Check that there is electric power supply.

Check the pressure gauge of the FM 200 cylinder Perform a general inspection of the system to verify that nothing hinders its operation. Check that discharge lines and components have not suffered any mechanical damage. Check the integrity of the electric line Disconnect the Actuated solenoid valves of the FM 200 and count how many turn /teeth Perform Function test for the smoke detectors simulate the FM 200 Solenoid valve Make sure that the solenoid valves is actuated by checking the solenoid PIN movement Check the panel for the coming alarm signal and audible sound (Bell and outdoor Horn) Normalize the loop and acknowledge the alarm Perform Function test for the manual release pushbuttons Make sure that the solenoid valves is actuated by checking the solenoid PIN movement Check the panel for the coming alarm signal and audible sound (Bell and outdoor Horn) Normalize the loop and acknowledge the alarm Perform function test for the manual lever in the solenoid valve it self Make sure that the solenoid valves is actuated by checking the solenoid PIN movement Return the lever back and normalize all loops and make sure that the solenoid is de- energized and the PIN is not released Install the solenoid valve carefully with the number the same dismantled turn count / Thread and carefully tight the solenoid (Do not over tight over tight will release the FM200) Perform a general inspection of the system to verify that nothing hinders its operation.

House keeping