISOLATED -MOUNTING

APPARATUS

DEGREE OF PROTECTION

NAME PLATES

IN.C

OUT.G

-PROTECTION -FORM TYPE

IP30 FORM1 FORM3

IP31

IP41 FORM2 FORM4

IP55

IP66

LABELS -WITH -ALUMINUM -MECHANICAL -GRAYVOPLY -TRAFFOLYTE -SELF STICK -SCREW

FIXED DRAW-OUT PLUG-IN -OPERATION BEHIND DOOR THROUGH PLATE INTERLOCK (AC) PADLOCKING SHUTTER THROUGH DOOR TERMINAL COVER

-WITH PANEL VENTILATION

POWER SUPPLY

-RIVETED

-COLOR : BLACK LETTER ON WHITE BACKGROUND -LANGUAGE : ENGLISH -PRIZMA PLUS -PRIZMA GE -PRIZMA G -HIMIL -END SHEETS -CABLW DUCT -WEATHERPROOF -UNIVERSAL -LAND TRANSPORT -OTHERS WITH WITHOUT PACKING

-DIRECT CURRENT

BUS BAR

CONNECTIONS IN.C OUT.G

-ELDON PRESENTATION -FIXED FRONT -FUNCTIONAL DOOR -PLAIN DOOR

-MATERIAL -SYSTEM

ALU

COPPER

DIRECT TO DEV.TERML'S THRU TERMINAL BLOCKS THRU BUSBAR LINK V V V -ACCESS FRONT REAR LEFT SIDE , RIGHT SIDE -ENTRY TOP BOTTOM -ACCESSORIES SCREWS GLAND PLATE CABLE GLAND -SHROUDING

-APPROXIMATE WEIGHT : ............................

CONSTANTSECTION DECREASING WITH BUSBAR SHOUD BARE -NEUTRAL

H H H

-TRANSPARENT DOOR -WITH KEY -OTHER SEGREGATION -VERTICAL FRONT : REAR -VERTICAL FRONT : REAR FOR C.B -BETWEEN CUBICAL COLOUR OF PAINTING -SPECIAL : MOUNTING -FREE STANDING RAL 7032 -DEVIATION -LOOSE MATERIAL WITH WITHOUT -APPARTUS DEFINED YES -PARTIC.DIMENSION YES -EXTENSION OF : ........................ -SIMILAR TO : ............................ -SPECIFICATION WITH WITHOUT NO NO PARTICULAR NOTES

NOT DISTRIBUTED SAME SECTION AS PHASES HALF SECTION HORIZANTAL VERTICAL

SUPPLY OF AUXILIARIES

......................................... WITH WITH WITHOUT WITHOUT

-VOLTAGE ALL CIRCUIT CONTROL SIGNALLING -ORIGIN

....VAC ..... VDC 110VAC 110VAC 24VAC 24VAC 24VDC 24VDC

CABLE ENDS

220VAC 220VAC

-SURFACE

......................................... ......................................... DRAWING -FOR APPROVAL

EXTERNAL FROM BATTERY AUXILIARY TRANSFORMER

AUXILIARY WIRING

INDICATING INSTRUMENT-METER

-SEC.VOLTAGE -CURRENT

SQ.MM 2.5 SQ.MM RED/BLK

INSTRUMENTS -SIZE 96x96 -SIZE 72x72

-AS BUILT

CLIMATIC CONDITION

-COLOR ------MARKING OF CIRCUIT -POWER OUTDOOR 50 deg.C -AUXILIARY SQ.MM

QTY :

NO

-TYPE OF CLIMATE -TYPE OF ATMOSPHERE -POLLUTION RISKS -MOUNTING -AMBIENT TEMPERATURE -RELATIVE HUMIDITY

NORMAL ORDINARY ------------INDOOR 40 deg.C 50% AT 40deg.C -------

-SIZE 48x48 REMARKS METER RELAY

R.Y.B.N

LOCAL END COLOURED STRIPS BOTH ENDS COMPOSED ---------

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

PROJECT INFORMATION

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

3 11

F1
2 1

CL2 / 5.0

CN2 / 5.0

Q1
MCCB ,3P 40A 2 4 6

Q2
MCB ,3P 20A 2 4 6

VFD-1
/5.3 15KW PE

VFD-2
/6.3 7.5KW PE

INVERTER
U V W

INVERTER
U V W

X1 R S T
1 2 3 4

X1
5 6 7

PE U1 V1 W1 PE U1 V1 W1 PE

M1

M
3

M2

M
3

POWER SUPPLY 3Ph/380V/60HZ

AHU SUPPLY FAN ( 15Kw ) 3Ph/380V/60Hz

AHU RETURN FAN (7.5Kw ) 3Ph/380V/60Hz

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

POWER DIAGRAM

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

4 11

BROWN
4.9 /

BROWN

BROWN

-CL2

X2
SF-AUTO RUN FROM BMS 1

X2
2

2
3 3 4

VFD-1
/4.3

11

11

R2
/5.3 7 3

R3
/5.4 7 3

SS1
4

27

FLA

FLC

FLB

RY

RC

RES

P24

CC

PLC

PP

VIA

CC

VIB

FM

33
9

34

35

31 29 28 30
6

R3
/5.4 1

R1
/5.1 10 A1 A1

8 12 /5.4 11

8 12

A1

3 32

9
x1 x1 x1

R2
/5.3

R3

13

R1
A2

R2
A2

R3
A2

10
H1
G x2

12
X2
11

H2
R x2

H3
Y x2

X2

X2
10

X2
12 13

X2

BLACK
4.9 /

BLACK
RUN RELAY TRIP RELAY

-CN2 ON/OFF CMD RELAY RUN STOP TRIP RUN TRIP AUX FREE CONTACT

10 /5.4

7 3 8 4

11 /5.7 12 /5.8

9 9 7 3 8 4

1 /5.1 1 /6.1 11 /5.8 12 /5.9

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

CONTROL DIAGRAM

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

5 11

BROWN
/

BROWN

-CL2

X2
RF-AUTO RUN FROM BMS 14

X2
15

15
3 3 4

VFD-2
/4.4

11

11

R5
/6.3 7 3

R6
/6.4 7 3

SS2
4

36

FLA

FLC

FLB

RY

RC

RES

P24

CC

PLC

PP

VIA

CC

VIB

FM

42
9

43

44

40 38 37 39
6

R3
/5.4 1

R4
/6.1 10 4 8 12 /6.4 24 4 8 12 A1 A1

A1

16 41

17

18

19

20

21

22
x1 x1 x1

R5
/6.3

R6

R4
A2

R5
A2

R6
A2

26

23
X2 X2
23 24

25
X2 X2
25 26

H4
G x2

H5
R x2

H6
Y x2

X2

BLACK
/

BLACK
RUN RELAY TRIP RELAY

16

17

18

19

20

21

22

-CN2 ON/OFF CMD RELAY RUN STOP TRIP RUN TRIP AUX FREE CONTACT

10 /6.4

7 3 8 4

11 /6.7 12 /6.8

7 3 8 4

11 /6.8 12 /6.9

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

CONTROL DIAGRAM

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

6 11

BILL OF QUANTITY
Part Number Description Quantity Reference
M1;M2 E9.108030E FUSE 2A ONKA-1041 ONKA-1031 1142 15636 XB7EV63P XB7EV64P XB7EV65P EZC100F3040 17081 RXZE2M114 RXM4AB1P7 XB7ED33P ATV21HD15N4 ATV21HU75N4 ENCLOSURE (1000x800x300)mm FUSE 2A MINI TERMINAL BLOCKS MRK 10mm2 MINI TERMINAL BLOCKS MRK 6mm2 MINI TERMINAL BLOCKS MRK 4mm2 ( FUSE HOLDER )STI 1P 10X38 500V Direct Supply Green Pilot, IP54 Direct Supply Red Pilot, IP54 Direct Supply Yellow, IP54 EZ100F MCCB 10KA/400V 3P 40A Domae 3P 20A C curve RELAY BASE RELAY 220V 4C/O 3 Pos Selector Switch 2NO, IP54 ATV21,380-480V,15KW,HVACapplication ATV21,380-480V,7.5KW,HVACapplication 1 1 1 6 26 1 2 2 2 1 1 6 6 2 1 1 U1 F1 X1 X1 X2 F1 H1;H4 H2;H5 H3;H6 Q1 Q2 R1...R6 R1...R6 SS1;SS2 VFD-1 VFD-2 ACE CHINT ONKA ONKA ONKA Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider

Supplier

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

BILL OF QUANTITY

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

7 11

TERMINAL DIAGRAM
Strip
External targets

X1
Target designation 1 2 3 4 5 6 7 jumper wiring Target designation -R1:A2 -VFD-1 -VFD-1 -VFD-1 -VFD-2 -VFD-2 -VFD-2 Placement /5.1 /4.3 /4.3 /4.3 /4.4 /4.4 /4.4

Internal targets

function text POWER SUPPLY 3Ph/380V/60HZ ( N ) U1 : FAN 1 V1 : FAN 1 W1 : FAN 1 U1 : FAN 1 V1 : FAN 1 W1 : FAN 1

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

Terminal diagram =PROJECT+ELECTRICAL DIAGRAMS-X1

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

8 11

TERMINAL DIAGRAM
Strip
External targets

X2
Target designation 1 BROWN jumper wiring Target designation -F1:1 -SS1:3 Placement /4.5 /5.1

Internal targets

function text SF-AUTO RUN FROM BMS

SF-AUTO RUN FROM BMS PTC probe PTC probe Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O SF-RUN STATUS SF-RUN STATUS SF-TRIP STATUS SF-TRIP STATUS RF-AUTO RUN FROM BMS RF-AUTO RUN FROM BMS PTC probe PTC probe Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O RF-RUN STATUS RF-RUN STATUS

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 16 17 18 19 20 21 22 23 24 -VFD-2-CC -VFD-2-PLC -VFD-2-PP -VFD-2-VIA -VFD-2-CC -VFD-2-VIB -VFD-2-FM -R5:12 -R5:8 /6.5 /6.5 /6.6 /6.6 /6.6 /6.6 /6.7 /6.8 /6.8 3 4 5 6 7 8 9 10 11 12 13 BROWN -VFD-1-CC -VFD-1-PLC -VFD-1-PP -VFD-1-VIA -VFD-1-CC -VFD-1-VIB -VFD-1-FM -R2:12 -R2:8 -R3:12 -R3:8 -SS2:3 /5.5 /5.5 /5.6 /5.6 /5.6 /5.6 /5.7 /5.8 /5.8 /5.9 /5.9 /6.1

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

Terminal diagram =PROJECT+ELECTRICAL DIAGRAMS-X2

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

9 11

TERMINAL DIAGRAM
Strip
External targets

X2
Target designation 25 26 jumper wiring 25 26 Target designation -R6:12 -R6:8 Placement /6.9 /6.9

Internal targets

function text RF-TRIP STATUS RF-TRIP STATUS

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

Terminal diagram =PROJECT+ELECTRICAL DIAGRAMS-X2

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

10 11

800mm

300mm

800mm

800mm

RUN

STOP

TRIP

RUN

STOP

TRIP

AHU-03
A-O-M A-O-M

1000mm

Merlin Gerin

INTERNAL LAYOUT

SIDE VIEW

INTERNAL DOOR ARRANGEMENT

DOOR LAYOUT

PANEL DESCRIPTION
MCC PANEL FOR AHU-03

Date : Designed : Checked by : Approved by :

4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ

Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177

PROJECT PANEL LAYOUT

FILE NO :

H:\Users\Public\EPLAN\Electric P8\Projects\TRUST SYSTEMS.CO\TSF12-09-02-HAIL-1150-P3.elk

Drawing Number :

TS12-09-02-HP3

Page Total Pages

11 11