Sei sulla pagina 1di 43

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

Tabla de contenido 1 2 3 INTRODUCCION ................................................................................................... 5 OBJETIVO ............................................................................................................. 5 ASPECTOS GENERALES .................................................................................... 6 3.1 4 5 Antecedentes.................................................................................................. 6

Ubicacin Geogrfica............................................................................................. 6 CARACTERISTICAS DE LA LOCALIDAD DE LIRCAY ......................................... 7 5.1 5.2 Ubicacin Geogrfica ..................................................................................... 7 Poblacin ........................................................................................................ 7

Cuadro 1 ..................................................................................................................... 8 5.3 Servicios Pblicos........................................................................................... 8 Energa Elctrica .......................................................................................... 8 Telecomunicaciones ..................................................................................... 8 Transporte .................................................................................................... 9

5.3.1 5.3.2 5.3.3 5.4 6

Vas De Acceso .............................................................................................. 9

DESCRIPCION DEL SISTEMA EXISTENTE ......................................................... 9 6.1 Agua ............................................................................................................... 9

Cuadro 2 ..................................................................................................................... 10 Cuadro 3 ..................................................................................................................... 10 Cuadro 4 ..................................................................................................................... 11 Cuadro 5 ..................................................................................................................... 11 Cuadro 6 ..................................................................................................................... 12 6.2 Red De Alcantarillado .................................................................................. 12 Red de recoleccin ..................................................................................... 13

6.2.1

Cuadro 7 ..................................................................................................................... 13 Cuadro 8 ..................................................................................................................... 13 7 DESARROLLO DEL ESTUDIO ............................................................................ 14 7.1 Parmetros de diseo................................................................................... 14 Pgina 1

HUANCAVELICA-ANGARAES-LIRCAY

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

7.2 7.3

rea de Influencia ......................................................................................... 15 Poblacin Actual ........................................................................................... 16

Cuadro 9 ..................................................................................................................... 16 Cuadro 10 ................................................................................................................... 16 7.4 7.5 7.6 7.7 7.8 7.9 7.10 8 Poblacin de Diseo ..................................................................................... 16 Horizonte del Diseo .................................................................................... 16 Poblacin Servida ......................................................................................... 17 Dotacin ....................................................................................................... 17 Consumo por conexin ................................................................................. 17 Demanda Actual Y Futura De Agua .............................................................. 17 Demanda Actual Y Futura De Alcantarillado ................................................. 19

PARAMETROS ESPECIFICOS DE AGUA POTABLE ........................................ 20 8.1 8.2 Coeficiente De Variacin De Consumo ......................................................... 20 Lneas De Aduccin Y Redes De Distribucin .............................................. 20

TABLA 1.................................................................................................................. 21 8.3 8.4 8.5 8.6 8.7 8.8 9 Pendientes mnimas ..................................................................................... 21 Vlvula de aire o ventosa.............................................................................. 21 Velocidad del Conducto ................................................................................ 22 Zonas de presin .......................................................................................... 22 Profundidad mnima de instalacin ............................................................... 22 Anclajes para accesorios de tuberas ........................................................... 23

PARAMETRO ESPECIFICOS DE ALCANTARILLADO ....................................... 23 9.1 9.2 9.3 9.4 Coeficiente De Retorno (C) ........................................................................... 23 Cuantificacin De Caudales De Aporte Domestico ....................................... 23 Aporte De Aguas Industriales, Comerciales Y Pblicas ................................ 23 Criterio De Diseo ........................................................................................ 24 Formulas para diseo de redes de alcantarillado ........................................ 24 Criterio de velocidad mnima ...................................................................... 24 Criterio de la Tensin Tractiva .................................................................... 24 Pgina 2

9.4.1 9.4.2 9.4.3

HUANCAVELICA-ANGARAES-LIRCAY

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

9.4.4 9.4.5 9.4.6 9.4.7 9.4.8 9.4.9 9.4.10 9.4.11 10 10.1

Criterio de la Tensin Tractiva .................................................................... 25 Coeficiente de rugosidad ............................................................................ 25 Tensin tractiva mnima .............................................................................. 26 Dimetro mnimo ........................................................................................ 26 Tirante mximo ........................................................................................... 26 Profundidad de instalacin.......................................................................... 26 Ubicacin de elementos de inspeccin ....................................................... 27 Material de la tubera .................................................................................. 27

DESCRIPCION DEL SISTEMA PROYECTADO .............................................. 28 Lneas de Aduccin y redes de Distribucin ................................................. 28 Lneas de Aduccin .................................................................................... 28 Red de distribucin ..................................................................................... 28

10.1.1 10.1.2

10.1.2.1 Evaluacin .................................................................................................. 30 10.1.2.2 Accesorios .................................................................................................. 30 10.1.2.3 Vlvulas ...................................................................................................... 31 10.1.2.4 Grifos contra incendio ................................................................................. 31 10.2 10.3 Vlvula de aire triple efecto........................................................................... 32 Estaciones reductoras de presin ................................................................. 32

Cuadro 11 ................................................................................................................... 32 10.4 11 11.1 Conexiones domiciliarias de agua ................................................................ 32 DESCRIPCION DEL SISTEMA PROYECTADO DE ALCANTARILLADO ....... 35 Sistema Proyectado De Alcantarillado .......................................................... 35

Tabla 2 ....................................................................................................................... 35 11.2 11.3 Redes Secundarias ...................................................................................... 36 Colectores Principales ................................................................................. 37 Colectores Av. Fernndez ......................................................................... 37 Colectores Jr. 6 de agosto ......................................................................... 37

11.3.1 11.3.2 11.4

Interceptor .................................................................................................... 37 Interceptor 01 Rio Opomayo ....................................................................... 37 Pgina 3

11.4.1

HUANCAVELICA-ANGARAES-LIRCAY

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

11.4.2 11.5 11.6 11.7

Interceptor 02 Rio Sicra .............................................................................. 37

Emisor .......................................................................................................... 38 Conexiones domiciliarias .............................................................................. 38 OBRAS ESPECIALES .................................................................................. 39 Cruce Adosado a Puente ............................................................................ 39 Cruce Areo ............................................................................................... 40

11.7.1 11.7.2 12 12.1 12.2 12.3 12.4 13 13.1 13.2 13.3 14

VIRGEN DEL CARMEN ................................................................................... 40 Poblacin de diseo ..................................................................................... 40 Caudal de diseo .......................................................................................... 40 Red de Alcantarillado ................................................................................. 41

Conexiones domiciliarias (Virgen del Carmen) ............................................. 41 COSTO DEL PROYECTO................................................................................ 42 Costo del proyecto por componente ............................................................. 42 Costo directo total ......................................................................................... 43 Costo total .................................................................................................... 43 CONCLUSIONES Y RECOMENDACIONES .................................................... 43

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 4

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESAGE DE LA LOCALIDAD DE LIRCAY


1 INTRODUCCION El Gobierno Regional de Huancavelica, ha previsto el desarrollo del presente Expediente Tcnico y su ejecucin de obra, a fin de de brindar la cobertura del servicio de agua y alcantarillado, los mismos que permitirn mejorar las

condiciones de vida, salud y socioeconmicas de la poblacin. En la localidad de Lircay cuenta con el suministro de agua potable las 24 horas del da con una cobertura de 92.75%, las viviendas que cuentan con el servicio intermitentemente practican el almacenamiento ya que solo les llega agua 6.00 horas/da y por 7 das a la semana. El nuevo sistema de desage a implementar, est conformado por las redes de recoleccin de desage que descargan en los tanques spticos y planta de tratamiento de aguas residuales - Del Programa Agua Para Todos y El Gobierno

Regional de Huancavelica- para luego ser conducido por el emisor hasta el rio.

OBJETIVO El objetivo central del proyecto consiste en disminuir el alto porcentaje de enfermedades infecciosas intestinales en la poblacin de la Localidad de Lircay. Mejorar la calidad del servicio de agua existente, mediante la renovacin de las tubera de AC, FF y plomo y un adecuado equilibrio hdrico del sistema de redes de distribucin, aumento de las horas de servicio de agua. Renovacin de los colectores y conexiones domiciliarias de concreto simple normalizado y construccin de un adecuado sistema de recoleccin. Implementar un programa de educacin sanitaria, para sensibilizar a la poblacin beneficiada en aspectos como: valorar el agua potable, el uso adecuado del nuevo sistema de evacuacin de desages y adecuadas prcticas de higiene. Mejorar la gestin de los servicios a fin de dar sostenibilidad al proyecto

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 5

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

3 3.1

ASPECTOS GENERALES Antecedentes Las actividades econmicas de la poblacin de Lircay, se basa en actividades primarias, como agricultura de pequeas parcelas, minera y comercio en pequea escala, que se traduce en una poblacin con alto ndice de pobreza y extrema pobreza, que obliga necesariamente mejorar e incrementar los servicios de agua y saneamiento, a travs de parmetros de Calidad, Continuidad, Cobertura, Costos, recoleccin y tratamiento de sus desages para garantizar la salud de la poblacin y mejorar los niveles de vida.

Ubicacin Geogrfica La va principal del distrito la constituye la carretera afirmada HuancayoLircay Julcamarca Ayacucho (345 km.), cuenta adems con infraestructura vial consistente en trochas carrozables que le permiten una articulacin interdistrital, entre las que se mencionan: Por el suroeste Lircay Huancavelica Lircay Huachocolpa Santa Ins Pisco La carretera Lircay Ruminachaca (Va Libertadores)

El acceso desde la ciudad de Lima, es a travs de la Carretera Central, el viaje dura aproximadamente 18 horas. Cuenta con servicios de taxis y de mnibus.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 6

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

5 5.1

CARACTERISTICAS DE LA LOCALIDAD DE LIRCAY Ubicacin Geogrfica La localidad de Lircay se encuentra ubicada en: Regin: Huancavelica Departamento: Huancavelica Provincia: Angaraes Distrito: Lircay

5.2

Poblacin Segn las proyecciones basadas en los censos poblacionales realizados para el distrito de Lircay, se tomo como ao base el 2008 el cual tiene una poblacin de 6,648 habitantes (ver clculo poblacional en la Memoria de Clculo) y una densidad poblacional de 3.89 habitantes por vivienda para el ao 2008.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 7

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY
Cuadro 1

Ao 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029

Horizonte 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Poblacin (hab) 6,648 6,734 6,822 6,910 7,000 7,091 7,183 7,276 7,371 7,466 7,563 7,662 7,761 7,862 7,964 8,067 8,172 8,278 8,385 8,494 8,604 8,716

5.3

Servicios Pblicos El distrito de Lircay, cuenta con insuficiente infraestructura de agua potable y alcantarillado. Cuenta con servicio de telefona, energa elctrica, servicios de transporte, centro mdico, infraestructura educativa hasta el nivel superior y una agencia del banco de la nacin.

5.3.1

Energa Elctrica El 97.1% de las viviendas de la localidad de Lircay cuentan con energa elctrica abastecidos por la empresa Electrocentro S.A. y el 2.9 % no cuenta con el servicio.

5.3.2

Telecomunicaciones El rea del proyecto existe seal de telfono fijo y mvil (Claro y Movistar), en cuanto a locales de telefona, se puede observar servicios de telfono pblico, privado, locutorios pblicos, cabinas de Internet.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 8

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

5.3.3

Transporte La poblacin de la localidad de Lircay se moviliza en autos y motocarro

5.4

Vas De Acceso La va principal del distrito la constituye la carretera afirmada Huancayo-LircayJulcamarca-Ayacucho (345 Km.), cuenta adems con infraestructura vial consistente en trochas carrozables que le permiten una articulacin intradistrital, entre las que se mencionan: Por el suroeste Lircay Huancavelica Lircay Huachocolpa Santa Ins Pisco La carretera Lircay Ruminachaca (Va Libertadores)

El acceso desde la ciudad de Lima, es a travs de la Carretera Central, el viaje dura aproximadamente 18 horas. Cuenta con servicios de taxis y de mnibus.

6 6.1

DESCRIPCION DEL SISTEMA EXISTENTE Agua La localidad de Lircay en cuenta actualmente con un sistema completo de agua, cuyos componentes: Captaciones Lnea de conduccin Planta de tratamiento Reservorios Red de distribucin Conexiones domiciliarias captacin, lnea de conduccin y los

Algunas de estas estructuras: como

reservorios estn siendo mejoradas por el Programa Agua Para Todos y El Gobierno Regional de Huancavelica.

En el rea del proyecto las redes de distribucin estn conformadas por tubera de AC, PVC y FF en mayor porcentaje predomina el AC cuyos dimetros varan entre 3 a 6 pulgadas. La longitud total de las tuberas es 10874.81 m. En el Cuadro2 se presenta el metrado, el dimetro de la tubera y el material del mismo

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 9

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

Cuadro 2

Longitud (m) Dimetro (pulg.) material 4691.41 991.44 254.19 745.48 1371.2 635.89 1668.52 516.68 10874.81 4 AC 6 AC 3 AC 6 FF 2 PVC 3 PVC 4 PVC 6 PVC

La antigedad de la red de distribucin es de aproximadamente 40 aos, segn la Informacin proporcionada por SEMSA, su estado de conservacin es deficiente, debido a la constante rotura de tubera que se presenta durante el ao, perjudicando la continuidad y calidad del servicio de agua potable. En el cuadro3, 4 y 5 se muestran las calles con el material de tubera.

Cuadro 3

CALLE/JR.AVENIDA D 6" AC Longitud(m)

JR. TUPAC AMARU AV. CENTENARIO AV. R FERNANDEZ JR. PUNO CALLE S/N LONGITUD TOTAL

89.9 473.44 135.02 159.71 133.37 991.44

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 10

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

Cuadro 4

CALLE/JR.AVENIDA

DE 4" AC

Longitud(m)

JR. BUENOS AIRES JR. PROGRESO JR. SIMON BOLIVAR JR. OLIMPICO JR. LIBERTAD JR. MARISCAL SUCRE JR. CAHUIDE AV. CENTENARIO JR. LIMA JR. PUNO JR. 27 NOVIEMBRE JR. 6 DE AGOSTO JR. 9 DE DICIEMBRE AV. LA ESMERALDA JR. MARAVILLA CALLE S/N JR. FERNANDEZ JR. AYACUCHO JR. ATAHUALPA TOTAL

178.82 178.64 213.88 630.06 476.88 482.73 474.12 182.19 392.05 157.32 109.56 120.37 119.29 230.07 294.32 102.55 67.67 137.07 143.82 4691.41

Cuadro 5

CALLE/JR.AVENIDA DE 3" AC

Longitud(m)

JR. BOLOGNESI CALLE S/N JR. CAETE TOTAL

169 41.79 43.4 254.19

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 11

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

La localidad de Lircay cuenta con redes de distribucin que cubren aproximadamente el 90.00% del rea, que han ido siendo instaladas desde hace 4 dcadas y su estado de conservacin es mala en lo que respecta a las tuberas de asbesto cemento y fierro fundido, que en total suman 6.682 Km. de dimetros que van de 3 a 6 pulgadas. En el cuadro 6 muestran

tuberas con detalladamente.

Cuadro 6

longitud (m) 254.19 4691.41 991.44 745.48 Tuberia_Total=6682.52

Dimetro 3 4 6 6

material AC AC AC FF

6.2

Red De Alcantarillado Para el anlisis de este rubro se toma en cuenta la informacin proporcionada por SEMSA Lircay vigente a agosto de 2008. Teniendo en cuenta el Padrn de usuarios mencionado, se ha clasificado el nmero de clientes por categoras domestico y comercial, tomando como criterio de clasificacin: la tarifa que est asignada al usuario y la razn social del mismo, asumiendo que en los casos en que se registra un nombre y apellidos, esa conexin corresponde a la categora domstica y los que se registran con una razn social son comerciales as mismo estn considerando las instituciones estatales y colegios como comerciales. Los componentes que conforman el sistema de alcantarillado y tratamiento de aguas residuales de las cuidad de Lircay estn conformados por: Conexiones domiciliarias de alcantarillado Red de recoleccin emisor Planta de tratamiento de aguas residuales

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 12

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

El rea en estudio cuenta con red de colectores de dimetros que van de DN 160mm a 200 mm cuyo material predominante es el concreto seguida por el PVC, en lo que respecta al material de concreto estas se encuentran en mal estado ya que en algunos tramos se ha erosionado la base del tubo, en cuanto al PVC esta ha sido recientemente cambiadas encontrndose en buen estado de conservacin. Sin embargo la descarga final lo realizan hacia los mrgenes del ro Sicra y la margen derecha del ro Opamayo sin ningn tratamiento previo. 6.2.1 Red de recoleccin

En la localidad de Lircay, se tiene que aproximadamente el 75% del rea del proyecto est cubierto con redes de alcantarillado, conformado por tuberas de DN 160mm a DN 200 mm en una longitud total de 8,873.83 m, el tipo de material que predomina es el de concreto simple normalizado seguida por PVC.

Cuadro 7

RED DE ALCANTARILLADO LONGITUD(m) DIAMETRO (pulg.) MATERIAL 4510.08 3338.74 1025.01 8 8 6 CSN PVC PVC

Teniendo en cuenta los sentidos actuales de los colectores y el interceptor proyectado se ha previsto renovar y ampliar los colectores en una longitud total de 8.149.37ml, as mismo la longitud total del interceptor rio SICRA es: 897.00ml. A continuacin cuadro de calles por longitud de tubera existente

Cuadro 8

CALLES Av. Centenario Pasaje Jr.Cahuide y Jr.Puno

LONGITUD (m) 354.5 39.69 421.12

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 13

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

CALLES Jr.Independencia y Jr.Puno Via Evitamiento yJiron 9 Jr.27 de Noviembre Jr.Tupac AmaruAv.Centenario y Jr.6 de Agosto Jr.Daniel Hernndez y Jr.Lima Av. Ricardo Fernandez Jr.Simon Bolivar Jr.Progreso y Jr.Micaela Bastidas Jr.Caete Jr.Buenos Aires,Jr.Bolognesi Jr.Atahualpa Pasaje 2 Jr.Ayacucho Jr.Atahualpa y Jr. Simon Bolivar Jr.Buenaventura Av. La Esmeralda y Jr.La Libertad Jr.Olimpico y Jr.Mariscal Sucre Av. 9 de Octubre Jr.Olimpico Calle Av. Gandolini

LONGITUD (m) 445.06 295.25 189.67 878.73 813.29 139.86 133.24 878.73 54.34 530.29 114.86 50.95 198.58 54.78 776.7 696.56 98.51 400.06 466.83 141.59

DESARROLLO DEL ESTUDIO

El diseo del Estudio definitivo para el Mejoramiento

de Redes de Agua y

Desage de la localidad de Lircay, comprende la solucin del abastecimiento de agua en base a la alternativa seleccionada en el estudio de Pre Inversin aprobado, comprende el desarrollo de los proyectos de las obras a ejecutarse con la finalidad de ampliar y mejorar los sistemas existentes.

7.1

Parmetros de diseo El objetivo especfico de este captulo es definir los criterios de diseo bsico para elaborar el presente informe para la construccin lnea de aduccin y redes

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 14

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

de distribucin de agua, redes secundarias de alcantarillado e interceptor rio Sicra. Los criterios de diseo que se presentan a continuacin se basan en las siguientes normativas:

Normas y requisitos para los proyectos de agua potable y alcantarillado destinadas a las localidades urbanas Ministerio de Vivienda Construccin y Saneamiento.

Reglamento Nacional de Construcciones. Nuevo reglamento de elaboracin de proyectos de agua potable y alcantarillado para habilitaciones urbanas de Lima y Callao SEDAPAL. Recomendaciones del CEPIS.

7.2

rea de Influencia El rea de Influencia, segn los Trminos de referencia, se encuentra definida como el distrito de Lircay, localidad de Lircay barrios: Barrio Nuevo Barrio Alto Barrio Viejo Bellavista Santa rosa Virgen del carmen comprendiendo los siguientes

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 15

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

7.3

Poblacin Actual Segn las proyecciones basadas en los censos poblacionales realizados para el distrito de Lircay, en la actualidad se tiene una poblacin de 6,648 habitantes.

Cuadro 9

Censo (ao) 1,972 1,981 1,993 2,007

Poblacin (habitantes) 4,706 5,114 4,654 6,563

Fuente: Censos de Poblacin y vivienda 1972, 1981, 1993, 1997

Cuadro 10

Lircay

Tasa de Crecimiento (%) 1.3

7.4

Poblacin de Diseo

La poblacin futura fue determinado teniendo en consideracin los datos censales de los aos 1972, 1981, 1993 y 2007. De acuerdo a esto, se ha seleccionado el mtodo geomtrico de crecimiento poblacional, el cual plantea una tasa de 1.30%. Esta misma tasa de crecimiento, el Consultor mantendr, como valido para efectuar la proyeccin de la poblacin hasta el 2029, debido a que dicha tasa toma las previsiones del comportamiento futuro de la localidad por los siguientes factores: rea de desarrollo urbano del distrito de Lircay.

7.5

Horizonte del Diseo El horizonte del estudio ha sido definido en el estudio de Pre inversin, notndose que el final del periodo de diseo es el 2029.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 16

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

En las Normas Tcnicas del Reglamento Nacional de Construcciones, el periodo de diseo est relacionado con el nmero de habitantes de cada localidad, con la finalidad de proyectarse a futuro las necesidades de la poblacin durante un periodo determinado de tiempo en concordancia del crecimiento poblacional. El horizonte del proyecto de agua potable y alcantarillado determinados en el estudio de Pre Inversin, es de 20 aos, contados a partir del inicio del funcionamiento del mismo, previsto para el ao base 2009.

7.6

Poblacin Servida Actualmente de acuerdo a informacin proporcionado la cobertura del servicio de agua potable es aproximadamente el 92.75% de la poblacin total, Las

viviendas que cuentan con conexiones domiciliarias en la localidad de Lircay, tienen aproximadamente 7 das a la semana de agua y 23 horas/da en promedio, en poca de lluvias y en estiaje se reduce a 14 horas/da.

7.7

Dotacin El nmero de usuarios del sector domestico representa el 95.77 % del total de conexiones existentes.

7.8

Consumo por conexin

Consumo por Tipo de Conexin Domestico Comercial Institucional C/Med. S/Med. C/Med. S/Med. C/Med. S/Med. 0.00 20.00 0.00 30.00 0.00 30.00

7.9

Demanda Actual Y Futura De Agua La demanda actual y futura fue determinada, considerando los siguientes valores. Ver cuadro

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 17

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

DEMANDA DE AGUA POTABLE


Conexiones ITEM Ao Pob. Urbana Cobert. Poblac. Servida N Viv. Servidas C/Med Domstico S/Med Total % C/Med Micromed. Comercial S/Med Total % C/Med Micromed. Institucional S/Med Total Total Conexiones % C/Med. S/Med. Micromed. Total Prdidas de Agua (%) Consumo Domstico m3/ao Consumo total de agua m3/Ao Consumo Comercial m3/ao Consumo Consumo Total Instituciomal Conectado 3 m /ao m3/Ao Caudal Promedio (l/dia) Demanda Produccion de Agua (l/da) Demanda Total m3/ao Demanda Total (l/s) Volumen de Almac. (m3)

-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029

6,648 6,734 6,822 6,910 7,000 7,091 7,183 7,276 7,371 7,466 7,563 7,662 7,761 7,862 7,964 8,067 8,172 8,278 8,385 8,494 8,604 8,716

92.75% 92.75% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95% 95%

6,166 6,246 6,481 6,565 6,650 6,736 6,824 6,912 7,002 7,093 7,185 7,279 7,373 7,469 7,566 7,664 7,763 7,864 7,966 8,069 8,174 8,280

1,585 1,606 1,666 1,688 1,710 1,732 1,754 1,777 1,800 1,823 1,847 1,871 1,895 1,920 1,945 1,970 1,996 2,022 2,048 2,074 2,101 2,129

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1,518 1,539 1,598 1,620 1,641 1,663 1,685 1,707 1,730 1,752 1,776 1,799 1,823 1,848 1,872 1,897 1,922 1,948 1,973 1,999 2,025 2,053

1,518 1,539 1,598 1,620 1,641 1,663 1,685 1,707 1,730 1,752 1,776 1,799 1,823 1,848 1,872 1,897 1,922 1,948 1,973 1,999 2,025 2,053

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3.89

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 hab/viv

30 30 31 31 32 32 32 33 33 34 34 35 35 35 36 36 37 37 38 38 39 39

30 30 31 31 32 32 32 33 33 34 34 35 35 35 36 36 37 37 38 38 39 39

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37

37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1,585 1,606 1,666 1,688 1,710 1,732 1,754 1,777 1,800 1,823 1,847 1,871 1,895 1,920 1,945 1,970 1,996 2,022 2,048 2,074 2,101 2,129

1,585 1,606 1,666 1,688 1,710 1,732 1,754 1,777 1,800 1,823 1,847 1,871 1,895 1,920 1,945 1,970 1,996 2,022 2,048 2,074 2,101 2,129

48.0 48.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0 35.0

364,320 369,360 383,520 388,800 393,840 399,120 404,400 409,680 415,200 420,480 426,240 431,760 437,520 443,520 449,280 455,280 461,280 467,520 473,520 479,760 486,000 492,720

10,800 10,800 11,160 11,160 11,520 11,520 11,520 11,880 11,880 12,240 12,240 12,600 12,600 12,600 12,960 12,960 13,320 13,320 13,680 13,680 14,040 14,040

13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320

388,440 393,480 408,000 413,280 418,680 423,960 429,240 434,880 440,400 446,040 451,800 457,680 463,440 469,440 475,560 481,560 487,920 494,160 500,520 506,760 513,360 520,080

1,064,219 1,078,027 1,117,808 1,132,274 1,147,068 1,161,534 1,176,000 1,191,452 1,206,575 1,222,027 1,237,808 1,253,918 1,269,699 1,286,137 1,302,904 1,319,342 1,336,767 1,353,863 1,371,288 1,388,384 1,406,466 1,424,877

2,046,575 2,073,129 1,719,705 1,741,960 1,764,720 1,786,975 1,809,231 1,833,003 1,856,269 1,880,042 1,904,320 1,929,105 1,953,383 1,978,672 2,004,468 2,029,757 2,056,565 2,082,866 2,109,674 2,135,975 2,163,794 2,192,118

747,000 756,692 627,692 635,815 644,123 652,246 660,369 669,046 677,538 686,215 695,077 704,123 712,985 722,215 731,631 740,861 750,646 760,246 770,031 779,631 789,785 800,123

23.69 23.99 19.90 20.16 20.43 20.68 20.94 21.22 21.48 21.76 22.04 22.33 22.61 22.90 23.20 23.49 23.80 24.11 24.42 24.72 25.04 25.37

640 648 537 544 552 558 565 573 580 588 595 603 610 618 626 634 643 651 659 667 676 685

(*) Para la elaboracin del cuadro de demanda se ha utilizado una densidad poblacional de FUENTE: Estudio de Prefactibilidad

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 18

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

7.10 Demanda Actual Y Futura De Alcantarillado


DEMANDA DE ALCANTARILLADO
Conexiones ITEM Ao Pob. Urbana Cobert. Poblac. Servida N Viv. Servidas Domstico Comercial Institusional Total Consumo Domstico m3/ao Consumo total de agua m3/Ao Consumo Comercial m3/ao Consumo Instituciomal m3/ao Consumo Total Conectado m3/Ao Caudal Promedio de consumo de agua (l/dia) Caudales de alcantarillado Demanda Demanda de Total alcantarillado Caudal Qmx alcantarillado F = 80% Promedio Horario (l/da) m3/ao (l/s) (l/da)

-1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029

6,648 6,734 6,822 6,910 7,000 7,091 7,183 7,276 7,371 7,466 7,563 7,662 7,761 7,862 7,964 8,067 8,172 8,278 8,385 8,494 8,604 8,716

81% 81% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85% 85%

5,411 5,455 5,799 5,874 5,950 6,027 6,106 6,185 6,265 6,346 6,429 6,513 6,597 6,683 6,769 6,857 6,946 7,036 7,127 7,220 7,313 7,409

1,391 1,402 1,491 1,510 1,530 1,549 1,570 1,590 1,611 1,631 1,653 1,674 1,696 1,718 1,740 1,763 1,786 1,809 1,832 1,856 1,880 1,905

1,324 1,335 1,423 1,442 1,461 1,480 1,501 1,520 1,541 1,560 1,582 1,602 1,624 1,646 1,667 1,690 1,712 1,735 1,757 1,781 1,804 1,829

30 30 31 31 32 32 32 33 33 34 34 35 35 35 36 36 37 37 38 38 39 39

37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37

1,391 1,402 1,491 1,510 1,530 1,549 1,570 1,590 1,611 1,631 1,653 1,674 1,696 1,718 1,740 1,763 1,786 1,809 1,832 1,856 1,880 1,905

317,760 320,400 341,520 346,080 350,640 355,200 360,240 364,800 369,840 374,400 379,680 384,480 389,760 395,040 400,080 405,600 410,880 416,400 421,680 427,440 432,960 438,960

10,800 10,800 11,160 11,160 11,520 11,520 11,520 11,880 11,880 12,240 12,240 12,600 12,600 12,600 12,960 12,960 13,320 13,320 13,680 13,680 14,040 14,040

13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320 13,320

341,880 344,520 366,000 370,560 375,480 380,040 385,080 390,000 395,040 399,960 405,240 410,400 415,680 420,960 426,360 431,880 437,520 443,040 448,680 454,440 460,320 466,320

936,658 943,890 1,002,740 1,015,233 1,028,712 1,041,205 1,055,014 1,068,493 1,082,301 1,095,781 1,110,247 1,124,384 1,138,849 1,153,315 1,168,110 1,183,233 1,198,685 1,213,808 1,229,260 1,245,041 1,261,151 1,277,589

749,326 755,112 802,192 812,186 822,970 832,964 844,011 854,794 865,841 876,625 888,198 899,507 911,079 922,652 934,488 946,586 958,948 971,046 983,408 996,033 1,008,921 1,022,071

273,504 275,616 292,800 296,448 300,384 304,032 308,064 312,000 316,032 319,968 324,192 328,320 332,544 336,768 341,088 345,504 350,016 354,432 358,944 363,552 368,256 373,056

8.67 8.74 9.28 9.40 9.53 9.64 9.77 9.89 10.02 10.15 10.28 10.41 10.54 10.68 10.82 10.96 11.10 11.24 11.38 11.53 11.68 11.83

17.34 17.48 18.56 18.80 19.06 19.28 19.54 19.78 20.04 20.30 20.56 20.82 21.08 21.36 21.64 21.92 22.20 22.48 22.76 23.06 23.36 23.66

(*) Para la elaboracin del cuadro de demanda se ha utilizado una densidad poblacional 3.89 de hab/viv. (*) Pa el calculo del caudal de alcantarilado se ha utilizado como coeficiente de retorno F = 0.80

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 19

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

8 8.1

PARAMETROS ESPECIFICOS DE AGUA POTABLE Coeficiente De Variacin De Consumo A partir de la demanda promedio neta de agua calculada por cada ao, se debe aplicar los coeficientes ms representativos de la demanda del agua. Los coeficientes establecidos a tomar: Coeficiente diario que caracteriza el consumo mximo anual: Coeficiente horario que caracteriza el consumo mximo del da: K1=1.3 K2=2.0

8.2

Lneas De Aduccin Y Redes De Distribucin

En lneas de aduccin y redes de distribucin, los parmetros a usar en los clculos son: Tipo de tubera Velocidad recomendada de conduccin Proteccin contra acumulacin de aire en los puntos altos Sistema de evacuacin de sedimentos en los puntos bajos

Para el clculo de las tuberas que trabajan con flujo a presin se utilizarn frmulas racionales. En caso de aplicarse la frmula de Hazen y Williams, se utilizarn los coeficientes de friccin que se establecen en la Tabla 1 Para el caso de tuberas no consideradas, se deber justificar tcnicamente el valor utilizado.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 20

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

COEFICIENTES DE FRICCIN C EN LA FRMULA DE HAZEN Y WILLIAMS TABLA 1 TIPO DE TUBERIA Acero sin costura Acero soldado en espiral Cobre sin costura Concreto Fibra de vidrio Hierro fundido C 120 100 150 110 150 100

Hierro fundido con revestimiento 140 Hierro galvanizado Polietileno, Asbesto Cemento Poli(cloruro de vinilo)(PVC) 100 140 150

8.3

Pendientes mnimas El diseo de las lneas de aduccin se ha realizado considerando la operacin del sistema, de la manera que facilite la acumulacin de aire en las partes altas pronunciadas, en donde se instalaran elementos (vlvulas de aire) que asegure la evacuacin de este. Se ha procurado dar siempre pendiente a la tubera para permitir el ascenso del aire. Pendiente mnima dos por mil. (2 m/km)

8.4

Vlvula de aire o ventosa Los aparatos de purga de aire se situaran en puntos altos y en cambios de pendiente. De acuerdo a dimetros del Conducto se coloca la vlvula de aire, alojadas en una cmara de concreto armado.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 21

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

8.5

Velocidad del Conducto La eleccin del dimetro se encuentra relacionada en forma directa a la

velocidad que se produzca en el conducto. Se ha considerado que las velocidades en la red deben ser menores a 1.5 m/s, excepcionalmente se consideraran velocidades mayores de hasta 3.00 m/s. V (m/s) = < 0.60 a 3.00>

8.6

Zonas de presin Las zonas de presin se definirn en funcin a: La topografa, delimita las zonas de abastecimiento, teniendo presente las presiones mximas y mnimas en la red de distribucin de 50 a 15 m.c.a., respectivamente, de acuerdo al Reglamento Nacional de Construcciones, sin embargo excepcionalmente se aceptaran presiones de hasta 10.00 m.c.a. de agua como presin mnima. Las presiones mnimas de 10.00 m.c.a. en las redes de distribucin se aplicaran en casos en que la zona cuenta con edificaciones de hasta 2 pisos. El rea de influencia del reservorio que abastezca esta zona de presin, en los casos que la presin supere los 50.00 m.c.a. se han diseado vlvulas reductoras de presin para regulara la presin en cada zona de presin.

8.7

Profundidad mnima de instalacin Se ha considerado el enterramiento mnimo de 1.00 m encima de la clave de la tubo. Solo en casos excepcionales y para dimetros de DN 110 mm de PVC o menores de ha previsto con una cobertura mnima de 0.80 m. Cuando se tenga que producir enterramientos ms superficiales se recomienda la proteccin de la tubera en forma conveniente, para el tipo de suelo y transito que se produzca en la superficie, o se instalara un tubo de mayor resistencia al esfuerzo de aplastamiento.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 22

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

8.8

Anclajes para accesorios de tuberas A fin de contrarrestar el empuje que se pueda presentar debido a la presin interna de la tubera se ha diseado anclajes de concreto en: Cambios de direccin (codos) Cambios de dimetro (reducciones, tees) Vlvulas de compuerta Hidrantes o grifos contra incendio Terminales de lnea taponadas

Las dimensiones y forma de los anclajes se han determinado teniendo en cuenta la presin de La lnea del tubo, clase de terreno y tipo de accesorio.

PARAMETRO ESPECIFICOS DE ALCANTARILLADO

9.1

Coeficiente De Retorno (C)

Estudios estadsticos han estimado el porcentaje de agua abastecida que llega a la red de alcantarillado. Este coeficiente oscila entre el 60% y 80% de la dotacin de agua potable, para nuestro caso, se adoptara un coeficiente de retorno (C) igual al 80% conforme a lo establecido Norma OS.70 REDES DE AGUAS RESIDUALES del Reglamento Nacional de Edificaciones. El proyectista deber en casos especficos ajustarse a datos reales y hbitos de uso del agua, siempre y cuando se realicen estudios de respaldo. 9.2 Cuantificacin De Caudales De Aporte Domestico

Los caudales de aporte domstico que deben ser cuantificados: Caudal medio diario (Qm) Caudal mximo horario (Qmh) Caudal de Diseo (Qd) = 0.80 Qmh

9.3

Aporte De Aguas Industriales, Comerciales Y Pblicas

La contribucin de las aguas residuales industriales, comerciales y pblicas ser evaluada en forma puntual y como descarga concentrada de acuerdo a los niveles de

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 23

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

consumo. La descarga estar condicionada a la ley de medio ambiente y sus reglamentos.

9.4 9.4.1

Criterio De Diseo Formulas para diseo de redes de alcantarillado

La tcnica de clculo admitir el escurrimiento en el rgimen uniforme y permanente, donde el caudal y la velocidad media permanecen constantes en una determinada longitud de conducto. Para el dimensionamiento del dimetro de la tubera de la red de alcantarillado se podr utilizar las formulas de Manning y la formula de Ganguiller-Kutter.

9.4.2

Criterio de velocidad mnima

En consideracin a que las aguas que circulan por los alcantarillados contienen normalmente partculas que podran sedimentarse y formar obstrucciones, se suele especificar que las pendientes sean superiores a un valor mnimo que en principio garantice velocidades suficientemente altas para producir el arrastre de los materiales en suspensin. La velocidad mnima recomendada que garantiza el arrastre es conocida como velocidad mnima de arrastre y es especificada por la mayora de normas en 0.60 m/s para el caso de alcantarillado sanitario. Sin embargo algunos autores consideran y recomiendan que con una velocidad igual a 0.30 m/s, es suficiente para garantizar el arrastre y la auto limpieza de la tubera.

9.4.3

Criterio de la Tensin Tractiva

La capacidad de auto limpieza de la tubera de alcantarillado, es decir, la posibilidad de que sean arrastradas las partculas en suspensin, depende del esfuerzo cortante que la corriente de agua ejerza sobre las paredes interiores donde podran ocurrir la sedimentacin. Conforme a lo establecido en el numeral 3.1 Norma OS.70 del Reglamento Nacional de Edificaciones, la pendiente del colector, ser calculada con el criterio de la tensin

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 24

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

tractiva. El valor mnimo de la Fuerza Tractiva ser igual a 1.00 Pa, sin embargo en tramos de arranque se podr considerar valores de la Fuerza tractiva igual a 0.60 Pa.

9.4.4

Criterio de la Tensin Tractiva

Conforme a lo establecido Norma OS.70 del Reglamento Nacional de Edificaciones, el proyecto de colectores de alcantarillado sanitario, tomar en cuenta las condiciones de flujo crticas que pueden presentarse debido a los bajos caudales de aporte durante los primeros aos despus de su construccin. Se deber garantizar que las pendientes no sean demasiado bajas como para producir sedimentacin, ocasionando elevados costos de mantenimiento antes de alcanzar los caudales de proyecto. La pendiente mnima de diseo se define para cualquier dimetro, como aquella que en condiciones de transporte de aguas residuales parcialmente llenos o a tubo lleno produzca una velocidad determinada (0.60 m/s) cuando se utiliza el criterio de velocidad mnima o cuando se quiere obtener un valor determinado de la Fuerza Tractiva (1.00 Pa) cuando se utiliza este criterio.

9.4.5

Coeficiente de rugosidad

El coeficiente de rugosidad n de la frmula de Manning ser diferente segn el tipo de material, LOS MISMOS que se presenta el siguiente cuadro:

MATERIAL PVC CONCRETO FIBROCEMENTO HIERRO DUCTIL

COEFICIENTE(C) 0.090 0.013 0.090 0.090

POLIETILENO (HDPE) 0.090

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 25

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

9.4.6

Tensin tractiva mnima

Conforme a lo establecido DISPOCISIONES ESPECIFICAS PARA DISEO NORMA OS.070 del Reglamento Nacional de Edificaciones, la fuerza tractiva mnima debe ser suficiente para transportar entre el 90% al 95% del material granular que se estima entra al sistema de alcantarillado. La Tensin Tractiva mnima para los sistemas de alcantarillado sanitario ser de un Pa. En los tramos iniciales la verificacin no podr ser inferior a 0,6 Pa.

9.4.7

Dimetro mnimo

Conforme a lo establecido en la Norma OS.070 REDES DE AGUAS RESIDUALES del Reglamento Nacional de Edificaciones, el dimetro mnimo de los colectores de alcantarillado sanitario ser de 150 mm.

9.4.8

Tirante mximo

Se acuerdo a los criterios de diseo y al numeral 3.1 DISPOCIONES ESPECIFICAS PARA DISEO de la Norma OS.070 del Reglamento Nacional de Edificaciones, el tirante mximo para el valor del caudal mximo futuro ser igual o inferior al 75% del dimetro interno del colector, para permitir la ventilacin de forma que se minimice o elimine la generacin y acumulacin de sulfuro de hidrgeno.

9.4.9

Profundidad de instalacin

Conforme a lo establecido UBICACIN DE TUEBRIAS de la Norma OS.070 DEL Reglamento Nacional de Edificaciones, la profundidad mnima de instalacin de una tubera ser definida por el recubrimiento mnimo y este no debe ser menor de 1.00 metro sobre la clave de las tuberas en vas de trnsito vehicular y de 0.80 metros en vas de trnsito justificados. peatonal. De haber menores recubrimientos estos deben ser

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 26

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

9.4.10 Ubicacin de elementos de inspeccin Conforme a lo establecido CAMARAS DE INSPECCION de la Norma OS.070 del Reglamento Nacional de Edificaciones, sern ubicados los elementos de inspeccin en los arranques de la red, cambios de direccin y pendiente. Las distancias mximas entre cmaras o tubos de inspeccin (no visitables) estarn en funcin de los equipos de limpieza previstos y disponibles. Se sugiere el siguiente cuadro:

DIAMETRO NOMINAL DE DISTANCIA LA TUBERIA (mm) 100 150 200 250 a 300 Dimetros mayores MAXIMA (m) 60 60 80 100 150

9.4.11 Material de la tubera Para transporte de fluidos por gravedad, PVC segn norma NTP-ISO 4422, tambin se podr utilizar otro material aceptado por la Supervisin y certificado bajo su norma correspondiente. Para transporte de fluidos por gravedad, PVC segn norma NTP-ISO 4435, tambin se podr utilizar otro material aceptado por la Supervisin y certificado bajo su norma correspondiente. Accesorios segn el material de la tubera.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 27

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

10 DESCRIPCION DEL SISTEMA PROYECTADO

10.1 Lneas de Aduccin y redes de Distribucin El sistema de distribucin de agua potable del distrito Lircay, contara con dos reservorios para abastecer a toda la poblacin. 10.1.1 Lneas de Aduccin Ver (plano AP 02) Las lneas de aduccin tienen como fin fundamental el transporte de agua potable desde el reservorio hasta la red de distribucin. Consisten en una lnea de tuberas de fabricadas para trabajar a presin debido a la carga hidrulica con que cuenta el sistema y a la correcta ubicacin del reservorio. Se ha proyectado una lnea de aduccin de 34.40m. Desde el Reservorio Bella Vista, que tendr un DN de 160mm de PVC C-7.5, esta Lnea se inicia en la casa de vlvulas de la Reservorio y contina por un camino hasta la red de distribucin.

10.1.2 Red de distribucin Ver (plano AP 02) Las redes de distribucin con la que cuenta la localidad de Lircay fueron

instalados en diferentes aos y su antigedad se puede definir al material que se encuentra instalado. La mayora de las tuberas existentes son de Asbesto Cemento, las mismas que sern reemplazadas por tuberas nuevas de PVC, en su totalidad. Se ha previsto la renovacin y ampliacin de la red de distribucin en los sectores abastecidos por los reservorios de Pueblo Viejo y Bellavista en una longitud total de 11,290.41ml de tuberas, para redes de agua potable de diferentes dimetros, los cuales se encuentran distribuidos en los diferentes sectores de abastecimiento, como se indica a continuacin:

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 28

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

CALLE LONGITUD DE TUBERIA BOLIVAR 261.08 JR. PROGRESO 270.51 JR. BUENOS AIRES 182.71 JR. PROCERES 167.20 JR. TUPAC AMARU 148.23 PASAJE 2 19.55 CALLE S/N 6 87.87 JR. CAETE 45.51 JR. BOLOGNESI 130.28 JR. OLIMPICO 405.56 AV. CENTENARIO 671.48 JR. LIMA 395.05 JR. PUNO 274.71 VIA DE EVITAMIENTO 904.78 JR. 9 38.65 PASAJE 3 32.60 JIRON 8 128.48 JR. CAHUIDE 333.20 CALLE S/N 3 120.97 PROLONGACION JR. PUNO 167.86 JR. 27 DE NOVIEMBRE 206.15 PASAJE 4 70.91 JR. 6 DE AGOSTO 132.08 PROLONG. 6 DE AGOSTO 65.66 JR. 9 DE DICIEMBRE 190.33 AV. R. FERNANDEZ 226.31 AVENIDA N 1 763.83 AV. LA ESMERALDA 1,026.73 JR. LIBERTAD 624.40 JR. MARISCAL SUCRE 405.36 JR. MARAVILLAS 287.58 PASAJE 5 98.88 MAREATEGUI 49.21 PROLONG. JR. CAHUIDE 183.81 CALLE N5 159.31 CALLE N 6 203.36 CALLE S/N 4 40.82 CALLE 07 55.24 PASAJE 6 125.58 PASAJE 7 130.29 PASAJE 8 66.95
HUANCAVELICA-ANGARAES-LIRCAY Pgina 29

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

CALLE PASAJE 9 PASAJE 10 PASAJE 11 PASAJE 12 CALLE S/N 01 JR. HAYA DE LA TORRE PASAJE 13 PASAJE 14 PASAJE 15 PASAJE 16 PASAJE 17 PASAJE 18 PROLONG. CAHUIDE 1 PROLONG. CAHUIDE 2 AVENIDA 9 DE OCTUBRE
10.1.2.1 Evaluacin

LONGITUD DE TUBERIA 91.95 45.00 142.47 119.79 80.05 44.04 175.17 71.52 65.58 65.68 24.39 38.89 34.40 289.02 103.39

La simulacin hidrulica se ha realizado al sistema de distribucin proyectado, para la situacin futura, empleando el caudal mximo horario, tomando en cuenta las siguientes consideraciones: Presin mnima = 15.00 m.c.a. Presin mxima = 50.00 m.c.a. Velocidad mnima en la red = 0.60 m/s Velocidad mxima en la red = 3.00 m/s En los tramos donde no se cumpla con la velocidad mnima se considerara la purga del tramo por los hidrantes cercanos al tramo. El software que se utiliz fue el watercad.

10.1.2.2 Accesorios Ver Plano AP-03 Se ha previsto la instalacin de accesorios en la red de distribucin, como son los, codos, accesorios de empalme, reducciones, etc., los cuales se detallan en HUANCAVELICA-ANGARAES-LIRCAY Pgina 30

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

los planos AP-03: Diagrama de Accesorios y laminas de detalles de empalmes adjuntos al presente

10.1.2.3 Vlvulas Ver Plano AP-03 Se ha previsto la instalacin de vlvulas de compuerta para el seccionamiento de la red, con fines de operacin y mantenimiento, tanto en redes existentes como en proyectadas. La ubicacin ser a una distancia promedio de 2.00 m de la esquina ms cercana. Para el nuevo sistema de distribucin, se ha previsto la instalacin de 34vlvulas, para ser colocadas en la red de distribucin segn la siguiente descripcin: 34 vlvulas de compuerta HD DN 110mm

10.1.2.4 Grifos contra incendio Ver Plano AP-03 Grifos contra incendio por lo que, se ha previsto la instalacin de 12 GCI tipo Poste. La cantidad de GCI nuevos a instalar se detalla a continuacin: 12 hidrantes en redes de DN 110mm

Los GCI sern de Hierro Dctil, y sern ubicados en las veredas, constaran con una vlvula de interrupcin (vlvula tipo compuerta) y su respectiva tee, esta vlvula constara con su caja de superficie para su operacin.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 31

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

10.2 Vlvula de aire triple efecto La ciudad del Lircay, debido a la topografa de la localidad se ha prevista la instalacin de una vlvula de aire de triple efecto, para su normal funcionamiento de las redes de agua potable en la ciudad de Lircay.1

10.3 Estaciones reductoras de presin La ciudad de Lircay actualmente cuenta con sectores de distribucin

plenamente definidos, para el nuevo sistema se han definido un sector de abastecimiento en funcin a la ubicacin del reservorio proyectado. Las presiones de estos sectores de abastecimiento varan de acuerdo a la topografa de la ciudad, por lo que tambin se ha considerado dos sub sectores de abastecimiento. Cuadro 11

Cuadro 11
COTA DESCRIPCION ITEM UBICACIN m.s.n.m. PRESION LLEGADA m.c.a. PRESION SALIDA m.c.a.

ERP1 ERP ERP2 ERP3

3328.36 3319.38 3335.30

55.10 60.04 49.00

7.00 8.00 10.00

10.4 Conexiones domiciliarias de agua Ver Plano: AP-02 El estudio de pre inversin ha contemplado la instalacin de 1251 conexiones domiciliarias, sin embargo no precisa su ubicacin. Las caractersticas de las conexiones domiciliarias son las siguientes:

Elementos de toma: 1 abrazadera con salida vertical, derivacin de , con empaquetaduras y dimetros variables de tubo matriz de PVC, en tuberas reemplazadas.
1

La ubicacin de la Vlvula est indicada en el plano

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 32

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

1 vlvula de cierre (corporation) de PVC

Elementos de conduccin: 1 tubo de conduccin (acometida) de PVC SAP Clase 10 de 5.98 m. de longitud en promedio. Micromedicin El estudio ha contemplado la instalacin de 1251 micromedidores, sin embargo no precisa su ubicacin. Las caractersticas de las conexiones domiciliarias son las siguientes: 3 codos de 1/8 x

Elementos de control: 1 micromedidor de 1 vlvula de paso de , colocada aguas arriba del medidor 1 vlvula de paso de , colocada aguas abajo del medidor 2 unin presin rosca

Elementos de proteccin: 1 caja porta medidor de concreto con marco y tapa de acero galvanizado con seguro

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 33

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

Detalle de Conexin Domiciliaria de Agua Potable

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 34

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

11 DESCRIPCION DEL SISTEMA PROYECTADO DE ALCANTARILLADO


11.1 Sistema Proyectado De Alcantarillado En la localidad de Lircay, se tiene que aproximadamente el 75% del rea del proyecto est cubierto con redes de alcantarillado, conformado por tuberas de DN 160mm a DN 200 mm en una longitud total de 8,873.83 m, el tipo de material que predomina es el de concreto simple normalizado seguida por las de PVC.

Tabla 2

RED DE ALCANTARILLADO LONGITUD(m) DIAMETRO (pulg.) MATERIAL 4510.08 3338.74 1025.01 8 8 6 CSN PVC PVC

Para la proyeccin de red de alcantarillado de la localidad de Lircay se a tomado en cuenta los sentidos actuales de los colectores se a previsto la renovacin y ampliacin de los colectores primarios y secundarios en una longitud total de 8149.37ml tubera de DN 200 mm S25 y DN 200 mm S25 a esto se le suma la instalacin de tubera de localidad VIRGEN DEL CARMEN, que es de 1430.55ml. Que nos dan un total de 9579.92ml DN 200 mm S25 y S20 El estudio de pre factibilidad indicaba un recorrido de los Interceptores por ambas mrgenes del rio Sicra, lo cual ocasionara el estrechamiento del cauce por la realizacin de terraplenes y obras de defensa riberea, atravesar las viviendas ubicadas en ambas mrgenes del rio. As, se est proyectando un dos interceptores en la margen izquierda del ro Sicra y rio Opamayo los

desages comprendidos en la margen izquierda del ro, asimismo, los desages de la margen derecha captados a travs de cruces de tubera, aprovechando la infraestructura de los puentes existentes. Consiste en el tendido de lneas a lo largo de la margen izquierda del ro Sicra y a la margen derecha del ro Opamayo.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 35

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

La longitud el interceptor 1 (Opamayo) cuenta con una longitud de 1,066.77ml 2 La longitud el interceptor 2 (Sicra) cuenta con una longitud de 897.00 ml* La longitud del Emisor proyectado para la recoleccin y traslado hacia la planta de tratamiento, tiene una longitud de 599.95 ml3
* Lo podemos ver ms detallado en los metrados adjunto

11.2 Redes Secundarias Para la ejecucin y ampliacin del nuevo sistema de alcantarillado de la localidad de Lircay, se ha proyectado la construccin de las siguientes obras: Construccin de 129 cmaras de inspeccin o buzones de Dimetro interior 1.20 m, espesor de pared 0.20 y altura variable que van desde 1.01 hasta 1.5 m. en terreno normal Construccin de 6 cmaras de inspeccin o buzones de Dimetro interior 1.20 m, espesor de pared 0.20 y altura variable que van desde 1.51 hasta 2.0 m. en terreno normal Construccin de 10 cmaras de inspeccin o buzones de Dimetro interior 1.20 m, espesor de pared 0.20 y altura variable que van desde 2.01 hasta 2.50 m. en terreno normal Construccin de 3 cmaras de inspeccin o buzones de Dimetro interior 1.20 m, espesor de pared 0.20 y altura variable que van desde 2.51 hasta 3.00 m. en terreno normal Construccin de 1 cmaras de inspeccin o buzones de Dimetro interior 1.50 m, espesor de pared 0.25 y altura variable que van desde 4.01 hasta 5.00 m. Construccin de 10 cmaras de inspeccin o buzones de Dimetro interior 1.20 m, espesor de pared 0.20 y altura variable que van desde 1.01 hasta 1.50 m. terreno rocoso Construccin de 2 cmaras de inspeccin o buzones de Dimetro interior 0.6 m, espesor de pared 0.15 y altura de 1.00. terreno normal. Construccin de 1cmaras de inspeccin o buzones de Dimetro interior 0.6 m, espesor de pared 0.15 y altura de 1.00. terreno rocoso

2 3

No est contemplado en el proyecto No est contemplado en el proyecto

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 36

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

Instalacin de 8149.37ml . de tuberas de alcantarillado DN 200mm en Serie 25 y Serie 20 con profundidades que varias desde 1.00 hasta 5.00m.

11.3 Colectores Principales 11.3.1 Colectores Av. Fernndez Se ha considerado la renovacin y ampliacin de 1118.54 ml de tubera abarca la avenida Fernndez y tambin Av. Centenario, con el objetivo que transporte la descarga de los lotes aledaos a la Av. Jos Mara Arguedas, jr. Puno, jr. Lima 11.3.2 Colectores Jr. 6 de agosto Se ha considerado la renovacin de 197.30m de tubera, que sigue el trazo de Jr. 6 de agosto con el objetivo de transportar la descarga de los lotes aledaos a: Av. Centenario, jr. Lima, calle s/n.

11.4 Interceptor 11.4.1 Interceptor 01 Rio Opomayo4 Se instala 1066.77ml de tubera en total, que se subdividen en:
SUMINISTRO E INSTALACION DE TUBERIA PVC NTP 4435 315mm S-25 916.91ml SUMINISTRO E INSTALACION DE TUBERIA PVC NTP 4435 315mm S-20 126.96ml SUMINISTRO E INSTALACION DE TUBERIA PVC NTP 4435 315mm S-16.7 22.90ml 13 BUZONES TIPO I DIMETRO INTERNO 1.20M

11.4.2 Interceptor 02 Rio Sicra Se instala 897.00ml de tubera en total, que se subdividen en:
SUMINISTRO E INSTALACION DE TUBERIA PVC NTP 4435 315mm S-25 745.08ml

No est contemplado en este proyecto.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 37

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

SUMINISTRO E INSTALACION DE TUBERIA PVC NTP 4435 315mm S-20 151.92ml

11 BUZONES TIPO I DIAMETRO INTERNO 1.20M

11.5 Emisor5 La lnea permite transportar los desages desde la ciudad de Lircay hacia la Planta de Tratamiento de aguas residuales, mediante un tramo bien definido: El traslado es por gravedad desde el BZ EMI 1 Hasta el BZ EMI 13, que tiene un recorrido que va por todo el borde del rio Sicra hasta llegar a la planta de tratamiento. Se instala 599.95ml de tubera en total.
SUMINISTRO E INSTALACION DE TUBERIA PVC NTP 4435 315mm S-25 13BUZONES TIPO I DE DI=1.20M

11.6 Conexiones domiciliarias Ver Plano: AL -04 Para el presente estudio se ha considerado la instalacin de 890 conexiones domiciliarias, en aquellos lugares donde se estn reemplazando las tuberas de alcantarillado sobre el mismo trazo de la tubera existente por cuestiones tcnicas. Las caractersticas de las conexiones domiciliarias de alcantarillado son las siguientes: Elementos de toma: 1 caja de concreto de 0.30 m x 0.60 m de altura variable

Elementos de conduccin: 1 tubo de conduccin (acometida) de PVC Serie 25 DN 160mm de 7.00 m. de longitud en promedio. 1 Codo de 45/90 x 160mm 1 Silla Tee o Yee (Cachimba) de PVC DN 200mm x 160mm

No est contemplado en este proyecto

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 38

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

2 Abrazaderas (sunchos) Pegamento para accesorios y tubera de PVC

Detalle de Conexin Domiciliaria de Desage

11.7 OBRAS ESPECIALES

11.7.1 Cruce Adosado a Puente Ver plano: adosado a puente De acuerdo a la configuracin topogrfica de la ciudad de Lircay se ha previsto la construccin de obras especiales para la instalacin de la tubera

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 39

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

11.7.2 Cruce Areo Ver plano: pase areo De acuerdo a la configuracin topogrfica de la ciudad de Lircay se ha previsto la construccin de obras especiales para la instalacin de la tubera, as como el pase areo.

12 VIRGEN DEL CARMEN La localidad del Virgen del Carmen no estaba tomada en cuenta en el perfil MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY, pero tomando en cuenta la necesidad de un sistema de recoleccin para la localidad de Virgen del Carmen, la Municipalidad Provincial de Angaraes y GEPSAR S.R.L. & CALVO se ha hecho posible desarrollar en este Expediente Tcnico MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESAGE DE LA LOCALIDAD DE LIRCAY 12.1 Poblacin de diseo La poblacin de Virgen del Carmen, se considero tomando la densidad de

vivienda de la ciudad de Lircay 3.89hab/Viv. Y con la cantidad de lotes totales de la Localidad de Virgen del Carmen. 253 lotes.

Lotes

Calculo Poblacional 253 Viv. 3.89 hab/Viv 984 Hab

Densidad de Vivienda Poblacin

12.2 Caudal de diseo Tomando en consideracin el consumo promedio de 20m3/mes de la ciudad de Lircay, el coeficiente mximo horario k2 = 2.0 y la contribucin de 80%, el caudal de diseo ser:
Coeficiente de retorno al alcantarillado 0.80 Caudal Caudal mximo Caudal de Nmero de promedio de horario de alcantarillado conexiones alcantarillado alcantarillado por conexin (Qp) (Qmh) 0.006088 lps 253 1.54 lps 3.08

Consumo de agua por conexin 20 m^3/mes 0.00761 lps

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 40

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

12.3 Red de

Alcantarillado

En la localidad de Virgen del Carmen se ha tomado en cuenta la topografa de la zona para el desarrollo de la red de alcantarillado. Para la ejecucin y ampliacin del nuevo sistema de alcantarillado de la localidad de Lircay- Virgen del Carmen, se ha proyectado la construccin de las siguientes obras: Instalacin de 1430.55 ml. de tuberas de alcantarillado DN 200mm en Serie 25 profundidades que varias desde 1.00 hasta 1.50m. Construccin de 46 cmaras de inspeccin o buzonetas de Dimetro interior 0.6 m, espesor de pared 0.15 y altura 1.00 m. Construccin de 22 cmaras de inspeccin o buzones de Dimetro interior 1.20 m, espesor de pared 0.20 y altura variable que van desde 1.01 hasta 1.50 m.

12.4 Conexiones domiciliarias (Virgen del Carmen)

Se ha considerado la cantidad de 253 conexiones domiciliarias.

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 41

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

13 COSTO DEL PROYECTO 13.1 Costo del proyecto por componente

COMPONENTE 01 SISTEMA DE AGUA POTABLE 01.01 REDES DE AGUA POTABLE 01.02 CONEXIONES DOMICILIARIAS 02 SISTEMA DE ALCANTARILLADO 02.01 REDES SECUNDARIAS DE ALCANTARILLADO 02.01.08 CONEXIONES DOMICILIARIAS DE DESAGUE 02.02 INTERCEPTOR RIO SICRA 02.03 RED DE ALCANTARILLADO (VIRGEN DEL CARMEN) 02.03.08 CONEXIONES DOMICILIARIAS DE DESAGUE

COSTO DIRECTO 1,729,170.67 1,191,822.34 537,348.33 2,389,387.82 1,893,051.87 483,028.20 165,238.02 331,097.93 130,864.58

TOTAL COSTO DIRECTO (1) GASTOS GENERALES (6%) (2) UTILIDAD (6.5%) (3) TOTAL COSTO (1)+(2)+(3) IGV (19%) COSTO TOTAL DE LA OBRA COSTO TOTAL DE SUPERVISION (3%) COSTO EXPEDIENTE TECNICO

COSTO TOTAL

4,118,558.49 247,113.51 267,706.30 ============ 4,633,378.30 880,341.88 ============ 5,513,720.18 165,411.61 136,000.00 ============ 5,815,131.79

HUANCAVELICA-ANGARAES-LIRCAY

Pgina 42

EXPEDIENTE TECNICO DEL PROYECTO MEJORAMIENTO Y RENOVACION DE REDES DE AGUA Y DESGE DE LA LOCALIDAD DE LIRCAY

13.2 Costo directo total El Costo directo total de la obra es igual a S/. 4118,558.49 (cuatro millones ciento dieciocho mil quinientos cincuenta y ocho con 49/100 nuevos soles), sin incluir los gastos generales y utilidades. 13.3 Costo total El Costo total referencial equivale a S/. 5815,131.79 (cinco millones ochocientos quince mil ciento treinta y uno con 79/100 nuevos soles), incluido IGV.

14 CONCLUSIONES Y RECOMENDACIONES Este expediente tcnico se ha visto indispensable la construccin de sistema de redes de agua potable y tambin las de redes de alcantarillado. Este expediente Tcnico ha visto indispensable la construccin de los

interceptores rio Sicra, as tambin cono la localidad del virgen del Carmen.

HUANCAVELICA-ANGARAES-LIRCAY