Sei sulla pagina 1di 60

C-DOT DSS MAX

RSU INSTALLATION MANUAL

System Practices

Section No. 401-305-0513 Issue 03, October 1999

C-DOT DSS MAX-XL

RSU INSTALLATION MANUAL

1999, C-DOT Printed in India

C-DOT DSS MAX-XL RSU INSTALLATION MANUAL

ISSUE 03 OCTOBER 1999 ASVINA 2056 SERIES 300 : INSTALLATION CSP SECTION NO. 401-305-0513 THIS CDOT SYSTEM PRACTICE REFERS TO THE CDOT DIGITAL SWITCHING SYSTEM MAIN AUTOMATIC EXCHANGE (ABBREVIATED AS C-DOT DSS MAX-XL IN THE REST OF THIS PUBLICATION).

THE INFORMATION IN THIS SYSTEM PRACTICE IS FOR INFORMATION PURPOSES AND IS SUBJECT TO CHANGE WITHOUT NOTICE.

A COMMENT FORM HAS BEEN INCLUDED AT THE END OF THIS PUBLICATION FOR READER'S COMMENTS. IF THE FORM HAS BEEN USED, COMMENTS MAY BE ADDRESSED TO THE DIRECTOR (SYSTEMS ), CENTRE FOR DEVELOPMENT OF TELEMATICS, 39, MAIN PUSA ROAD, NEW DELHI - 110 005

1999 BY CDOT, NEW DELHI.

Preface
The objective of this manual is to provide necessary information & guidance for the installation of an RSU. Since most of the chapters for RSU installation, viz. Grouting, Iron Work installation, Cabinet installation, D.C. Distribution Panel, MDF installation, Power Distribution Panel installation, Cable Preparation and laying, Fuse Details and Placement, Jumper Settings, Expansion with Line Module etc. will be similar to those which are covered in SBM RAX installation manual. For installation of ISDN Terminal Unit (ISTU) in RSU, refer MAX-XL Installation Manual. Only those points where there are changes/modifications and extra work to be done, are covered in this document along with the figures. Apart from the installation procedure to be done on the RSU side, there are few changes and extra cable preparation and laying to be done in the parent exchange (C-DOT DSS MAX) for RSU installation which are also covered in this document. We hope that this manual will serve as a useful reference for the installant alongwith respective SBM RAX Installation document for RSU Installation. Following configurations are possible as per field requirement. Configuration MAX-L MAX-XL Central Module CM-L (16 BM Connectivity) CM-XL (32 BM Connectivity) Local BMs BM-L or BM-XL BM-L or BM-XL Remote BMs (RSU) BM-L or BM-XL BM-L or BM-XL

BM-L is defined as BM working with CPU & TME cards in BPU BM-XL is defined as BM with BPC &BME cards in BPU MAX-L/XL supports a mix of BM-Ls and BM-XLs in the same exchange even for RBM.

Table of Contents
Preface Chapter 1. ...................................................................................................................................................1 Introduction ..............................................................................................................................5 1.1. General...............................................................................................................................5 Chapter 2. Modifications in Floor Marking...............................................................................................7 2.1. Marking of Suite Lines......................................................................................................7 Chapter 3. RSU Cable Preparation And Laying .......................................................................................9 3.1. Introduction .......................................................................................................................9 3.2. Cable Preparation on RSU Side .....................................................................................10 3.3. Cable Preparation on MBM Side for RSU .....................................................................33 3.4. Cable Placements ............................................................................................................35 Chapter 4. Jumper Settings and Modem Set-Up ....................................................................................41 4.1. APC-BPU43X/H-M01 ......................................................................................................41 4.2. Extending IOP Terminal to RSU Site Using Modems..................................................44 Chapter 5. MDF - Installation..................................................................................................................49 5.1. General.............................................................................................................................49 5.2. Digital Trunk Cable Termination on RBM to MDF (For RSU PCMS)........................49 5.3. Digital Trunk Cable Termination on CM to DDF (For RSU PCMs)............................50 5.4. Inter Connections ............................................................................................................50

H:\HOME\MAX-XL\WORD\XLRSUINM.DOC

October 7, 1999

Chapter 1.

Introduction
1.1. GENERAL RSU, by definition, is the Remote Switching Unit of a geographically distributed exchange being controlled by the parent exchange, which has the capability for local switching. For all purposes, RSU is similar to a colocated BM in an MBM exchange. The only difference in RSU and colocated BM is that RSU placed remotely will be connected to parent exchange by digital trunks interface from CM to RSU via respective MDFs and digital media while colocated BM is connected to CM by BMCM data cables and clock cables. Hence RSU is also termed as Remote Base Module (RBM) and names `RSU' and `RBM' are interchangeably used in this document wherever necessary. With the present hardware only an even number BM of MBM (i.e. BM-2, BM-4, etc.) can be made as an RSU. Hence maximum number of RSUs that can be supported in C-DOT DSS MAX and corresponding RSU cards required are given in Table 1. Table-1 Maximum No. of RSUs Supported 8 16 RSU Cards CM ESL ESM RBM ETS ETS No. of Cards Per RSU 2ESL&2ETS 2ESM&2ETS

Configuration MAX-L MAX-XL

Since there will be no IOPs and ADP on RSU side, a CRP terminal can be extended through modem for maintenance purposes. It should be clear that a Base Module in C-DOT DSS MAX can be converted into a Remote Base Module (RSU) with minimum changes. Following are the changes required on RSU side and main exchange side for connecting a RBM to main exchange.

RSU INSTALLATION MANUAL

Chapter 1.

1. 2.

Only an even numbered BM can be made as an RSU RSU Side : (BM-L/BM-XL) To distinguish between a Remote Base Module and colocated Base Module, the Most Significant Bit (MSB) position on each column of jumper settings on copy 0 and copy 1 side of Base Processor Unit (BPU) mother board is made one, i.e. it is left open. Time Switch Switch (TSS) card will be replaced by Enhanced Remote Time Switch (ETS) card. For connection with the parent exchange, two sets of digital trunk cables for Bus-0 and Bus-1 from the Time Switch Unit (TSU) of RBM will be laid towards the DDF/MDF. On the CM side, Space Switch Multiplexer card in Bus Termination unit will be replaced by Enhanced Remote Space Switch Multiplexer in the slot where a RSU link is to be connected as given below. CM-L : SSM replaced by ESL CM-XL : PSM replaced by ESM Two sets of digital trunk cables coming from the RSU (i.e. from DDF of CM side) as Bus-0 and Bus-1 will be terminated on to corresponding bus of ESL/ESM card in BTU. The other position in the same ESL/ESM card will be used for connecting a colocated BM.

3.

CM Side

Note: Each SSM/PSM supports two local BMs Each ESL/ESM supports one local BM and one RBM.

C-DOT DSS MAX-XL

Chapter 2.

Modifications in Floor Marking


2.1. MARKING OF SUITE LINES The suite lines are drawn as per the procedure outlined in section 1.5 of respective SBM RAX installation manual. Since there will be no IOPs and ADP in RSU, the suite lines will be as shown in Fig. 2.1. To draw the suite lines the distance of 600mm, 2995mm for Base Frame Assembly-1, 3000mm and 3985mm for Base Frame Assembly-2 parallel to the second datum line is measured and four vertical lines are drawn. Also two horizontal lines at a distance of 400mm and 1000mm parallel to the first datum line are drawn. The intersection of respective horizontal and vertical lines give the physical placement of the suite. Also markings for placement of CRP terminal are made as per figure 2.1 in the switch room.

RSU INSTALLATION MANUAL

Chapter 2.

C-DOT DSS MAX-XL

Chapter 3.

RSU Cable Preparation And Laying


3.1. INTRODUCTION Following are the main cables required for RSU installation apart from the other cables mentioned in C-DOT SBM RAX/DSS MAX-L/XL installation manual. a. b. c. d. RSU Clock cable. Digital Trunk Cables on RSU side. Digital Trunk Cables on Central Module (CM) side. BP Terminal cable on RSU side.

Co-axial cable is used to prepare the clock cable for RSU. Clock cable will be connected between ETS (Enhanced Remote Time Switch) card slot position and TSC (Time Switch Controller) card slot position on each copy of TSU. Since the connections on the contact blocks at both ends are not one-to-one, care needs to be taken by the installer while fixing it on the mother-board. Digital Trunk Cable on RSU side is connected from Time Switch Unit to DDF. On CM side, it is connected between Bus Termination Unit (BTU) and DDF. The shield at DDF end of these cables are connected to chassis ground. Other end of the cable shields (RBM and CM side) should be left open to isolate the ground. Assembly of the digital trunk cable on RSU side also provides connection to an ACIO cable. For ACIO part, jumper wire with PVC sleeve may be used. BP terminal cable is optional only. This may be required for debugging switch units in case RBM is totally cut off from the parent exchange and it is having critical switch unit faults. One CRP terminal is extended through modem on RSU side for maintenance functions. This does not require any additional cables as Modem is normally supplied alongwith a cable which is having D-type 25 pin connectors on both ends.

RSU INSTALLATION MANUAL

Chapter 3.

3.2. 3.2.1.

CABLE PREPARATION ON RSU SIDE Detail of RSU Clock Cable (BM-L/BM-XL)


C-DOT ASSY NO. DRAWING NO. CABLE PART NO. CABLE MARKER NO. CABLE DESCRIPTION CABLE UNIT COLOR CODE CABLE LENGTH SOURCE TERMINATION PART NO. : : : : : : : : : ACB-RSUXRCXN-100 Fig. 3.1 (a) & 3.1 (b) MCA-CXO188AU-401 RCXN * RG-188 A/u 50 ohm co-axial cable WHITE 20 cm Solderable Contact block. MCC-BPSCB207-401 Polarised Hood 14 contact Module. MCC-BPPOH207-401 Plain Hood. MCC-BPPLH207-401 DESTINATION TERMINATION PART NO. : Same as Source Termination part No. Copy 0 SOURCE PLACEMENT : Frame Slot TSU 13 A 1 RCA0 TSU 12 B 1 RCB0 Copy 1 TSU 14 A 1 RCA1 TSU 15 B 1 RCB1

Connector TAB NO. RETAINED CABLE MARKER NO. DESTINATION PLACEMENT : : : TAB NO Frame Slot Connector TAB NO Fig. 3.1(a) & 3.1(b) -

TAB NO RETAINED CABLE MARKER NO. ASSEMBLY PROCEDURE

: : :

Note: * X N = A indicates connector A side of slot 13/14 = B indicates connector B side of slot 12/15 = 0 indicates copy 0 cable = 1 indicates copy 1 cable

10

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

11

Chapter 3.

12

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

3.2.2.

Details of Digital Cables at RSU At RBM end, for connecting RSU to DDF/MDF, 4 Pair or 8 Pair digital Trunk cables may be used. Note : For using 4 pair cable at RSU end, refer section 3.2.2.1 & 3.2.2.2 on cable preparation and connection details. For using 8 pair cables, refer section 3.2.2.3 on cable preparation and connection details.

3.2.2.1.

Digital Trunk Cable - I (Using 4 Pair Cable) C-DOT ASSY NO. DRAWING NO. CABLE PART NO. CABLE MARKER NO. : : : : ACB-ERSURN01-000 Fig. 3.2 (a) MCA-PVCTPS04-401 R `N' `uu' R `N' `xx' where N

= A for copy 0 = B for copy 1 For uu, and xx, refer table no. 3-4. CABLE DESCRIPTION CABLE UNIT COLOR CODE CABLE LENGTH : : : Digital cable - Shielded twisted 4 pair cable Digital Trunk cable - GREY Site dependent (Maximum of 100 mtrs). Digital Part - 2x25m. (Typical) excluding unsheathed section. Wire Wrap Contact block. MCC-BCFSW307-002 Polarised Hood 14 contact Module. MCC-BPPOH207-401 DESTINATION TERMINATION PART NO. SOURCE PLACEMENT : Digital cable -stripped wire to MDF/DDF Copy 0 : Frame Slot TSU 13 A Copy 1 TSU 14 A

SOURCE TERMINATION PART NO.

Connector -

RSU INSTALLATION MANUAL

13

Chapter 3.

TAB NO. RETAINED CABLE MARKER DESTINATION PLACEMENT ASSEMBLY PROCEDURE

: : : :

For Module -1

2 RA `uu' RA `xx'

2 RB `uu' RB `xx'

*Digital Part - Stripped wire to DDF. Refer Fig. 5.1(a). Wire wrapping tool Soldering Iron (For jumper wire) Ref fig. 3.2(a) and Tables 3-1 and 3-2.

The shields of this cable are to be connected as shown in fig.3.2(c)

14

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

15

Chapter 3.

Connections for Digital Trunk Cable RBM end (4 Pair Cable)


Module No. Pin No. 1 2 1 3 4 5 6 7 1 2 2 3 4 5 6 7 Blue Orange Green Brown Blue Green -Blue Orange Green Brown Blue Green -(vv) (vv) (vv) (vv) (yy) (yy) Orange White Brown White White White `A' (uu) (uu) (uu) (uu) (xx) (xx) Orange White Brown White White White `B' (xx) (xx) [O] (xx) (xx) [Br] (xx) [Bl] (xx) [G] -(yy) (yy) [O] (yy) (yy) [Br] (yy) [Bl] (yy) [G] --White (vv) [Bl] White (vv) [O] White (vv) [G] White (vv) [Br] ---`C' White (uu) [Bl] White (uu) [O] White (uu) [G] White (uu) [Br]

Table No. 3-1 Note : For the values of uu, vv, xx, yy for different BM's please see table No. 3-4. () indicates cable number [] indicates corresponding cable colour pair Bl : Blue O : Orange G : Green Br : Brown

16

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

Signal Names for Digital Trunk Cable (RBM End)


Module No. Pin No. 1 2 1 3 4 5 6 7 1 2 2 3 4 5 6 7 A TX_P {1} TX_P {3} RX_P {1} RX_P {3} TX_P {5} RX_P {5} -TX_P {2} TX_P {4} RX_P {2} RX_P {4} TX_P {6} RX_P {6} -B TX_P {7} TX_N {7} RX_P {7} RX_N {7} TX_N {5} RX_N {5} -TX_P {8} TX_N {8} RX_P {8} RX_N {8} TX_N {6} RX_N {6} -C TX_N {1} TX_N {3} RX_N {1} RX_N {3} ---TX_N {2} TX_N {4} RX_N {2} RX_N {4} ----

Note : {} indicates digital Trunk number Table No. 3-2 Connections for ACIO Cable
Module & Source PIN No 5C 6C Signal Name RXD TXD Module 3 Destinatio n PIN No 3C 4C Signal Name TXD RXD Colour of Wire Used Red White

Table No. 3-3 Wiring diagram for Fig. 3.2(b)

RSU INSTALLATION MANUAL

17

Chapter 3.

Cable No.'s for Different RBM No.'s


RBM No. 02 04 06 08 10 12 14 16 18 20 22 24 26 28 30 32 uu 01 05 09 13 17 21 25 29 33 37 41 45 49 53 57 61 vv 02 06 10 14 18 22 26 30 34 38 42 46 50 54 58 62 xx 03 07 11 15 19 23 27 31 35 39 43 47 51 55 59 63 yy 04 08 12 16 20 24 28 32 36 40 44 48 52 56 60 64

Table No. 3-4 3.2.2.2. Digital Trunk Cable - II (4 Pair Cable) C-DOT ASSY NO. DRAWING NO. CABLE PART NO. : : : ACB-ERSURN02-000 Fig. 3.2 (b) MCA-PVCTPS04-401 MCA-PVCSC013-401 MCA-PVCJW002-401 R `N' `vv' R `N' `yy' where N = A for copy 0 = B for copy 1 For vv, and yy, refer table no. 3-4. Digital cable - Shielded twisted 4 pair cable

CABLE MARKER NO.

CABLE DESCRIPTION

18

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

Ground Cable - 32/0.2mm Black Colour PVC wire. ACIO cable -- Jumper wire with PVC sleeve CABLE UNIT COLOR CODE CABLE LENGTH : Digital Trunk cable - GREY Ground Cable - Black ACIO cable Red and white pair Site dependent (Maximum of 100 mtrs) Digital Part - 2x25m. (Typical) excluding unsheathed section. Ground Cable - 0.3m ACIO part-20 cm Wire Wrap Contact block. MCC-BCFSW307-002 Polarised Hood 14 contact Module. MCC-BPPOH207-401 DESTINATION TERMINATION PART NO : Digital cable -stripped wire to MDF * Ring Terminal 2.5sq. mm/M6. MCT-ERRIN015-401 * 32/0.2 mm. PVC wire, black (MCA-PVCSC013-401) 300mm in length ACIO cable - Wire Wrap Contact Block MCC-BPWCB207-401 Polarised hood 14 contact module MCC-BPPOH207-401 Copy 0 SOURCE PLACEMENT : Frame Slot TAB NO. RETAINED CABLE MARKER DESTINATION PLACEMENT : : : TSU 13 A 3 RA `vv' RA `yy' Copy 1 TSU 14 A 3 RB `vv' RB `yy'

SOURCE TERMINATION PART NO.

Connector For Module 2 -

*Digital Part - Stripped wire to MDF/DDF Refer Fig. 5.1(a) For ACIO -> Copy 0 TSU Copy 1 TSU Frame -

RSU INSTALLATION MANUAL

19

Chapter 3.

Slot TAB NO. RETAINED CABLE MARKER ASSEMBLY PROCEDURE : : :

12 B 4 - RRSA

15 B 4 RRSB

Connector For Module 3 -

Soldering Iron (For jumper wire) Ref . Tables 3-1 and 3-2, 3-3 and Fig. 3.2 (b) For ACIO connection details refer Table No. 3-3.

These parts are to be connected as shown in Fig.3.2(c)

Notes: 1. 2. 3. Wire wrap the pairs onto contact block pins of each module as per wiring details given. Snap the hood onto the contact block such that polarity tab(1) is towards pin 1 as per wiring done. The shields of the four digital trunk cables are joined together at MDF end. Solder 32/0.2 square mm multistrand wire on to the shield (copper braid) at the point shown and crimping terminal ring as shown. The wire length shall be as shown in the figure. Polarity tabs to be retained as given below module 1:2, module 2:3, module 3:4. Put 6.00mm black silicon rubber sleeve for L1. Put 12.0mm PVC/Black silicon rubber sleeve of 50mm length at both ends of L tied with cable ties. The four digital trunk cables on each side (copy 0 and copy 1) are tied together with cable ties.

4. 5. 6. 7. 8. Note :

All signal names are w.r.t RBM side.

20

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

21

22
\DESIGN\DSSMAX\MAX-XL\RSU-XLIM\RSXLC3

Chapter 3.

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

3.2.2.3.

Digital Trunk Cable (Using 8 Pair Cable) C-DOT ASSY NO. DRAWING NO. CABLE PART NO. : : : ACB-ERSURN03-000 Fig. 3.3 MCA-PVCTPS08-401 MCA-PVCSC013-401 MCA-PVCJW002-401 R `N' `uu' , vv R `N' `xx' , yy where N = A for copy 0 = B for copy 1 For uu, vv and xx, yy refer table no. 3-5. Digital cable - Shielded twisted 8 pair cable Digital Trunk cable - GREY Ground Cable - Black Site dependent (Maximum of 100 mtrs). Digital Part - 2x25m. (Typical) excluding unsheathed section. Ground cable - 0.3m Wire Wrap Contact block. MCC-BCFSW307-002 Polarised Hood 14 contact Module. MCC-BPPOH207-401 DESTINATION TERMINATION PART NO : Digital cable -stripped wire to MDF * Ring Terminal 2.5sq. mm/M6. MCT-ERRIN015-401 * 32/0.2 mm. PVC wire, black (MCA-PVCSC013-401) Copy 0 SOURCE PLACEMENT : Frame Slot TAB NO. RETAINED CABLE MARKER : : TSU 13 A 2 3 RA `uu' RA, 'vv' RA `xx' RA 'yy' Copy 1 TSU 14 A 2 3 RB 'uu' RB `vv' RB 'xx' RB `yy'
23

CABLE MARKER NO.

CABLE DESCRIPTION CABLE UNIT COLOR CODE CABLE LENGTH

: : :

SOURCE TERMINATION PART NO.

Connector For Module 1 For Module 2 -

RSU INSTALLATION MANUAL

Chapter 3.

DESTINATION PLACEMENT

Digital Part - Stripped wire to MDF. For ACIO Frame Slot Connector
Copy 0 TSU 12 B 4 Copy 1 TSU 15 B 4

TAB NO. RETAINED ASSEMBLY PROCEDURE

: :

For module 3

Wire wrapping tool Soldering Iron (For jumper wire) Ref. Fig. 3.3 and Tables 3-5. For ACIO connection details refer Table No.3-3.

These parts are to be connected as shown in Fig. 3.3

Notes: 1. 2. 3. Wire wrap the pairs onto contact block pins of each module as per wiring details given. Snap the hood onto the contact block such that polarity tab(1) is towards pin 1 as per wiring done. The shields of the two digital trunk cables are joined together at MDF end. Solder 32/0.2 square mm multistrand wire on to the shield (copper braid) at the point shown and crimping terminal ring as shown. The wire length shall be as shown in the figure. Polarity tabs to be retained as given below module 1:2, module 2:3, module 3:4. Put 12.0mm PVC/Black silicon rubber sleeve of 50mm length at both ends of L tied with cable ties. The two digital trunk cables on each side (copy 0 and copy 1) are tied together with cable ties.

4. 5. 6. 7. Note:

All signal names are w.r.t. RBM side.

24

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

25

Chapter 3.

A.

Connections for Digital Trunk Cable RBM end (Using 8 pair cable)
Pin No. 1 2 1 3 4 5 6 7 1 2 2 3 4 5 6 7 Slate Blue Orange Green Slate Orange -Blue Orange Green Brown Blue Green -(vv) (vv) (vv) (vv) (yy) (yy) Blue Red Green Red White Red -A (uu) (uu) (uu) (uu) (xx) (xx) B Orange (xx) White Brown White White White (xx) [O] (xx) (xx) [Br] (xx) [Bl] (xx) [G] -(yy) (yy) [B1] (yy) (yy) [G] (yy) [S] (yy) [Ol] -White (vv) [S] Red Red Red (vv) [B1] (vv) [O] (vv) [G] ---C White (uu) [Bl] White (uu) [O] White (uu) [G] White (uu) [Br]

Module No.

Table No. 3-5 () indicates cable number [] indicates corresponding cable colour pair Bl : Blue O : Orange G : Green Br : Brown S Slate

26

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

3.2.3.

Details of BP Terminal Cable for BM-XL C-DOT ASSY NO. DRAWING NO. CABLE PART NO. CABLE MARKER NO. CABLE DESCRIPTION CABLE LENGTH SOURCE TERMINATION PART NO. : : : : : : : ACB-MAXXBPTX-000 Fig. 3.4a, 3.4b & 3.4c MCA-ICSBZ007-401 BPTX* 8 pair telephone cable. (only 4 pairs are used). 25m. (max.) excluding unsheathed section. 25 pin D-type wire wrap (Female) : MCC-DCFMZ002-301 MCC-DHXXXT25-100 7X2 IDC Crimp connector MCC-BPCSZ012-401 MCC-BPCSZ011-401 MCC-BPCSZ022-401 VDU Rack Frame TAB No. ASSEMBLY PROCEDURE *X = 1 for BP-0 and 2 for BP-1. : RBM 5 J7 4 RBM 5 J24 4

DESTINATION TERMINATION PART NO. SOURCE PLACEMENT DESTINATION PLACEMENT

: :

: :

Connector -

Crimping Tool and Wire wrapping tool. Fig. 3.4(a), 3.4(b) & 3.4(c)

RSU INSTALLATION MANUAL

27

Chapter 3.

3.2.4.

Details of BP Terminal Cable for BM-L C-DOT ASSY NO. DRAWING NO. CABLE PART NO. CABLE MARKER NO. CABLE DESCRIPTION CABLE LENGTH SOURCE TERMINATION PART NO. : : : : : : : ACB-RSUVTEZX-000 Fig. 3.4d, 3.4b,3.4c MCA-ICSBZ007-401 TEZX* 8 pair telephone cable. (only 4 pairs are used). 25m. (max.) excluding unsheathed section. 25 pin D-type wire wrap (Female) : MCC-DCFMZ002-301 MCC-DHXXXT25-100 7X2 IDC Crimp connector MCC-BPCSZ012-401 MCC-BPCSZ011-401 MCC-BPCSZ022-401 VDU Rack Frame TAB No. ASSEMBLY PROCEDURE *X = 1 for BP-0 and 2 for BP-1 : RBM 5 2B 1

DESTINATION TERMINATION PART NO. SOURCE PLACEMENT DESTINATION PLACEMENT

: :

: :

Connector -

Crimping Tool and Wire wrapping tool. Fig. 3.4(d), 3.4(b) & 3.4(c)

28

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

29

Chapter 3.

30

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

31

32
\DESIGN\DSSMAX\MAX-XL\RSU-XLIM\RSXLIBTC

Chapter 3.

NOTE: USE SILICON RUBBER SLEEV ON LENGTHS L1, L2

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

3.3.

CABLE PREPARATION ON MBM SIDE FOR RSU For each RSU, eight lengths of 4 Pair shielded cables (4 for bus-0 and 4 for bus-1) are required on CM side and cables in each bus are tied together as shown in fig. 3.5 (b).

3.3.1.

Detail of Digital Trunk Cable (For RSU Link) C-DOT ASSY NO. DRAWING NO. CABLE PART NO. CABLE MARKER NO. : : : : ACB-MAXRMDXX-000 Fig. 3.5 (a), MCA-PVCTPS04-401 MCA-PVCSC013-401 M`N' `uu', M`N' `vv', M`N' `xx', M`N' `yy' Where N = A for Bus 0 B for Bus 1 Refer Table No. 3-4 for uu, vv, xx, yy. Shielded digital cable 4 pairs. 32/0.2mm black colour PVC wire. GREY. Site dependent (Max. of 100 m) * Digital cable - 4x25 m. (Typical) excluding unsheathed section # Ground cable - 0.3 m Wire Wrap Contact block. MCC-BCFSW307-002 Polarised Hood 14 contact Module. MCC-BPPOH207-401 Digital cables - stripped wire to MDF # Ring Terminal 2.5sq. mm/M6 MCT-ERRIN015-401 # 32/0.2 mm. PVC wire, black (MCA-PVCSC013-401) 0.3m in length Frame - BTU 0/1 in CM-XL. (Refer Table 5-1) Slot - ESM slot Connector - B TAB NO. - 1 For Module 1 2 For Module 2

CABLE DESCRIPTION CABLE UNIT COLOR CODE CABLE LENGTH

: : :

SOURCE TERMINATION PART NO.

DESTINATION TERMINATION PART NO.

SOURCE PLACEMENT

TAB NO. RETAINED

RSU INSTALLATION MANUAL

33

Chapter 3.

DESTINATION PLACEMENT ASSEMBLY PROCEDURE

: :

MDF Wire Wrapping Refer fig. 3.5 (a), 3.5 (b) and table 3-6,3-7.

Note * The exact length of the digital cable from exchange to MDF is site dependent. Care should be taken so that total length of the cable from exchange to first repeater position should not exceed more than hundred metres. These parts are required to be connected as shown in Fig. 3.5 (b). Connections for Digital Trunk Cable CM-XL end
Module No. Pin No. 1 2 1 3 4 5 6 7 1 2 2 3 4 5 6 7 A Blue (uu) Orange (uu) Green (uu) Brown (uu) Blue (vv) Orange (vv) Green (vv) Blue (xx) Orange (xx) Green (xx) Brown (xx) Blue (yy) Orange (yy) Green (yy) B -----Brown (vv) White (vv) [Br] -----Brown (yy) White (yy) [Br] C White (uu) [Bl] White (uu) [O] White (uu) [G] White (uu) [Br] White (vv) [Bl] White (vv) [O] White (vv) [G] White (xx) [Bl] White (xx) [O] White (xx) [G] White (xx) [Br] White (yy) [Bl] White (yy) [O] White (yy) [G]

Table No. 3-6 Note : For the values of uu, vv, xx and yy for different BMs please see table No. 3-4. () indicates cable number [] indicates corresponding cable colour pair Bl : Blue O : Orange G : Green Br : Brown

34

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

Signal Names for Digital Trunk Cable (CM End)


Module No. Pin No. 1 2 1 3 4 5 6 7 1 2 2 3 4 5 6 7 A RX_P {1} RX_P {3} TX_P {1} TX_P {3} RX_P {2} RX_P {4} TX_P {2} RX_P {5} RX_P {7} TX_P {5} TX_P {7} RX_P {6} RX_P {8} TX_P {6} B -----TX_P {4} TX_N {4} -----TX_P {8} TX_N {8} C RX_N {1} RX_N {3} TX_N {1} TX_N {3} RX_N {2} RX_N {4} TX_N {2} RX_N {5} RX_N {7} TX_N {5} TX_N {7} RX_N {6} RX_N {8} TX_N {6}

Table 3-7 Note : {} indicates digital Trunk number Notes: 1. 2. 3. 4. 5. 6. Wire wrap the pairs onto contact block pins of each module as per wiring details given. Snap the hood onto the contact block such that polarity tab (1) is towards pin 1 as per wiring done. The wire length shall be as shown in the figure. Polarity tabs to be retained as given below module 1:1, module 2:2. Put 12.0mm PVC/Black silicon rubber sleeve of 50mm length at both ends of L tied with cable ties. The two sets of digital trunk cables on each BTU (BUS 0 and BUS 1) are tied together with cable ties.

Note : All signal names are w.r.t MBM side. 3.4. CABLE PLACEMENTS Fig. 3.6 diagramatically explains the clock, ACIO and Digital trunk cable placements at TSU on RBM side and Fig. 3.7 and Fig. 3.8 show the cable placements at BTU0/1, on the CM side.

RSU INSTALLATION MANUAL

35

Chapter 3.

36

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

37

Chapter 3.

38

C-DOT DSS MAX-XL

RSU CABLE PREPARATION AND LAYING

RSU INSTALLATION MANUAL

39

Chapter 3.

40

C-DOT DSS MAX-XL

Chapter 4.

Jumper Settings and Modem Set-Up


4.1. 4.1.1. JUMPER SETTING ON ESM & ESL CARDS APC-ESM 397/H-S01 (IN CM-XL) 2 PIN JUMPERS (in all slots) Jumpers W11, W21, W22, W24 are to be shorted. Rest of the jumpers are to be left open. 4.1.2. APC-ESL 362/H-S00 (IN CM-L) A. B. Short 2 pin jumpers W3 & W11 in all the slots i) For ODD Number slot of ESL card (i.e. 5,7,9, etc.) Short pins 2 & 3 of 3 PIN jumpers W5 & W10 and short pins 1 & 2 of 3 PIN jumpers W6 & W9. For EVEN Number Slot of ESL Card (ie 6,8,10 etc.) Short PINS 1&2 of 3 pin jumpers W5 & W10. Short PINS 2&3 of 3 pin jumpers W6 & W9. 4.2. APC-BPU43X/H-M01 (BPU MOTHERBOARD OF BM-XL) Jumper settings on BPU mother board as viewed from soldering side are as follows: Copy 1 Copy 0
(LSB)W2 1 W22 W23 W24 o o o o o o o o o o o o o o o o W17 W18 W19 W20 (MSB) (LSB)W13 W14 W15 W16 o o O O o o o o o o o o o o o o W9 W10 W11 W12 (MSB)

ii)

Currently only even numbered BM can be made as a RBM and for RBM-ID, the most significant bit (MSB) positions in the copy 0 and copy 1 BPU have to be made one, i.e. left open (no short). The jumper settings for RBM can be as follows:

RSU INSTALLATION MANUAL

41

Chapter 4.

Jumper Settings for W9-W16 (BPU COPY 0)


RBM NO. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Shorting Position W13,W15,W16,W9,W10,W11 W13,W16,W9,W10,W11 W13,W15,W9,W10,W11 W13,W9,W10,W11 W13,W15,W16,W10,W11 W13,W16,W10,W11 W13,W15,W10,W11 W13,W10,W11 W13,W15,W16,W9,W11 W13,W16,W9,W11 W13,W15,W9,W11 W13,W9,W11 W13,W15,W16,W11 W13,W16,W11 W13,W15,W11 W13,W11 Copy id Function = 82 = 86 = 8A = 8E = 92 = 96 = 9A = 9E = A2 = A6 = AA = AE = B2 = B6 = BA = BE

Table No. 4-1 Jumper Settings for W17-W24 (BPU COPY 1)


RBM NO. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 Shorting Position W23,W24,W17,W18,W19 W24,W17,W18,W19 W23,W17,W18,W19 W17,W18,W19 W23,W24,W18,W19 W24,W18,W19 W23,W18,W19 W18,W19 W23,W24,W17,W19 W24,W17,W19 W23,W17,W19 W17,W19 W23,W24,W19 W24,W19 W23,W19 W19 Copy id Function = 83 = 87 = 8B = 8F = 93 = 97 = 9B = 9F = A3 = A7 = AB = AF = B3 = B7 = BB = BF

Table No. 4-2


42 C-DOT DSS MAX-XL

JUMPER SETTINGS AND MODEM SET-UP

Note : 1. 2. 4.3. The mechanical jumpers to be shorted as shown above. The jumpers not mentioned to be left open.

APC-BPU 005/T-M01 (BM-L BPU MOTHERBOARD) Jumper settings on BPU-M01 as viewed from soldering side are as follows in general.
. . . . . . . . . . . . . . . . W9 W10 W11 W12 W13 W14 W15 W16 . . . . . . . . . . . . . . . . W1 W2 W3 W4 W5 W6 W7 W8

MSB (always open for RBM)

MSB (always open for RBM)

Currently only an Even No BM can be made as a RBM and for RBM-ID, the Most Significant Bit (MSB) positions in the copy 0 & copy 1 BPU have to be made one, i.e. left open (no short) so the jumper settings for RBM can be as follows : JUMPER SETTINGS FOR W1-W8 (BPU COPY 0)
BM NO. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 SHORTING POSITION W1, W3, W4, W5, W6, W7 W1, W4, W5, W6, W7 W1, W3, W5, W6, W7 3 W1, W5, W6, W7 W1, W3, W4, W6, W7 W1, W4, W6, W7 W1, W3, W6, W7 3 W1, W6, W7 W1, W3, W4, W5, W7 W1, W4, W5, W7 W1, W3, W5, W7 W1, W5, W7 W1, W3, W4, W7 W1, W4, W7 W1, W3, W7 W1, W7 FUNCTION Copy id = 82 = 86 = 8A = 8E = 92 = 96 = 9A = 9E = A2 = A6 = AA = AE = B2 = B6 = BA = BE

Note : 1. The mechanical jumpers have to be shorted as shown above. 2. The jumpers not mentioned to be left open.

RSU INSTALLATION MANUAL

43

Chapter 4.

JUMPER SETTINGS FOR W9-W16 (BPU COPY 1)


BM NO. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 HORTING POSITION W11, W12, W13, W14, W15 W12, W13, W14, W15 W11, W13, W14, W15 W13, W14, W15 W11, W12, W14, W15 3 W12, W14, W15 W11, W14, W15 W14, W15 W11, W12, W13, W15 W12, W13, W15 W11, W13, W15 W13, W15 W11, W12, W15 W12, W15 W11, W15 W15 FUNCTION Copy id = 83 = 87 = 8B = 8F = 93 = 97 = 9B = 9F = A3 = A7 = AB = AF = B3 = B7 = BB = BF

Note : 1. The mechanical jumpers have to be shorted as shown above. 2. The jumpers not mentioned to be left open. 4.4. EXTENDING IOP TERMINAL TO RSU SITE USING MODEMS Two modems are required to extend IOP terminals to RSU site. One modem is required at IOP end and other at RSU end. Modems can be configured for leased line working or dial up working using AT commands and jumper settings. Modem setup is shown in Fig. 4.1. To configure the modem, refer modem users guide/operation manual.

44

C-DOT DSS MAX-XL

JUMPER SETTINGS AND MODEM SET-UP

4.4.1.

Dial Up Mode Working Connect terminal to modem, power on modem/terminal, issue AT commands to achieve the following : Restore factory default settings Set serial baud rate to 9600 Set modem baud rate to 9600 Disable flow control Set S register value to indicate after how many rings modem has to answer (Ex 1,2,3 ) Set the jumper settings if any for dial up working Test set may be made as in Fig. 4.1 To dial remote modem type ATDP followed by called Modem Telephone Number and wait for connect message on terminal, CD lamp to glow on modem.

4.4.2.

Leased Line Working In leased line working, two modems are connected by external plant cable pair or 64 kbps data circuit. Configure the modems as given below using AT commands and jumper settings. Configuring Modem IOP and Modem Configuration 1. 2. 3. 4. 5. 6. Configure modem as answer modem Configure modem for power on 2 wire leased line working Disable flow control Disable DTR (Data Terminal Ready) Signal Set serial baud rate and modem baud rate to 9600 bps Disable commands echo

RSU end (Terminal End) Modem Configuration 1. 2. 3. Configure modem as originate modem Configure modem for power on 2 wire leased line working Disable flow control

RSU INSTALLATION MANUAL

45

Chapter 4.

4. 5.

Set serial baud rate and modem baud rate to 9600 bps Disable DTR signal

Note : 1. For configuring modem using AT commands; power on modem, connect terminal to modem, issue AT commands to achieve required configuration. For exact commands, refer modem user guide/operation manual. Use jumper settings if any, to achieve above configuration Typical AT commands for configuring multi-tech MT2834ZDX are given in section 4.4.3, 4.4.4 for reference.

2. 3. 4.4.3.

Procedure for Configuring Multitech (MT2834ZDX) for Dial Up Working For dial up working the following are the commands for configuring modem. AT&F8&W0 AT$SB9600&W0 AT$MB9600&W0 AT&E3&W0 AT&D0&W0 ATS0=1&W0 Jumper settings lease/dial may be set to dial position modem. Set up may be made as shown in Fig. 4.1.

4.4.4.

Procedure for Configuring Multitech (MT2834ZDX) for Leased Line Working Step 1: Configure one modem as originate modem as follows : Connect terminal to modem, set terminal speed to 9600, power on modem. On typing 'AT', the modem responds as saying "OK". AT&F8&W0 AT$SB9600&W0 AT$MB9600&W0 AT&E3&W0 (Store default settings and save) (Serial baud rate set to 9600 and save) (Modem baud rate set to 9600 and save) (Disable flow control and save)
C-DOT DSS MAX-XL

46

JUMPER SETTINGS AND MODEM SET-UP

AT&D0&W0

(Ignore DTR signal and save)

Now set the jumper inside modem as follows : Set lease/dial to lease position Set originate/answer to originate position Step 2: Configure another modem as answer modem as follows : Connect terminal to modem, set terminal speed to 9600, power on modem and type the following. On typing 'AT', response from modem should be "OK". AT&F8&W0 AT$SB9600&W0 AT$MB9600&W0 AT&E3&W0 AT&D0&W0 (Store default settings and save) (Serial baud rate set to 9600 and save) (Modem baud rate set to 9600 and save) (Disable flow control and save) (Ignore DTR signal and save)

Now set the jumper inside modem as follows : Set lease/dial to lease position. Set originate/answer to answer position Step 3: Verify IOP serial port by connecting a terminal, login should appear and it should be possible to login. Connect answer modem RS232 port to this IOP port. Connect terminal to RS232 port of originate modem connect line jacks (RJ11) of both modems by using a shorting cable supplied for leased line working (simulating cable pair between modems or 64 kbps data circuits). Now power on modems, CD lamp will glow in both modems and link is established login should appear on terminal. Please note that when terminal/IOP port is connected to modem, TR lamp should glow in modem. Note : If login does not appear in icc port when terminal is connected, edit file "init tab" in / etc directory using vi editor. In line wherever required icc port is available, replace "off" by "respawn", save the file.

RSU INSTALLATION MANUAL

47

Chapter 4.

48

C-DOT DSS MAX-XL

Chapter 5.

MDF - Installation
5.1. GENERAL The MDF installation, on the RBM side, is similar to the MDF installation for CDOT-SBM RAX in respect of subscriber and trunk cabling. However the additional cabling is required for RSU installation on the RBM side and on the parent exchange side in respect of 16 PCMs between parent exchange and RBM. 5.2. DIGITAL TRUNK CABLE TERMINATION ON RBM TO MDF (FOR RSU PCMS) a) b) 16 PCMs i.e. L1 to L8, L17 to L24 are terminated on 4 Nos of 2/8 LSA modules. If 4 pair cable is used from TSU frame to MDF, terminations on MDF are done as shown in figure 5.1 (a). If 8 pair cable is used from TSU frame to DDF, terminations on MDF are done as shown in figure 5.1 (b). Cables marked RNUU, RNVV coming from copy 0 of TSU are terminated on first 2/8 module as shown in figure. Cables marked RNXX, RNYY coming from Copy 0 of TSU are terminated on second 2/8 module as shown in figure. For cables coming from copy 1 of TSU termination is done on third & fourth modules. Termination is done in the same way, as done for copy 0 cables. For digital trunk cable preparation using 4 pair shielded cable & placement details, refer to sections 3.2.2.1 & 3.2.2.2. For digital trunk cable preparation using 8 pair shielded cable & placement details, refer to section 3.2.2.3. The grounding leads coming out from digital cables at the ends near MDF can be crimped to a ring terminal and terminated on one of the screw & nut holding same backmount frame as shown in Fig. 3.2 c.

c)

d)

e)

49

C-DOT DSS MAX-XL

Chapter 5.

5.3.

DIGITAL TRUNK CABLE TERMINATION ON CM TO DDF (FOR RSU PCMS) While laying the cables on CM side, details given in table 5-1 may be seen depending on CM-L or CM-XL. a) b) c) 16 PCMs ie. L1 to L8, L17 to L24 are terminated on 4 Nos of 2/8 LSA modules as shown in Figure 5.2. For each RBM, 4 Nos of 4 pair shielded cables are used per BTU frame. 4 Nos. of 4 pair cables from BTU0 are terminated on first and second 2/8 LSA Modules. Cables marked MNUU, MNVV are terminated on first 2/8 LSA Module and Cables marked MNXX, MNYY are terminated on second 2/8 LSA. Similarly 4 Nos of cables from BTU1 are terminated on third & fourth 2/8 LSA modules. All terminations are done as shown in Figure 5.2. For cable preparation & placement details refer to section 3.3.1 & 3.4. The grounding leads coming out from digital cables near DDF can be crimped to ring terminal & terminated to one of screw & nut of backmount frame.

d) e) 5.4.

INTER CONNECTIONS The connections between RBM & CM through respective DDFs are shown in Figure 5.3.

50

C-DOT DSS MAX-XL

WH BN BN BN L4 Rx BN L20 Rx L24 Rx WH L8 Rx WH WH

WH GN GN GN L2 Rx GN L18 Rx WH L6 Rx WH L22 Rx

WH

YY

VV

LABEL HOLDER

UU

XX

WH OR OR OR L3 Tx OR L19 Tx L7 Tx WH WH

WH

UU

XX

RSU INSTALLATION MANUAL


WH OR OR OR OR L4 Tx L20 Tx L24 Tx WH L8 Tx WH WH WH BL BL BL BL L2 Tx L18 Tx WH L6 Tx L22 Tx WH WH WH BN BN BN BN L3 Rx L19 Rx L23 Rx WH L7 Rx WH WH WH GN GN GN GN L1 Rx L17 Rx L21 Rx WH L5 Rx WH WH

VV

YY

L23 Tx

WH BL BL BL L1 Tx L17 Tx L5 Tx WH

WH

WH BL

L21 Tx

BUS-

BUS-1

FIG. 5.1 (a) 4 PAIR DIGITAL TRUNK CABLE TERMINATION ON RBM END MDF (FOR RSU PCMs)
\DESIGN\DSSMAX\MAX-XL\RSU-XLIM\RSXLIF1A

MDF - INSTALLATION

51

VV

YY

VV

YY

LABEL HOLDER

UU

UU

XX

XX

52
RD GN L4 Rx GN GN L8 Rx GN L20 Rx L24 Rx RD RD RD RD OR L2 Rx OR OR L6 Rx OR L18 Rx L22 Rx RD RD RD RD BL L4 Tx BL BL L8 Tx BL L20 Tx L24 Tx RD RD RD WH SL L2 Tx SL SL L6 Tx SL L18 Tx L22 Tx WH WH WH WH BN L3 Rx BN BN L7 Rx BN L19 Rx L23 Rx WH WH WH WH GN L1 Rx GN GN L5 Rx GN L17 Rx L21 Rx WH WH WH WH OR OR L3 Tx L7 Tx OR OR L19 Tx WH WH WH L23 Tx WH BL L1 Tx BL BL L5 Tx WH L17 Tx WH WH BL L21 Tx BUS- BUS-1

Chapter 5.

FIG. 5.1 (b) 8 PAIR DIGITAL TRUNK CABLE TERMINATION ON RBM END MDF (FOR RSU PCMs)
\DESIGN\DSSMAX\MAX-XL\RSU-XLIM\RSXLIF1B

C-DOT DSS MAX-XL

WH BN BN BN L4 Tx BN WH L8 Tx L20 Tx L24 Tx WH

WH

WH GN GN GN L2 Tx GN WH L6 Tx L18 Tx L22 Tx WH

WH

YY

VV

VV

WH OR OR OR L4 Rx OR L24 Rx WH L8 Rx L20 Rx WH

LABEL HOLDER

XX

UU

WH OR L3 Rx OR OR OR L7 Rx L19 Rx L23 Rx

WH WH WH

WH BL BL L1 Rx BL L5 Rx L17 Rx

WH WH

UU

XX

RSU INSTALLATION MANUAL


WH WH BL BL BL L2 Rx BL L22 Rx WH L6 Rx L18 Rx WH WH WH BN BN L3 Tx BN BN WH L7 Tx L19 Tx L23 Tx WH WH WH GN GN L1 Tx GN GN WH L5 Tx L17 Tx L21 Tx WH WH

YY
WH BL

L21 Rx

BUS-

BUS-1

FIG. 5.2 4 PAIR DIGITAL TRUNK CABLE TERMINATION ON CM END DDF (FOR RSU PCMs)
\DESIGN\DSSMAX\MAX-XL\RSU-XLIM\RSXLIF2

MDF - INSTALLATION

53

Chapter 5.

54

C-DOT DSS MAX-XL

MDF - INSTALLATION

CABLE LAYOUT TABLE 5.1


Sl. No. 1. 2. 3#. Cable Marker RCX0 RCX1 RA01 & RA03 RA02 & RA04 RRSA 4#. RB01 & RB03 RB02 & RB04 RRSB 5. BPT1 & BPT2 MA01 & MA02 MA03 & MA04 MB01 & MB02 MB03 & MB04 MA05 & MA06 MA07 & MA08 MB05 & MB06 C-DOT Assy. No. From To Remarks

On RSU Side * ACB-RSUXRCX0-000 ACB-RSUXRCX1-000 ACB-ERSURN01-000 ACB-ERSURN02-000 -doACB-ERSURN01-000 ACB-ERSURN02-000 -doACB-MAXXBPTX-000 OR ACB-RSUUTEZX-000 ACB-MAXRMD01-000 ACB-MAXRMD02-000 ACB-MAXRMD03-000 ACB-MAXRMD04-000 ACB-MAXRMD05-000 ACB-MAXRMD06-000 ACB-MAXRMD07-000 2/1/6/13/A/1 2/1/6/14/A/1 2/1/6/13/A/2 2/1/6/13/A/3 2/1/6/13/A/3 2/1/6/14/A/2 2/1/6/14/A/3 2/1/6/14/A/3 2/1/5/J7/4 2/1/5/J24/4 CM/1/05/B/1 CM/1/05/B/2 CM/4/05/B/1 CM/4/05/B/2 CM/1/06/B/1 CM/1/06/B/2 CM/4/06/B/1 2/1/6/12/B/1 2/1/6/15/B/1 MDF a) MDF b) 2/1/6/ 12/B/4 MDF a) MDF b) 2/1/6/ 15/B/4 VDU VDU DDF DDF DDF DDF DDF DDF DDF RBM-04 RBM-02 BM-XL BM-L For RBM-02

CM side 1. 2. 3. 4. 5. 6. 7.

For convenience, cables on RSU side are shown for RBM -02 only. For other RBMs similar cables are required. For 4 pair cables, cable layout is shown above. In case of 8 pair cables, cable layout will be changed according to section 3.2.2.3.

CM side cables are shown for CM-XL for all 16 RSUs. In case of MAX-L, MBXX will be terminated on CM/1/15/B/1 & CM/1/15/B/2 for RBM-02, CM/1/16/B/1 & CM/1/16/B/2 for RBM-04

RSU INSTALLATION MANUAL

55

Chapter 5. Sl. No. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. Cable Marker MB07 & MB08 MA09 & MA10 MA11 & MA12 MB09 & MB10 MB11 & MB12 MA13 & MA14 MA15 & MA16 MB13 & MB14 MB15 & MB16 MA17 & MA18 MA19 & MA20 MB17 & MB18 MB19 & MB20 MA21 & MA22 MA23 & MA24 MB21 & MB22 MB23 & MB24 MA25 & MA26 MA27 & MA28 MB25 & MB26 MB27 & MB28 MA29 & C-DOT Assy. No. ACB-MAXRMD08-000 ACB-MAXRMD09-000 ACB-MAXRMD10-000 ACB-MAXRMD11-000 ACB-MAXRMD12-000 ACB-MAXRMD13-000 ACB-MAXRMD14-000 ACB-MAXRMD15-000 ACB-MAXRMD16-000 ACB-MAXRMD17-000 ACB-MAXRMD18-000 ACB-MAXRMD19-000 ACB-MAXRMD20-000 ACB-MAXRMD21-000 ACB-MAXRMD22-000 ACB-MAXRMD23-000 ACB-MAXRMD24-000 ACB-MAXRMD25-000 ACB-MAXRMD26-000 ACB-MAXRMD27-000 ACB-MAXRMD28-000 From CM/4/06/B/2 CM/1/07/B/1 CM/1/07/B/2 CM/4/07/B/1 CM/4/07/B/2 CM/1/ 08/B/1 CM/1/08/B/2 CM/4/08/B/1 CM/4/08/B/2 CM/1/09/B/1 CM/1/09/B/2 CM/4/09/B/1 CM/4/09/B/2 CM/1/10/B/1 CM/1/10/B/2 CM/4/10/B/1 CM/4/10/B/2 CM/1/11/B/1 CM/1/11/B/2 CM/4/11/B/1 CM/4/11/B/2 MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF RBM-14 RBM-12 RBM-10 RBM-08 RBM-06 To Remarks

29. 56

ACB-MAXRMD29-000

CM/1/12/B/1

MDF C-DOT DSS MAX-XL

MDF - INSTALLATION Sl. No. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. Cable Marker MA30 MA31 & MA32 MB29 & MB30 MB31 & MB32 MA33 & MA34 MA35 & MA36 MB33 & MB34 MB35 & MB36 MA37 & MA38 MA39 & MA40 MB37 & MB38 MB39 & MB40 MA41 & MA42 MA43 & MA44 MB41 & MB42 MB43 & MB44 MA45 & MA46 MA47 & MA48 MB45 & MB46 MB47 & MB48 MA49 & C-DOT Assy. No. From To Remarks

ACB-MAXRMD30-000 ACB-MAXRMD31-000 ACB-MAXRMD32-000 ACB-MAXRMD33-000 ACB-MAXRMD34-000 ACB-MAXRMD35-000 ACB-MAXRMD36-000 ACB-MAXRMD37-000 ACB-MAXRMD38-000 ACB-MAXRMD39-000 ACB-MAXRMD40-000 ACB-MAXRMD41-000 ACB-MAXRMD42-000 ACB-MAXRMD43-000 ACB-MAXRMD44-000 ACB-MAXRMD45-000

CM/1/12/B/2 CM/4/12/B/1 CM/4/12/B/2 CM/1/15/B/1 CM/1/15/B/2 CM/4/15/B/1 CM/4/15/B/2 CM/1/16/B/1 CM/1/16/B/2 CM/4/16/B/1 CM/4/16/B/2 CM/1/17/B/1 CM/1/17/B/2 CM/4/17/B/1 CM/4/17/B/2 CM/1/18/B/1

MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF

RBM-16

RBM-18

RBM-20

RBM-22

46.

ACB-MAXRMD46-000

CM/1/18/B/2

MDF

RBM-24

47.

ACB-MAXRMD47-000

CM/4/18/B/1

MDF

48.

ACB-MAXRMD48-000

CM/4/18/B/2

MDF

49.

ACB-MAXRMD49-000

CM/1/19/B/1

MDF

RSU INSTALLATION MANUAL

57

Chapter 5. Sl. No. 50. 51. 52. 53. 54. 55. 56. 57. 58. 59. 60. 61. 62. 63. 64. Cable Marker MA50 MA51 & MA52 MB49 & MB50 MB51 & MB52 MA53 & MA54 MA55 & MA56 MB53 & MB54 MB55 & MB56 MA57 & MA58 MA59 & MA60 MB57 & MB58 MB59 & MB60 MA61 & MA62 MA63 & MA64 MB61 & MB62 MB63 & MB64 C-DOT Assy. No. From To Remarks

ACB-MAXRMD50-000 ACB-MAXRMD51-000 ACB-MAXRMD52-000 ACB-MAXRMD53-000 ACB-MAXRMD54-000 ACB-MAXRMD55-000 ACB-MAXRMD56-000 ACB-MAXRMD57-000 ACB-MAXRMD58-000 ACB-MAXRMD59-000 ACB-MAXRMD60-000 ACB-MAXRMD61-000 ACB-MAXRMD62-000 ACB-MAXRMD63-000 ACB-MAXRMD64-000

CM/1/19/B/2 CM/4/19/B/1 CM/4/19/B/2 CM/1/20/B/1 CM/1/20/B/2 CM/4/20/B/1 CM/4/20/B/2 CM/1/21/B/1 CM/1/21/B/2 CM/4/21/B/1 CM/4/21/B/2 CM/1/22/B/1 CM/1/22/B/2 CM/4/22/B/1 CM/4/22/B/2

MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF MDF

RBM-26

RBM-28

RBM-30

RBM-32

Note: Only an even number BM can be made an RBM. Accordingly, cable markers on CM side are shown in the above table.

58

C-DOT DSS MAX-XL

Potrebbero piacerti anche