Sei sulla pagina 1di 1

300 MIN

300

MIN
1. HEIGHT

NOTES:
SEE SPECIAL NOTES ENTITLED "OWNER REQUIREMENTS FOR WATER MAINS AND APPURTENANCES" FOR ADDITIONAL INFORMATION ON THRUST RESTRAINT REQUIREMENTS. 2. THRUST RESTRAINT USING THRUST BLOCKS OR RESTRAINED LENGTHS ARE SHOWN ON THESE SHEETS. THRUST BLOCKS, RESTRAINED JOINTS USING TIE RODS, OR RETAINER GLANDS ARE ALL ACCEPTABLE METHODS TO NYSDOT. HOWEVER, THE THRUST RESTRAINT METHOD SELECTED SHALL BE APPROVED BY THE SYSTEM OWNER. 3. IF THE OWNER OF THE WATER SYSTEM REQUIRES A METHOD THAT RESTRAINS INDIVIDUAL JOINTS, EACH JOINT THAT FALLS WITHIN THE MINIMUM RESTRAINED LENGTH, MEASURED FROM THE CENTER OF THE FITTING, AS SHOWN ON THESE SHEETS SHALL BE RESTRAINED, AND SHALL WITHSTAND THE MAXIMUM PRESSURE APPLIED TO THE SYSTEM.

WIDTH WIDTH
HEIGHT

PLAN PLAN END VIEW

END VIEW

90n BEND THRUST BLOCK


PIPE SIZE
4 NPS 6 NPS 8 NPS 10 NPS 12 NPS WIDTH 700 1000 1300 1600 1800 HEIGHT 350 500 650 800 1000

22
HEIGHT 1100 1250 1400 1500 1800

n BEND THRUST BLOCK


HEIGHT 200 250 350 400 500

4.

CLASS A CONCRETE SHALL NOT BE PLACED UNDER WATER. THE CONTRACTOR SHALL DEWATER THE EXCAVATION OR PLACE TYPE G CONCRETE USING APPROPRIATE UNDERWATER PLACEMENT TECHNIQUES.

PIPE SIZE
14 NPS 16 NPS 18 NPS 20 NPS 24 NPS

WIDTH 2200 2500 2800 3200 3800

PIPE SIZE
4 NPS 6 NPS 8 NPS 10 NPS 12 NPS

WIDTH 350 600 700 900 1000

PIPE SIZE
14 NPS 16 NPS 18 NPS 20 NPS 24 NPS

WIDTH 1100 1400 1500 1500 1900

HEIGHT 600 650 750 900

5.

CONCRETE FOR THRUST BLOCKS SHALL NOT BE ALLOWED TO COVER OR INTERFERE WITH JOINT OR RESTRAINT HARDWARE. PLASTIC SHEETING OR BUILDING FELT MAY BE PLACED OVER PIPE OR FITTINGS TO PREVENT CONCRETE FROM ADHERING TO SURFACES. CONCRETE FOR THRUST BLOCKS SHALL BE POURED AGAINST UNDISTURBED SOIL.

6.
1000

FOR BENDS, BEARING AREA SHALL BE PARALLEL TO THE EDGE OF THE FITTING AT THE FITTING MIDPOINT.

* DIMENSIONS ARE FOR STANDARD CONDITIONS, SEE NOTE 10

* DIMENSIONS ARE FOR STANDARD CONDITIONS, SEE NOTE 10 7. 8. FOR TEES, BEARING AREA SHALL BE PERPENDICULAR TO THE BRANCH (SINGLE LEG) AXIS. FOR REDUCERS, BEARING AREA SHALL BE PERPENDICULAR TO THE FITTING AXIS. THE MINIMUM THICKNESS ALONG THE FITTING AXIS SHALL BE 300mm OR THE LENGTH BETWEEN THE BELLS, WHICHEVER IS SMALLER. 9. THRUST RESTRAINT FOR SIZES OVER 24 NPS OR FOR FITTINGS NOT SHOWN ON THESE SHEETS WILL BE DESIGNED ON A CASE BY CASE BASIS, AND WILL BE SHOWN IN THE CONTRACT DOCUMENTS. 10. THRUST BLOCKS SIZES AND MINIMUM RESTRAINED LENGTHS SHOWN ON THESE SHEETS ARE BASED UPON THE FOLLOWING STANDARD CONDITIONS: 1.5 1.5 m 1380 kPa 96 kPa SAFETY FACTOR DEPTH OF COVER WATER SYSTEM TEST PRESSURE SOIL BEARING CAPACITY

300 MIN

300
MIN

WIDTH
HEIGHT

WIDTH

HEIGHT
11.

1440 kg/z SOIL UNIT WEIGHT FOR INSTALLATIONS NOT MEETING THE CONDITIONS OF NOTE 10, THE CONTRACTOR SHALL SUBMIT CALCULATIONS TO THE ENGINEER FOR APPROVAL OF RESTRAINT LENGTH CHOSEN. 12. TO DETERMINE REQUIRED SIZES FOR DIFFERENT CONDITIONS, MULTIPLY THE DIMENSION BY A FACTOR OF THE SPECIFIC VALUE DIVIDED BY THE STANDARD VALUE.

PLAN

END VIEW

PLAN

END VIEW

EXAMPLE: FIND THRUST BLOCK DIMENSION FOR 12 NPS 45n BEND WITH 690 kPa TEST PRESSURE:

45n BEND THRUST BLOCK


PIPE SIZE
4 NPS 6 NPS 8 NPS 10 NPS 12 NPS WIDTH 600 800 1000 1200 1400 HEIGHT 250 350 500 600 700

11
HEIGHT 800 1000 1000 1200 1400

n
WIDTH 300 350 500 600 700

BEND THRUST BLOCK


HEIGHT 125 200 250 300 350

FROM TABLE "45n BEND THRUST BLOCK" AREA REQUIRED AT 1380 kPa IS 1.4m X 0.7m = 0.98s FOR 690 kPa, AREA = 0.98 X (690/1380) = 0.49s

PIPE SIZE
14 NPS 16 NPS 18 NPS 20 NPS 24 NPS

WIDTH 1600 1700 2200 2200 2700

PIPE SIZE
4 NPS 6 NPS 8 NPS 10 NPS 12 NPS

PIPE SIZE
14 NPS 16 NPS 18 NPS 20 NPS 24 NPS

WIDTH 900 1000 1100 1100 1400

HEIGHT 400 500 500 600 700

USE WIDTH = 1.0m, HEIGHT = 0.5m (AREA = 0.5s)

* DIMENSIONS ARE FOR STANDARD CONDITIONS, SEE NOTE 10

* DIMENSIONS ARE FOR STANDARD CONDITIONS, SEE NOTE 10

MINIMUM RESTRAINED LENGTH OF PIPE (m) L R


FITTING
HORIZONTAL BENDS 11n 0.4 0.4 0.9 2.1 2.6 0.6 0.6 1.2 3.0 3.8 0.8 0.8 1.6 3.8 4.9 0.9 0.9 1.9 4.7 5.9 1.1 1.1 2.3 5.5 7.0 1.2 1.2 2.6 6.2 8.0 1.4 1.4 2.9 7.0 9.0 1.5 1.5 3.2 7.8 10.0 1.7 1.7 3.5 8.5 11.0 1.9 2.0 4.1 9.9 12.9 4 NPS 6 NPS 8 NPS 10 NPS 12 NPS 14 NPS 16 NPS 18 NPS 20 NPS 24 NPS

300 MIN WIDTH

22n 45n 90n DEAD ENDS

NOTE* FOR POLYETHYLENE WRAPPED PIPE, MULTIPLY VALUES IN TABLE BY 1.45 NOTE* PVC PIPE WILL TYPICALLY HAVE SLIGHTLY GREATER RESTRAINED LENGTH.

300 MINIMUM

HEIGHT

WIDTH

HEIGHT

NOTE: ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE NOTED

PLAN

END VIEW

PLAN

END VIEW

STATE OF NEW YORK DEPARTMENT OF TRANSPORTATION

REDUCER THRUST BLOCK


SIZE
6x4 NPS 8x4 NPS 8x6 NPS 10x6 NPS 10x8 NPS 12x6 NPS 12x8 NPS 12x10 NPS WIDTH 450 700 550 800 600 1000 900 700 HEIGHT 450 700 550 800 600 1000 900 700

METRIC STANDARD SHEET


HEIGHT 1350 1200 1050 1550 1200 2000 1750 1350

SIZE
16x8 NPS 16x10 NPS 16x12 NPS 20x12 NPS 20x16 NPS 24x12 NPS 24x16 NPS 24x20 NPS

WIDTH 1350 1200 1050 1550 1200 2000 1750 1350

TEEv/vDEAD END THRUST BLOCK


WIDTH 600 900 1000 1300 1600 HEIGHT 300 400 600 700 800 WIDTH 1700 2000 2300 2600 3100 HEIGHT 1000 1100 1200 1300 1600

PIPE SIZE
4 NPS 6 NPS 8 NPS 10 NPS 12 NPS

PIPE SIZE
14 NPS 16 NPS 18 NPS 20 NPS 24 NPS

WATER MAIN HORIZONTAL THRUST RESTRAINT DETAILS


APPROVED NOVEMBER 1, 2011
/S/ RICHARD W. LEE, P.E.

ISSUED UNDER EB 11-025 EFFECTIVE DATE: 05/03/2012

DEPUTY CHIEF ENGINEER (DESIGN)

* DIMENSIONS ARE FOR STANDARD CONDITIONS, SEE NOTE 10

* DIMENSIONS ARE FOR STANDARD CONDITIONS, SEE NOTE 10