Normal operation

AEB Grid 165 kV

BAA

BCT01

BBT01

G BCA08 OPEN

BBA09 BBA

BBA10 OPEN

BCA09 BCA

BBA11

BBT01

BBT01

BCA02 BHT01

BCA01

BCA05

BCA06 BHT03

BFT01

BFT02 BHF06 AB001 OPEN

BHT02

BCT02

BCT03

AFB01 60 kV

BFE BFE02 AB001 OPEN BBB BFG06 AB001 BMF BHT03 BHT04

BFF BFG02 AB001 BFG

BHF

BHE08 AB001 OPEN

BHE BHC BCC

BCA10

BCC04 OPEN

ST.ESTRI PVEJ

AFB 60 kV

G
g

BBB06

BHF03 AL001 BME02 AB001 OPEN

BHF02 AL001

BHF01 AE001

BHE03 AB001

BHE01 AE001

BHE06 AE001

BCC07

BHT06 BLJ BLG BLD BLE BLF BLC BHG01 AB001

BBB05

BBB07

BMF06 AB001

BME

BME01 AB001 OPEN

BHG BHG01 AG001 BCB (Kulpids)

BFK BFH10 BFH20 BFK05 AB001 BMK

BMK02 AB001 OPEN

BHT04 BHT05

BLH

BRA UPS OPEN OPEN BHH BRK BHA BHB BHJ

Startup operation
AEB Grid 165 kV

BAA

BCT01

BBT01

G BBA09 OPEN BBA10 CLOSED BCA08 CLOSED

BCA09 BCA

BBA11

BBA

BBT01

BBT01

BCA02 BHT01

BCA01

BCA05

BCA06 BHT03

BFT01

BFT02 BHF06 AB001 OPEN

BHT02

BCT02

BCT03

AFB01 60 kV

BFE BFE02 AB001 OPEN BFG06 AB001 BMF BHT03 BHT04

BFF BFG02 AB001 BFG

BHF

BHE08 AB001 OPEN BHF01 AE001 BHE03 AB001

BHE BHC BCC

BCA10

BCC04 OPEN

ST.ESTRI PVEJ

AFB 60 kV

G
g

BBB06 BBB

BHF03 AL001 BME02 AB001 OPEN

BHF02 AL001

BHE01 AE001

BHE06 AE001

BCC07

BHT06 BLJ BLG BLD BLE BLF BLC BHG01 AB001

BBB05

BBB07

BMF06 AB001

BME

BME01 AB001 OPEN

BHG BHG01 AG001 BCB (Kulpids)

BFK BFH10 BFH20 BFK05 AB001 BMK

BMK02 AB001 OPEN

BHT04 BHT05

BLH

BRA OPEN OPEN BHH BRK BHA BHB BHJ

Visited network
AEB Grid 165 kV

BAA

BCT01

BBT01

G BBA09 OPEN BBA10 OPEN BCA08 OPEN

BCA09 OPEN

BCA

BBA11

BBA

BBT01

BBT01

BCA02 BHT01

BCA01

BCA05

BCA06 BHT03

BFT01

BFT02 BHF06 AB001 OPEN

BHT02

BCT02

BCT03

AFB01 60 kV

BFE BFE02 AB001 BBB BFG03 AB001 OPEN BMF BFG

BFF BFG02 AB001

BHF

BHE08 AB001 OPEN

BHE BHC BCC

BCA10

BCC04 CLOSED

ST.ESTRI PVEJ

AFB 60 kV

G
g

BBB06

BHF03 AL001 BME02 AB001 OPEN

BHF02 AL001

BHF01 AE001

BHE03 AB001

BHE01 AE001

BHE06 AE001

BCC07

BHT06 BLJ BLG BLD BLE BLF BLC BHG01 AB001

BBB05 BHT03

BBB07 BHT04

BMF06 AB001 CLOSED

BME

BME01 AB001 CLOSED BFK BFH10 BFH20 BFK05 AB001 OPEN BMK BCB (Kulpids) BHG

BHG01 AG001

BMK02 AB001 CLOSED BHT04 BHT05 BLH

BRA UPS CLOSED CLOSED BHH BRK BHA

BHB

BHJ

Diesel set
AEB Grid 165 kV

BAA

BCT01

BBT01

G BBA09 OPEN BBA10 OPEN BCA08 OPEN

BCA09 OPEN

BCA

BBA11

BBA

BBT01

BBT01

BCA02 BHT01

BCA01

BCA05

BCA06 BHT03

BFT01

BFT02 BHF06 AB001 OPEN

BHT02

BCT02

BCT03

AFB01 60 kV

BFE BFE02 AB001 BBB BFG03 AB001 OPEN BMF BFG

BFF BFG02 AB001

BHF

BHE08 AB001

BHE BHC BCC

BCA10

BCC04 OPEN

ST.ESTRI PVEJ

AFB 60 kV

G
g

BBB06

BHF03 AL001 BME02 AB001

BHF02 AL001

BHF01 AE001

BHE03 AB001

BHE01 AE001

BHE06 AE001

BCC07

BHT06 BLJ BLG BLD BLE BLF BLC BHG01 AB001

BBB05 BHT03

BBB07 BHT04

BMF06 AB001 CLOSED

BME

CLOSED

BME01 AB001 CLOSED BFK BFH10 BFH20 BFK05 AB001 OPEN BMK BCB (Kulpids) BHG

BHG01 AG001

BMK02 AB001 CLOSED BHT04 BHT05 BLH

BRA UPS CLOSED CLOSED BHH BRK BHA

BHB

BHJ

Low voltage level


GRID AEB03 165kV

AEB 165 kV

BBT01

BCA09 FRA BCT10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) BCT01 Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 3150

Value 3150

BCA08 BBA Power kW/kVA Normal current (A) Start current (A) Starting time (sec)

Setting 3150

Value 3150

BBA10 FRA BCA Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec BBA 10 kV I>>=5% / 0.5 Sec SG1 checksum

Setting 3150

Value 3150

BBA09 FRA BBT Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 SG1 checksum checksum

Setting 3150

Value 3150

indfdning 2750/1 2,55 0,20 3,67 0,04 No 8 40

indfdning 2750/1 8032,5 0,20 11560,5 0,04 No 8 40

Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec BCA 10kV I>>=5% / 0.5 Sec SG1 checksum

2750/1 2,55 0,04 3,55 0,140 No 8 40

2750/1 8032,5 0,04 11182,5 0,140 No 8 40

2750/1 2,55 0,200 3,76 0,04 Yes 1+8 40

2750/1 8032,5 0,200 11844 0,04 Yes 1+8 40 BBA11 BBB Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Setting 630 Value 630

BCC04 B2 BCT02 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) AFB01 AFB60 kV GRID 60 kV ST.ESTRIPVEJ BCT03 14MVA BCT02 8MVA SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 8000 440

Value 8000 440

BCA10 BCC Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 835

Value 835

BCA01 BHT01 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1600 88

Value 1600 88

BCA02 BHT02 Power kW/kVA Normal current (A) Start current (A) Starting time (sec)

Setting 1600 88

Value 1600 88

T 500/1 1,06 10 3,52 0,04 Yes 6 27 No

T 500/1 466,4 10 1548,8 0,04 Yes 6 27 No

800/1 0,97 10 4,40 0,14 No 6 11 No Yes 220

800/1 809,95 10 3674 0,14 No 6 11 No Yes 220

T 100/1 1,06 100 3,96 0,04 Yes 6 27 No Yes 220

T 100/1 93,28 100 348,48 0,04 Yes 6 27 No Yes 220

Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

T 100/1 1,06 100 3,96 0,04 Yes 6 27 No Yes 220

T 100/1 93,28 100 348,48 0,04 Yes 6 27 No Yes 220

BBA20 BFT01 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 2500 137,5

Value 2500 137,5

T 150/1 1,10 100 3,67 0,04 Yes 6 27 No Yes 220

T 150/1 151,25 100 504,625 0,04 Yes 6 27 No Yes 220

BBA21 BFT02 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 2500 137,5

Value 2500 137,5

Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum BBB BBB05 BFT03 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>>

400/1 1,55 15 1,80 0,14 No 8 43 No Yes 220

400/1 976,5 15 1134 0,14 No 6+8 43 No Yes 220

T 150/1 1,10 100 3,67 0,04 Yes 6 27 No Yes 220

T 150/1 151,25 100 504,625 0,04 Yes 6 27 No Yes 220

Setting 1250 69

Value 1250 69

BCC

BBB07 BFT04 Power kW/kVA Normal current (A) Start current (A) Starting time (sec)

Setting 2000 110

Value 2000 110

BCC07 BFT06 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum BHT06

Setting 400 22

Value 400 22

T 100/1 0,83 10 3,11 0,04 Yes 6 27 No Yes 220 220

T 100/1 57,27 10 214,59 0,04 Yes 6 27 No Yes 220

Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

T 125/1 1,06 10 3,96 0,04 Yes 6 27 No Yes 220

T 125/1 116,6 10 435,6 0,04 Yes 6 27 No Yes 220

T 40/1 0,66 10 2,20 0,04 Yes 6 59 No Yes 220

T 40/1 14,52 10 48,4 0,04 Yes 6 59 No Yes 220 DYN5


BFE07 Setting Value AB001 LG 1250 R800/800 Ith 800A 1.600A 800A I1 1*Ith 800A t1 INT 20 s I2 10*Ith 96.000A 8.000A t2 0,3 s 0,3 s I3 10kA 10kA BHE08 AB001 G2 Ith I1 t1 I2 t2 I3

Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation DYN5 BFT01 DYN5 BFT02 Setting Value
4000/4000 4000A 4000A 1*Ith 4000A Max 12 s 6*Ith 24.000A 0,3 s 0,3 s 12*Ith 48.000A

I>= 2% / 5 Sec
BFF01 AB001 G5 Ith I1 t1 I2 t2 I3

DYN5 BHT01

Setting

Value

BHT02

BHE

MAX SLM03 -/400, OESA63 -/63

2500/2500 2.500A 2.500A 1*Ith 2.500A Min 2s 4*Ith 10.000A 0,15 s 0,15 s 4*Ith 10.000A

BHF

BHF07 AB001 G2 Ith I1 t1 I2 t2 I3

Setting

Value

2500/2500 2.500A 2.500A 1*Ith 2.500A INT 5,5 s 4*Ith 10.000A 0,15 s 0,15 s 12*Ith 30.000A

BHF06 AB001 G2 Ith I1 t1 I2 t2 I3

Setting

Value

1250/1250 1.250A 1.250A 1*Ith 1.250A Min 2s 6*Ith 7.500A 0,15 s 0,15 s 10kA 10.000A

MAX SLM03 -/400, DIN02 -/350

BFE

BFE12 AB001 G5 Ith I1 t1 I2 t2 I3

Setting

Value

I>>=5% / 0.5 Sec SG1 checksum

BFF

4000/4000 4000A 4000A 1*Ith 4000A Max 12 s 6*Ith 24.000A 0,3 s 0,3 s 12*Ith 48.000A

DYN5 MAX SLM02-/300 BFT03 BFT04 Setting


Ith I1 t1 I2 t2

BHE03AB001

BHF02AL001

BFK04AC001 -F01

BFK03AC001 -F01

BHG

5*Ith 0,1 s 10kA

10.000A 0,1 s 10kA

MAX OESA63 -/16, S273 U16 -/16, SLM00 -/100

BLC

BLF

BLE

BLD

BLG

BLJ

BJD

BJE

BJH

BHG02Ak001-F01

BHG01AL001-F01

BHG02Ak001-F02

BHG01AL001-F02

BHG03AD002

BFG06AB001

6*Ith 0,1 s 10kA

4.800A 0,1 s 10kA

BFG05AC001 -F01

BHG01 AG001 G2 Ith I1 t1 I2 t2 I3

Setting
1250/400 800A 0.5*Ith

Value MAX SLM03 -/400, DIN02 -/250


800A 400A BFG03 AB001 G3 Ith I1 t1 I2 t2 I3

BFG

BFE02 AB001 G5 Ith I1 t1 I2 t2 I3

Setting

Value

4000/4000 4000A 4000A 1*Ith 4000A INT 5,5 s 4*Ith 16.000A 0,3 s 0,3 s 12*Ith 48.000A

BFG02 AB001 G5 Ith I1 t1 I2 t2 I3

Setting

Value BJF BJJ

4000/4000 4000A 4000A 1*Ith 4000A INT 5,5 s 4*Ith 16.000A 0,3 s 0,3 s 12*Ith 48,000A

Setting

Value

BTS51 +24v

~ =

~ BTS52 -24V = BTS61 +24V

~ =

~ BTS62 -24V =

~ BTL50 250V =

1600/1600 1600A 1600A 1*Ith 1600A INT 5,5 s 6*Ith 9.600A 0,3 s 0,3 s 12*Ith 19.200A

BFG04 Setting Value AB001 LG 1250 R800/800 Ith 800A 1.600A 800A I1 1*Ith 800A t1 INT 20 s I2 10*Ith 96.000A 8.000A t2 0,45 s 0,45 s I3 10kA 10kA

BFK04AB001

BJK

BJL

BFK04AG001

BJM

BTG52 BTG51

BTG61
~ =

BTL30 250V BTG62 BTA50

BJG

BMX

BLH02AC001

BTA30 DIESEL

BUM01AE001

BUL01AB001

BUM01AB001

G
MAX BMK

BUL01AE001

BFE03AE001

BUL +_24V

BUM +_24V

BTA50 250V DC

BLH MAX
BMF05 AB001 BMF05 AC001

BMF

BMF06AB001

BME

BMF03AC001-F01

BMF04AD001

BMF04AF001

BTL10 220V

~ =

~ =

BTL20 220V BTL40 250V


~ =

BTA20 BTA10 BTA40

BUA01AB001

BUA01AG001

BUB01AG001

BUB01AB001

BME01AB001

BME02AB001

BMK02AB001

BUB220V DC

BTG12

BUA 250V DC

BUA01AL001

BUB01AL001

BTS21+24V

~ =

BTS22-24V
=

BTS11+24V

~ =

BTS12-24V
=

BUD 250V DC

= ~

BRU10

BRU20

BTG21
~

BTG22

BTG11

BTG12
~

BUD01AB001

BFE03AE001

BUC 250V DC

BFE03AE001

BFE03AE001

BTS41+24V BTS31+24V
~ = =

BFK03AB001

BHG01 AB001 G2 Ith I1 t1 I2 t2 I3

Setting
1250/760 1250A 0.6*Ith

Value
1250A 2500A

BFE06 AE001 Setting Value LN800 R630/630 630A It 630A 3.150A Im Min

BFE01 AE001 Setting Value LN800 R630/630 630A It 630A 3.150A Im Min

BFE11 AE001 Setting Value LN500 R500/500 500A It 500A 5.000A Im Max

BFE06AG001

BHF01 AE001 Setting Value LN800 R630/630 630A It 630A 3.150A Im Min

BHF03 AE001 Setting Value LN800 R630/630 630A It 630A 3.150A Im Min

BFE09 AE001 Setting Value LN500 R500/450 450A It 450A 2.500A Im Min

BFE03 AE001 Setting Value LN500 R400/400 400A It 400A 4.000A Im Max

BFE10 AE001 Setting Value LN500 R500/500 450A It 450A 2.500A Im Min

BFE07 Setting Value AB001 LG 1250 R800/800 Ith 800A 1.600A 800A I1 1*Ith 800A t1 INT 20 s I2 10*Ith 96.000A 8.000A t2 0,3 s 0,3 s I3 10kA 10kA

BFE08 Setting Value AB001 LG 1250 R800/800 Ith 800A 1.600A 800A I1 1*Ith 800A t1 Max 30 s I2 10*Ith 96.000A 8.000A t2 0,3 s 0,3 s I3 10kA 10kA

BFF06 Setting Value AB001 LG 1250 R800/800 Ith 800A 1.600A 800A I1 1*Ith 800A t1 Max 30 s I2 10*Ith 96.000A 8000A t2 0,45 s 0,45 s I3 10kA 10kA

BFF07 Setting Value AB001 LG 1250 R800/800 Ith 800A 1.600A 800A I1 1*Ith 800A t1 INT 20 s I2 10*Ith 96.000A 8000A t2 0,45 s 0,45 s I3 10kA 10kA

BFF08AC001 -F01

MAX SLM03 -/400, DIN02 -/250

BFF08AE001-F01

BFE06AB001

Setting
BFF04 Setting Value AE001 LN500 R500/500 450A It 450A 2.500A Im Min BFF05 Setting Value AE001 LN500 R500/500 450A It 450A 2.500A Im Min BFF03 Setting Value AE001 LN500 R500/500 500A It 500A 5.000A Im Max BFF02 Setting Value AE001 LN500 R500/500 500A It 500A 5.000A Im Max Ith I1 t1 I2 t2 I3

Value
1.600A 96.000A

Value
1.600A

BFK
96.000A BFK05 Setting Value AB001 LN500 R500/500 400A It 400A 4.000A Im Max

MAX SLM03 -/500 ,DIN02 -/250

BFH10

BFH20 I3

BUH01AF001

BTS32-24V

~ =

BRA01AB001

BUG01AF001

BUG01AB001

BUH01AB001

BRB01AB001

BTS42 -24V
=

BTG32 BTG31 BTG41 BTG42

BUH+_24V

BUC+_24V

BRB01AD002

BUJ01AF001

BRA01AD001

BUJ01AB001

BUk01AF001

BRA01AD002

BRB01AD001

BUJ +_24V

BUK +_24V

BRA01AH001

BRA01AF001

BRB01AH001

BRA

MAX

BRB

BRA01AM001

BRA01AN001

BRA01AM002

BRA01AL001

BRB01AF001

BRK01AB001

BRD

BRC01

BRC05 BRK

BRK01AM001

BRM

BRK01AB002

BUK01AB001

Medium level
AEB01
BAT01 457,5MVA ex=12,5% 162 kV AEB02

AEB03
YNd11

YNd11

BCt01 50 MVA ex=14,5% BBT01 50 MVA Ex=12,5% BBA09 FRA BBT Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum Setting 3150 Value 3150 BBA10 FRA BCA Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum Setting 3150 Value 3150 L YKKEGJRD BCA08 BBA Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum Setting 3150 Value 3150 BCA09 FRA BCT10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum Setting 3150 Value 3150

DISP (Block 4)

BAA
MKC 50
G

YY0 MKA10 528MVA

CUG

2750/1 2,55 0,200 3,76 0,04 Yes 1+8 40

2750/1 8032,5 0,200 11844 0,04 Yes 1+8 40

2750/1 2,55 0,04 3,55 0,140 No 8 40

2750/1 8032,5 0,04 11182,5 0,140 No 8 40

indfdning 2750/1 2,55 0,20 3,67 0,04 No 8 40

indfdning 2750/1 8032,5 0,20 11560,5 0,04 No 8 40

BCA 10,5 kV
BBA12 HNC50 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum M BBA22 DISP Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum BCA01 BHT01 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

BBA 10,5 kV
BBA01 LCB10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum M Setting 630 34,6

Value 630 34,6

Dyn5

Dyn5

T/M 60/1 0.69 25 3,50 0,04 Yes 6 27 No Yes 220

T/M 60/1 23,874 25 121,11 0,04 Yes 6 27 No Yes 220 M

BBA02 LCB20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 630 34,6

Value 630 34,6

Dyn5

T/M 60/1 0.69 25 3,50 0,04 Yes 6 27 No Yes 220

T/M 60/1 23,874 25 121,11 0,04 Yes 6 27 No Yes 220 M

BBA03 LCB30 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 630 34,6

Value 630 34,6

T/M 60/1 0.69 25 3,50 0,04 Yes 6 27 No Yes 220

T/M 60/1 23,874 25 121,11 0,04 Yes 6 27 No Yes 220 M

BBA04 HFC10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1850 119 656 3 5 M 125/1 1,14 10 7,05 0,04 Yes 7 27 Yes Yes Yes 252

Value 1850 119 656 3 5 M 125/1 135,66 10 838,95 0,04 Yes 7 27 Yes Yes Yes 252 M

BBA05 HFC20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1850 119 656 3 5 M 125/1 1,14 10 7,05 0,04 Yes 7 27 Yes Yes Yes 252

Value 1850 119 656 3 5 M 125/1 135,66 10 838,95 0,04 Yes 7 27 Yes Yes Yes 252 M

BBA06 HFC30 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1850 119 656 3 5 M 125/1 1,14 10 7,05 0,04 Yes 7 27 Yes Yes Yes 252

Value 1850 119 656 3 5 M 125/1 135,66 10 838,95 0,04 Yes 7 27 Yes Yes Yes 252

YNyn5

BBA07 LAC10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting Value 8600/11000 8600/11000 625 625

YNyn5

T/M 700/1 1,07 10 3,89 0,04 Yes 1+8 40 No Yes 252

T/M 700/1 668,75 10 2431,25 0,04 Yes 1+8 40 No Yes 252 M

BBA08 LAC20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting Value 8600/11000 8600/11000 625 625

T/M 700/1 1,07 10 3,89 0,04 Yes 8 40 No Yes 252

T/M 700/1 668,75 10 2431,25 0,04 Yes 8 40 No Yes 252

BBA11 BBB Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 630

Value 630

400/1 1,55 15 1,80 0,14 No 8 43 No Yes 220

400/1 976,5 15 1134 0,14 No 6+8 43 No Yes 220

Setting 4200 270 1350 12 12 M 300/1 1,08 18 6,05 0,04 Yes 10 7 27 Yes Yes Yes 252

Value 4200 270 1350 12 12 M 300/1 291,6 18 1633,5 0,04 Yes 10 7 27 Yes Yes Yes 252 M

BBA13 HNC60 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 4200 270 1350 12 12 M 300/1 1,08 18 6,05 0,04 Yes 10 7 27 Yes Yes Yes 252

Value 4200 270 1350 12 12 M 300/1 291,6 18 1633,5 0,04 Yes 10 7 27 Yes Yes Yes 252 M

BBA14 PAC10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1450 104 520 1,8 10 M 125/1 1,00 10 5,60 0,04 Yes 7 27 Yes Yes Yes 252

Value 1450 104 520 1,8 10 M 125/1 520 10 2912 0,04 Yes 7 27 Yes Yes Yes 252 M

BBA15 PAC20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1450 104 520 1,8 10 M 125/1 1,00 10 5,60 0,04 Yes 7 27 Yes Yes Yes 252

Value 1450 104 520 1,8 10 M 125/1 520 10 2912 0,04 Yes 7 27 Yes Yes Yes 252 M

BBA16 HLB30 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1450 93,4 466 6 14 M 100/1 1,17 100 6,26 0,04 Yes 6 7 27 Yes Yes Yes 252

Value 1450 93,4 466 6 14 M 100/1 109,278 100 584,684 0,04 Yes 6 7 27 Yes Yes Yes 252 M

BBA17 HLB40 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1450 93,4 466 6 14 M 100/1 1,17 100 6,26 0,04 Yes 6 7 27 Yes Yes Yes 252

Value 1450 93,4 466 6 14 M 100/1 109,278 100 584,684 0,04 Yes 6 7 27 Yes Yes Yes 252 M

BBA18 HFE41 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1000 64,6 323 19 20 M 100/1 0,77 25 4,80 0,04 Yes 10 7 27 Yes Yes Yes 252

Value 1000 64,6 323 19 20 M 100/1 49,742 25 310,08 0,04 Yes 10 7 27 Yes Yes Yes 252 M

BBA19 HFE42 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1000 64,6 323 19 20 M 100/1 0,77 25 4,80 0,04 Yes 10 7 27 Yes Yes Yes 252

Value 1000 64,6 323 19 20 M 100/1 49,742 25 310,08 0,04 Yes 10 7 27 Yes Yes Yes 252

Dyn5

BBA20 BFT01 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 2500 137,5

Value 2500 137,5

Dyn5

T 150/1 1,10 100 3,67 0,04 Yes 6 27 No Yes 220

T 150/1 151,25 100 504,625 0,04 Yes 6 27 No Yes 220

BBA21 BFT02 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) Omdr.vagt200 0/Min(sec) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 2500 137,5

Value 2500 137,5

Setting 4085 124,1

Value 4085 124,1

Dyn5

Setting 1600 88

Value 1600 88

Dyn5

T 150/1 1,10 100 3,67 0,04 Yes 6 27 No Yes 220

T 150/1 151,25 100 504,625 0,04 Yes 6 27 No Yes 220

(T) 150/1 0,99 10 3,97 0,04 Yes 6 27 No Yes 220

(T) 150/1 122,859 10 492,677 0,04 Yes 6 27 No Yes 220

T 100/1 1,06 100 3,96 0,04 Yes 6 27 No Yes 220

T 100/1 93,28 100 348,48 0,04 Yes 6 27 No Yes 220

BCA02 BHT02 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1600 88

Value 1600 88

T 100/1 1,06 100 3,96 0,04 Yes 6 27 No Yes 220

T 100/1 93,28 100 348,48 0,04 Yes 6 27 No Yes 220

BCA03 EAA10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1600 88

Value 1600 88

T 100/1 security 160A 7 Yes Yes Yes 252

T 100/1 security 160A 7 Yes Yes Yes 252

BCA04 EAA20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1600 88

Value 1600 88

T 100/1 security 160A 7 Yes Yes Yes 252

T 100/1 security 160A 7 Yes Yes Yes 252

BCA05 BHT04/05 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 4000 220

Value 4000 220

Dyn5

T 250/1 1,8 1 3,96 0,04 Yes 6 26 No Yes 220

T 250/1 396 1 871,2 0,04 Yes 6 26 No Yes 220

BCA06 BHT03 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1600 88

Value 1600 88

T 100/1 1,25 100 3,96 0,04 Yes 6 27 No Yes 220

T 100/1 110 100 871,2 0,04 Yes 6 27 No Yes 220

BCA07 QHA01 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 30000 1650

Value 30000 1650

Verme 1800/1 1,01 10 1,83 0,04 No 7 42 No Yes Yes 252

Verme 1800/1 1666,5 100 3019,5 0,04 No 7 42 No Yes Yes 252

BCA10 BCC Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 835

Value 835

800/1 0,97 10 4,40 0,14 No 6 11 No Yes 220

800/1 809,95 10 3674 0,14 No 6 11 No Yes 220 BCT02 8MVA Ex=6%

St . ESTRUPVEJ BCT03 14 MVA AFB01 GV001Q01 64 kV

0,4kV 0,4kV
1850 kW 119 A 1850 kW 119 A 550 kW 34,6 A 550 kW 34,6 A 8600 kW 625 A 1850 kW 119 A 8600 kW 625 A 4200 kW 270 A 4200 kW 270 A 1450 kW 104 A 1450 kW 93,4 A 1450 kW 93,4 A 1450 kW 104 A 1000 kW 64,6 A 550 kW 34,6 A 1000 kW 64,6 A

0,4kV
1600 kW 88A

0,4kV
1600 kW 88 A 1600 kW 88 A

0,66kV
30000 kW 1650 A

KUlPADS

BCB
BCC14 TRF 23 B1 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

BCC 10,5kV
BCC01 NDC01/11 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum BCC02 NDC02/12 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum BCC05 NDC03/13 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

BCC04 B2 BCT02 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

2500 kVA 137,5 A

LCB10 AP001 -M01 HKDNENSAT.PUM 10

LCB20 AP001 -M01 HKDNENSAT.PUM 20

2500 kVA 137,5 A

1600 kW 88 A

1300 kW 88 A

Setting 8000 440

Value 8000 440

Yd11

Yd11 AFB 60 kV ANLCG

PAC10 AP001 -M01 HOVEDK\LE PUMPE 10

PAC20 AP001 -M01 HOVEDK\LE PUMPE 20

HFE42 AN001 -M01 PA-BLESER 42 MOTOR

HFE41 AN001 -M01 PA-BLESER 41 MOTOR

HLB30 AN001 -M01 SABLESER 30

HLB40 AN001 -M01 SABLESER 40

T 500/1 1,06 10 3,52 0,04 Yes 6 27 No

T 500/1 466,4 10 1548,8 0,04 Yes 6 27 No

HFC10 AJ001 -M01 KM10 HDVEDMOTOR

HFC20 AJ001 -M01 KM20 HDVEDMOTOR

LCB30 AP001 -M01 HKDNENSAT.PUM 30

HFC30 AJ001 -M01 KM30 HDVEDMOTOR

HNC50 AN001 -M01 SUGER 50 MOTOR

HNC60 AN001 -M01 SUGER 60 MOTOR

BHT01 LYS/KRAFT 1 BL 3

BHT02 LYS/KRAFT 2 BL 3

LAC20 AP001 -M01 F\DEP.20 MOTOR

EAA20 KULKRAN 1

BHT03 EL-OVERHEDER

LAC10 AP001 -M01 F\DEP.10 MOTOR

BFT01 LOKAL TRANSFORMER 1

BFT02 LOKAL TRANSFORMER 2

EAA20 KULKRAN 2

QHA01 AH001 El -KEDEL

BBB 10,5 kV
BBB01 HTF10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum M
560 kW 36,8 A

Setting 560 36,8 186 2 10 M 40/1 1,10 10 6,25 0,04 Yes 7 27 Yes Yes Yes 252

Value 560 36,8 186 2 10 M 40/1 371,68 10 6,25 0,04 Yes 7 27 Yes Yes Yes 252 M
560 kW 36,8 A

BBB02 HTF20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 560 36,8 186 2 10 M 40/1 1,10 10 6,25 0,04 Yes 7 27 Yes Yes Yes 252

Value 560 36,8 186 2 10 M 40/1 371,68 10 6,25 0,04 Yes 7 27 Yes Yes Yes 252 M
600 kW 39,3 A

BBB03 HTF40 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 600 39,3 200 2 8 M 40/1 1,18 10 6,70 0,04 Yes 7 27 Yes Yes Yes 252

Value 600 39,3 200 2 8 M 40/1 46,374 10 263,31 0,04 Yes 7 27 Yes Yes Yes 252 M

BBB04 HTF50 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 600 39,3 200 2 8 M 40/1 1,18 10 6,70 0,04 Yes 7 27 Yes Yes Yes 252

Value 600 39,3 200 2 8 M 40/1 46,374 10 263,31 0,04 Yes 7 27 Yes Yes Yes 252

Dyn5

BBB05 BFT03 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 1250 69

Value 1250 69

Dyn5

T 100/1 0,83 10 3,11 0,04 Yes 6 27 No Yes 220

T 100/1 57,27 10 214,59 0,04 Yes 6 27 No Yes 220

BBB07 BFT04 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 2000 110

Value 2000 110

T 12571 1,06 10 3,96 0,04 Yes 6 27 No Yes 220

T 12571 116,6 10 435,6 0,04 Yes 6 27 No Yes 220 M

BBB08 HTG10 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 400 26 130 13 14 M 40/1 0,78 19 4,30 0,04 Yes 7 27 Yes Yes Yes 252

Value 400 26 130 13 14 M 40/1 20,28 10 111,8 0,04 Yes 7 27 Yes Yes Yes 252 M

BBB09 HTG20 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 2000 110

Value 2000 110

Dyn5

Setting 1600 88

Value 1600 88

Dyn5

Setting 1600 88

Value 1600 88

Dyn5

Setting 1600 88

Value 1600 88

Dyn5

Setting 400 26 130 13 14 M 40/1 0,78 19 4,30 0,04 Yes 7 27 Yes Yes Yes 252

Value 400 26 130 13 14 M 40/1 20,28 10 111,8 0,04 Yes 7 27 Yes Yes Yes 252

D0ynyn5

D0ynyn5

BHH01 AB001 G2 Ith I1 t1 I2 t2 I3

Setting
1250/600 800A 0.75*Ith 8*Ith 0,1 s 10kA

Value
800A 600A 6.400A 0,1 s 10kA BHA01 AB001 G2 Ith I1 t1 I2 t2 I3

Setting

Value

0,45 6*Ith

2000/1400 2000A 2000A 0,7*Ith 1400A INT 5,5 s 4*Ith 16.000A s 0,45 s 12.000A

BHB01 AB001 G2 Ith I1 t1 I2 t2 I3

Setting

Value

1600/1400 1600A 1600A 0,9*Ith 1440A INT 5,5 s 6*Ith 9.600A 0,15 s 0,15 s 9*Ith 14.400A

BHJ01 AB001 G2 Ith I1 t1 I2 t2 I3

Setting
1250/600 800A 0,7*Ith 8*Ith 0,1 s 12*Ith

Value
800A 760A 6400A 0,1 s 9,600A

T 100/1 1,32 10 4,40 0,04 Yes 6 27 No Yes 220

T 100/1 145,2 10 484 0,04 Yes 6 27 No Yes 220

T/M 100/1 1,06 10 3,96 0,04 Yes 6 27 No Yes 220

T/M 100/1 93,28 10 348,48 0,04 Yes 6 27 No Yes 220

T/M 100/1 1,06 10 4,50 0,04 Yes 6 27 No Yes 220

T/M 100/1 93,28 10 396 0,04 Yes 6 27 No Yes 220

T/M 100/1 1,06 10 3,96 0,04 Yes 6 27 No Yes 220

T/M 100/1 93,28 10 348,48 0,04 Yes 6 27 No Yes 220

BCC06 NDC31/32 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 950 52

Value 950 52

Dyn5

T/M 60/1 1,04 10 3,90 0,04 Yes 6 27 No Yes 220

T/M 60/1 54,08 10 202,8 0,04 Yes 6 27 No Yes 220

BCC07 BFT06 Power kW/kVA Normal current (A) Start current (A) Starting time (sec) Shortcircuit time (sec) Transformer/Motor Current Transformer Overcurrent I> Overcurrent time T> Shortcircuitcurrent I>> Shortcircuit time T>> Doubling V.ST.(I>>) SGR relay=(1) SG1 checksum Earth fault isolation I>= 2% / 5 Sec I>>=5% / 0.5 Sec SG1 checksum

Setting 400 22

Value 400 22

T 40/1 0,66 10 2,20 0,04 Yes 6 59 No Yes 220

T 40/1 14,52 10 48,4 0,04 Yes 6 59 No Yes 220

0,4kV MAX OESA63 -/63, S273 BHH U16 -/16, SLM01 -/160
2000 kVA 110 A

BHA

0,66kV

BHB

0,4kV

0,66kV BHJ MAX SLM01 -/160, S273 U16 -/ 16, DIN01 -/160, OESA63 -/16
2000 kVA 110 A

0,4kV

600 kW 39,3 A

0,4kV
1250 kVA 69 A

0,4kV
2000 kVA 110 A 400 kW 26 A 400 kW 26 A

BHA04 AD001 Setting Value LN500 R320/250 250A It 250A 3.200A Im Max

BHB02 AH001 Setting Value LN500 R320/250 250A It 250A 3.200A Im Max

BHT04 LOKAL TRANSFORMER 1

BHT05 LOKAL TRANSFORMER 2

750 kW

HTF10 AP001 -M01 REC, PUMPE 10

520 kW

750 kW

520 kW

750 kW

HTG10 AN001 -M01 OX.BLESER 10

HTG20 AN001 -M01 OX.BLESER 20

HTF20 AP001 -M01 REC, PUMPE 20

HTF40 AP001 -M01 REC, PUMPE 40

HTF50 AP001 -M01 REC, PUMPE 50

520 kW

370 kW

BFT03 EL -FILTER

BFT04 LOKAL TRANSFORMER 1

370 kW

NDC01 AP001 -M01 F JV.PUMPE 01 MOTOR

NDC11 AP001 -M01 F JV.PUMPE 11 MOTOR

NDC02 AP001 -M01 F JV.PUMPE 02 MOTOR

NDC12 AP001 -M01 F JV.PUMPE 12 MOTOR

NDC03 AP001 -M01 F JV.PUMPE 03 MOTOR

NDC13 AP001 -M01 F JV.PUMPE 13 MOTOR

NDC31 AP001 -M01 F JV.PUMPE 31 MOTOR

NDC32 AP001 -M01 F JV.PUMPE 32 MOTOR

BHT06 LOKAL TRANSFORMER 1

400 kVA 22 A

Min phase to ground short circuit current condition

Max three phase short circuit current condition

Min phase to ground short circuit condition

Automatic change over condition

No automatic changeover but with sub-distribution