BOTTOM ENTRY 700 X 500 X 250 MM 380 VAC, 3Ph&N&G 220VAC OUTDOOR WITH COVER SHEET IP 55
4/16/2013 4/16/2013
10
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
FILE NO :
Drawing Number :
TS12-09-02-HP2
1 10
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
OFF DELAY TIMER CONTACT NO.NC
SYMBOLS
DESCRIPTION
SYMBOLS
DESCRIPTION
PROXIMITY SWITCH CHANG OVER CONTACT
3P CIRCUIT BREAKER
BUZZER
DRAW-OUT
CURRENT TRANSFORMER
BATTARY
ISOLATOR
LED
3
TRANSFORMER
CAPACITOR
POWER SUPPLY
FUSE SWITCH
HEATING RESISTOR
M 1~
PE
1PHASE MOTOR
3P CONTACTOR
EARTH
1P CIRCUIT BREAKER
OVERLOAD
TERMINAL
2P CIRCUIT BREAKER
A-0-H
3P SELECTOR SWITCH
3 PHASE BUSBAR/CABLE
3P HEATER
PUSHBOTTON NO.NC
INDICATION LAMP
1P HEATER
CHANEGOVER CONTACT
AMMETER
INTERLOCK
M 3~
3 PHASE MOTOR
EMERGENCY STOP
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
PROJECT LEGEND
FILE NO :
Drawing Number :
TS12-09-02-HP2
2 10
POWER SUPPLY -SOURCE QTY : -SOURCE VOLTAGE : NO PARALLEL OPERATION PARALLEL OPERATION OF INCOMERS ONLY DURING ON-LOAD CHANGEOVER Isc = KA/1Sec -NEUTRAL SYSTEM DIRECT TO EARTH (TT) ISOLATED (IT) SEPERATE (TN-S) --------------------TO EARTH ISOLATED -MOUNTING
APPARATUS
DEGREE OF PROTECTION
NAME PLATES
IN.C
OUT.G
IP31
IP55
IP66
FIXED DRAW-OUT PLUG-IN -OPERATION BEHIND DOOR THROUGH PLATE INTERLOCK (AC) PADLOCKING SHUTTER THROUGH DOOR TERMINAL COVER
POWER SUPPLY
-RIVETED
-COLOR : BLACK LETTER ON WHITE BACKGROUND -LANGUAGE : ENGLISH -PRIZMA PLUS -PRIZMA GE -PRIZMA G -HIMIL -END SHEETS -CABLW DUCT -WEATHERPROOF -UNIVERSAL -LAND TRANSPORT -OTHERS WITH WITHOUT PACKING
-DIRECT CURRENT
BUS BAR
-MATERIAL -SYSTEM
ALU
COPPER
DIRECT TO DEV.TERML'S THRU TERMINAL BLOCKS THRU BUSBAR LINK V V V -ACCESS FRONT REAR LEFT SIDE , RIGHT SIDE -ENTRY TOP BOTTOM -ACCESSORIES SCREWS GLAND PLATE CABLE GLAND -SHROUDING
H H H
-TRANSPARENT DOOR -WITH KEY -OTHER SEGREGATION -VERTICAL FRONT : REAR -VERTICAL FRONT : REAR FOR C.B -BETWEEN CUBICAL COLOUR OF PAINTING -SPECIAL : MOUNTING -FREE STANDING RAL 7032 -DEVIATION -LOOSE MATERIAL WITH WITHOUT -APPARTUS DEFINED YES -PARTIC.DIMENSION YES -EXTENSION OF : ........................ -SIMILAR TO : ............................ -SPECIFICATION WITH WITHOUT NO NO PARTICULAR NOTES
SUPPLY OF AUXILIARIES
CABLE ENDS
220VAC 220VAC
-SURFACE
AUXILIARY WIRING
INDICATING INSTRUMENT-METER
-SEC.VOLTAGE -CURRENT
-AS BUILT
CLIMATIC CONDITION
QTY :
NO
-TYPE OF CLIMATE -TYPE OF ATMOSPHERE -POLLUTION RISKS -MOUNTING -AMBIENT TEMPERATURE -RELATIVE HUMIDITY
R.Y.B.N
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
PROJECT INFORMATION
FILE NO :
Drawing Number :
TS12-09-02-HP2
3 10
F1
2 1
CL2 / 5.0
CN2 / 5.0
Q1
/5.2 MS ,3P 6 ~ 10A
Q2 I>
2
I>
4
I>
6
/5.4 MS , 3P 4 ~ 6.3A
I>
2
I>
4
I>
6
6 2
K1
5 3P,9A 4 2
K2
5 3P,9A 4
X1
1 2 3 4
X1
5 6 7
X1
8 9 10
PE U1 V1 W1 PE U1 V1 W1 PE
M1
M
3
M2
M
3
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
POWER DIAGRAM
FILE NO :
Drawing Number :
TS12-09-02-HP2
4 10
BROWN
4.9 /
-CL2
X2
SF-AUTO RUN FROM BMS 1
X2
RF-AUTO RUN FROM BMS 3
X2
2
X2
4
10 3 4
2
3
4
3 3 4 2
10
11
11
11
11
SS1
4
R1
/5.1 6
SS2
4
R3
/5.3 6 2
R1
/5.1 7 3
R2
/5.2 7 3
R3
/5.3 7 3
R4
/5.4 7 3
13
13
17
13
Q1
/4.3 14
Q2
16
9
/4.4
14
20
21
22
23
24
25
26
R2
/5.2 1
15 14
R4
/5.4 1
19 18
A1
A1
A1
A1
A1
A1
x1
x1
x1
x1
x1
x1
R1
A2
R2
A2
K1
A2
R3
A2
R4
A2
K2
A2
H1
G x2
H2
R x2
H3
Y x2
H4
G x2
H5
R x2
H6
Y x2
BLACK
4.9 /
-CN2 RUN RELAY TRIP RELAY MAIN RUN RELAY TRIP RELAY MAIN RUN STOP TRIP RUN STOP TRIP
4 6 2 7 3 8 4 10 /5.2 11 /5.5 12 /5.7 9 7 3 8 4 1 /5.1 11 /5.6 12 /5.7 6 2 7 3 8 4 10 /5.5 11 /5.7 12 /5.8 9 7 3 8 4 1 /5.3 11 /5.7 12 /5.9
8 12
8 12
8 12 /5.4 10
8 12
R1
/5.1
6 /5.2
R2
R3
/5.3
R4
12
5
X2 X2
5 6
7
X2 X2
7 8
9
X2 X2
9 10
11
X2 X2
11 12
RUN
TRIP
RUN
TRIP
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
CONTROL DIAGRAM
FILE NO :
Drawing Number :
TS12-09-02-HP2
5 10
BILL OF QUANTITY
Part Number Description Quantity Reference
M1;M2 E9.8060250E FUSE 2A ONKA-1041 ONKA-1031 1142 15636 XB7EV63P XB7EV64P XB7EV65P 17080 17079 RXZE2M114 RXM4AB1P7 XB7ED33P ATV21HU40N4 ATV21HD22N4 ENCLOSURE (800x600x250)mm FUSE 2A MINI TERMINAL BLOCKS MRK 10mm2 MINI TERMINAL BLOCKS MRK 6mm2 MINI TERMINAL BLOCKS MRK 4mm2 ( FUSE HOLDER )STI 1P 10X38 500V Direct Supply Green Pilot, IP54 Direct Supply Red Pilot, IP54 Direct Supply Yellow, IP54 Domae 3P 16A C curve Domae 3P 10A C curve RELAY BASE RELAY 220V 4C/O 3 Pos Selector Switch 2NO, IP54 ATV21,380-480V,4KW,HVACapplication ATV21,380-480V,22KW,HVACapplication 1 1 1 6 26 1 2 2 2 1 1 6 6 2 1 1 U1 F1 X1 X1 X2 F1 H1;H4 H2;H5 H3;H6 Q1 Q2 R1...R6 R1...R6 SS1;SS2 VFD-1 VFD-2 ACE CHINT ONKA ONKA ONKA Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider Schneider
Supplier
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
BILL OF QUANTITY
FILE NO :
Drawing Number :
TS12-09-02-HP2
7 10
TERMINAL DIAGRAM
Strip
External targets
X1
Target designation 1 2 3 4 5 6 7 jumper wiring Target designation -R1:A2 -VFD-1 -VFD-1 -VFD-1 -VFD-2 -VFD-2 -VFD-2 Placement /5.1 /4.3 /4.3 /4.3 /4.4 /4.4 /4.4
Internal targets
function text POWER SUPPLY 3Ph/380V/60HZ ( N ) U1 : FAN 1 V1 : FAN 1 W1 : FAN 1 U1 : FAN 1 V1 : FAN 1 W1 : FAN 1
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
FILE NO :
Drawing Number :
TS12-09-02-HP2
8 10
TERMINAL DIAGRAM
Strip
External targets
X2
Target designation 1 BROWN jumper wiring Target designation -F1:1 -SS1:3 Placement /4.5 /5.1
Internal targets
SF-AUTO RUN FROM BMS PTC probe PTC probe Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O SF-RUN STATUS SF-RUN STATUS SF-TRIP STATUS SF-TRIP STATUS RF-AUTO RUN FROM BMS RF-AUTO RUN FROM BMS PTC probe PTC probe Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O Voltage/current for analog I/O RF-RUN STATUS RF-RUN STATUS
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 16 17 18 19 20 21 22 23 24 -VFD-2-CC -VFD-2-PLC -VFD-2-PP -VFD-2-VIA -VFD-2-CC -VFD-2-VIB -VFD-2-FM -R5:12 -R5:8 /6.5 /6.5 /6.6 /6.6 /6.6 /6.6 /6.7 /6.8 /6.8 3 4 5 6 7 8 9 10 11 12 13 BROWN -VFD-1-CC -VFD-1-PLC -VFD-1-PP -VFD-1-VIA -VFD-1-CC -VFD-1-VIB -VFD-1-FM -R2:12 -R2:8 -R3:12 -R3:8 -SS2:3 /5.5 /5.5 /5.6 /5.6 /5.6 /5.6 /5.7 /5.8 /5.8 /5.9 /5.9 /6.1
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
FILE NO :
Drawing Number :
TS12-09-02-HP2
9 10
TERMINAL DIAGRAM
Strip
External targets
X2
Target designation 25 26 jumper wiring 25 26 Target designation -R6:12 -R6:8 Placement /6.9 /6.9
Internal targets
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
FILE NO :
Drawing Number :
TS12-09-02-HP2
10 10
400mm
250mm
400mm
400mm
AHU-01
RUN STOP TRIP
A-O-M
RUN
STOP
TRIP
600mm
A-O-M
INTERNAL ARRANGEMENT
SIDE VIEW
FRONT ARRANGEMENT
PANEL DESCRIPTION
MCC PANEL FOR AHU-02
4/16/2013
MOAAZ ENG : MAHER ENG : MOTAZ
Saudi Building & Constraction Management CITY : JEDDAH Fax: 02 668 6645 Phone: 02 664 4177
FILE NO :
Drawing Number :
TS12-09-02-HP2
11 10