Introduction:
Three phase transformer consists of three sets of primary windings, one for each phase, and three sets of secondary windings wound on the same iron core. Separate single-phase transformers can be used and externally interconnected to yield the same results as a 3-phase unit. The primary windings are connected in one of several ways. The two most common configurations are the delta, in which the polarity end of one winding is connected to the non-polarity end of the next, and the star, in which all three non-polarities (or polarity) ends are connected together. The secondary windings are connected similarly. This means that a 3-phase transformer can have its primary and secondary windings connected the same (delta-delta or star-star), or differently (delta-star or star-delta). Its important to remember that the secondary voltage waveforms are in phase with the primary waveforms when the primary and secondary windings are connected the same way. This condition is called no phase shift. But when the primary and secondary windings are connected differently, the secondary voltage waveforms will differ from the corresponding primary voltage waveforms by 30 electrical degrees. This is called a 30 degree phase shift. When two transformers are connected in parallel, their phase shifts must be identical; if not, a short circuit will occur when the transformers are energized.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
1/26
8/22/13
An ac voltage applied to a coil will induce a voltage in a second coil where the two are linked by a magnetic path. The phase relationship of the two voltages depends upon which ways round the coils are connected. The voltages will either be in-phase or displaced by 180 deg When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil voltages can be in phase or displaced as above with the coils connected in star or delta and, in the case of a star winding, have the star point (neutral) brought out to an external terminal or not. Six Ways to wire Star Winding:
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
2/26
8/22/13
(http://electricalnotes.files.wordpress.com/2012/05/dd1.jpg)
Polarity:
An ac voltage applied to a coil will induce a voltage in a second coil where the two are linked by a magnetic path. The phase relationship of the two voltages depends upon which way round the coils are connected. The voltages will either be in-phase or displaced by 180 deg. When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil voltages can be in phase or displaced as above with the coils connected in star or delta and, in the case of a star winding, have the star point (neutral) brought out to an external terminal or not.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
3/26
8/22/13
(http://electricalnotes.files.wordpress.com/2012/05/untitled33.jpg) When Pair of Coil of Transformer have same direction than voltage induced in both coil are in same direction from one end to other end. When two coil have opposite winding direction than Voltage induced in both coil are in opposite direction.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
4/26
8/22/13
8/22/13
Digit 6 = 180 lagging (LV lags HV with 180) When transformers are operated in parallel it is important that any phase shift is the same through each. Paralleling typically occurs when transformers are located at one site and connected to a common bus bar (banked) or located at different sites with the secondary terminals connected via distribution or transmission circuits consisting of cables and overhead lines. Phase Shift (Deg) 0 30 lag 60 lag 120 lag 150 lag 180 lag 150 lead 120 lead 60 lead 30 lead Yd11 Yd5 Yy6 Yd7 Yy0 Yd1 Connection
Dd0 Dy1 Dd2 Dd4 Dy5 Dd6 Dy7 Dd8 Dd10 Dy11
Dz0 Yz1 Dz2 Dz4 Yz5 Dz6 Yz7 Dz8 Dz10 Yz11
The phase-bushings on a three phase transformer are marked either ABC, UVW or 123 (HV-side capital, LV-side small letters). Two winding, three phase transformers can be divided into four main categories Group Group I Group II Group III Group IV Oclock 0 oclock, 0 6 oclock, 180 1 oclock, -30 11 oclock, +30 TC delta/delta, star/star delta/delta, star/star star/delta, delta/star star/delta, delta/star
6/26
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
8/22/13
Clock Notation: 0
Clock Notation : 1
Clock Notation: 2
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/ 7/26
8/22/13
Clock Notation: 4
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
8/26
8/22/13
Clock Notation: 5
Clock Notation: 6
Clock Notation: 7
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
9/26
8/22/13
Clock Notation: 11
8/22/13
determine the phase-shift between primary and secondary. Transformer vector group depends upon Removing harmonics: Dy connection y winding nullifies 3rd harmonics, preventing it to be reflected on delta side. Parallel operations: All the transformers should have same vector group & polarity of the winding. Earth fault Relay: A Dd transformer does not have neutral. to restrict the earth faults in such systems, we may use zig zag wound transformer to create a neutral along with the earth fault relay.. Type of Non Liner Load: systems having different types of harmonics & non linear Types of loads e.g. furnace heaters ,VFDS etc for that we may use Dyn11, Dyn21, Dyn31 configuration, wherein, 30 deg. shifts of voltages nullifies the 3rd harmonics to zero in the supply system. Type of Transformer Application: Generally for Power export transformer i.e. generator side is connected in delta and load side is connected in star. For Power export import transformers i.e. in Transmission Purpose Transformer star star connection may be preferred by some since this avoids a grounding transformer on generator side and perhaps save on neutral insulation. Most of systems are running in this configuration. May be less harmful than operating delta system incorrectly. Yd or Dy connection is standard for all unit connected generators. There are a number of factors associated with transformer connections and may be useful in designing a system, and the application of the factors therefore determines the best selection of transformers. For example: For selecting Star Connection: A star connection presents a neutral. If the transformer also includes a delta winding, that neutral will be stable and can be grounded to become a reference for the system. A transformer with a star winding that does NOT include a delta does not present a stable neutral. Star-star transformers are used if there is a requirement to avoid a 30deg phase shift, if there is a desire to construct the three-phase transformer bank from single-phase transformers, or if the transformer is going to be switched on a single-pole basis (ie, one phase at a time), perhaps using manual switches. Star-star transformers are typically found in distribution applications, or in large sizes interconnecting high-voltage transmission systems. Some star-star transformers are equipped with a third winding connected in delta to stabilize the neutral. For selecting Delta Connection: A delta connection introduces a 30 electrical degree phase shift. A delta connection traps the flow of zero sequence currents. For selecting Delta-Star Connection: Delta-star transformers are the most common and most generally useful transformers. Delta-delta transformers may be chosen if there is no need for a stable neutral, or if there is a requirement to avoid a 30 electrical degree phase shift. The most common application of a deltadelta transformer is as tan isolation transformer for a power converter.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/ 11/26
8/22/13
For selecting Zig zag Connection: The Zig Zag winding reduces voltage unbalance in systems where the load is not equally distributed between phases, and permits neutral current loading with inherently low zero-sequence impedance. It is therefore often used for earthing transformers. Provision of a neutral earth point or points, where the neutral is referred to earth either directly or through impedance. Transformers are used to give the neutral point in the majority of systems. The star or interconnected star (Z) winding configurations give a neutral location. If for various reasons, only delta windings are used at a particular voltage level on a particular system, a neutral point can still be provided by a purpose-made transformer called a neutral earthing. For selecting Distribution Transformer: The first criterion to consider in choosing a vector group for a distribution transformer for a facility is to know whether we want a delta-star or star-star. Utilities often prefer star-star transformers, but these require 4-wire input feeders and 4-wire output feeders (i.e. incoming and outgoing neutral conductors). For distribution transformers within a facility, often delta-star are chosen because these transformers do not require 4-wire input; a 3-wire primary feeder circuit suffices to supply a 4-wire secondary circuit. That is because any zero sequence current required by the secondary to supply earth faults or unbalanced loads is supplied by the delta primary winding, and is not required from the upstream power source. The method of earthing on the secondary is independent of the primary for delta-star transformers. The second criterion to consider is what phase-shift you want between primary and secondary. For example, Dy11 and Dy5 transformers are both delta-star. If we dont care about the phase-shift, then either transformer will do the job. Phase-shift is important when we are paralleling sources. We want the phase-shifts of the sources to be identical. If we are paralleling transformers, then you want them to have the same the same vector group. If you are replacing a transformer, use the same vector group for the new transformer, otherwise the existing VTs and CTs used for protection and metering will not work properly. There is no technical difference between the one vector groups (i.e. Yd1) or another vector group (i.e. Yd11) in terms of performance. The only factor affecting the choice between one or the other is system phasing, ie whether parts of the network fed from the transformer need to operate in parallel with another source. It also matters if you have an auxiliary transformer connected to generator terminals. Vector matching at the auxiliary bus bar
8/22/13
Common for distribution transformers. Normally Dyn11 vector group using at distribution system. Because Generating Transformer are YNd1 for neutralizing the load angle between 11 and 1. We can use Dyn1 at distribution system, when we are using Generator Transformer are YNd11. In some industries 6 pulse electric drives are using due to this 5thharmonics will generate if we use Dyn1 it will be suppress the 5th harmonics. Star point facilitates mixed loading of three phase and single phase consumer connections. The delta winding carry third harmonics and stabilizes star point potential. A delta-Star connection is used for step-up generating stations. If HV winding is star connected there will be saving in cost of insulation. But delta connected HV winding is common in distribution network, for feeding motors and lighting loads from LV side.
8/22/13
(6) Yd5:
Mainly used for machine and main Transformer in large Power Station and Transmission Substation. The Neutral point can be loaded with rated Current.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
14/26
8/22/13
(7) Yz-5
For Distribution Transformer up to 250MVA for local distribution system. The Neutral point can be loaded with rated Current.
8/22/13
By doing some unconventional connections externally on one side of the Transformer, an internal connected Dyn1 transformer can be changed either to a Dyn5(-150) or Dyn9(+90) connection. (4) Group IV: Example: Dyn11 (+30 displacement between HV and LV). By doing some unconventional connections externally on one side of the Transformer, an internal connected Dyn11 transformer can be changed either to a Dyn7(+150) or Dyn3(-90) connection. Point to be remembered: For Group-III & Group-IV: By doing some unconventional connections externally on both sides of the Transformer, an internal connected Group-III or Group-IV transformer can be changed to any of these two groups. Thus by doing external changes on both sides of the Transformer an internal connected Dyn1 transformer can be changed to either a: Dyn3, Dyn5, Dyn7, Dyn9 or Dyn11 transformer, This is just true for star/delta or delta/star connections. For Group-I & Group-II: Changes for delta/delta or star/star transformers between Group-I and Group-III can just be done internally.
Why 30phase shift occur in star-delta transformer between primary and secondary?
The phase shift is a natural consequence of the delta connection. The currents entering or leaving the star winding of the transformer are in phase with the currents in the star windings. Therefore, the currents in the delta windings are also in phase with the currents in the star windings and obviously, the three currents are 120 electrical degrees apart. But the currents entering or leaving the transformer on the delta side are formed at the point where two of the windings comprising the delta come together each of those currents is the phasor sum of the currents in the adjacent windings. When you add together two currents that are 120 electrical degrees apart, the sum is inevitably shifted by 30 degrees.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
16/26
8/22/13
(http://electricalnotes.files.wordpress.com/2012/05/3333.jpg) The Main reason for this phenomenon is that the phase voltage lags line current by 30degrees.consider a delta/star transformer. The phase voltages in three phases of both primary and secondary. you will find that in primary the phase voltage and line voltages are same, let it be VRY(take one phase).but, the corresponding secondary will have the phase voltage only in its phase winding as it is star connected. the line voltage of star connected secondary and delta connected primary wont have any phase differences between them. so this can be summarized that the phase shift is associated with the wave forms of the three phase windings.
8/22/13
There is magnetic coupling between HT and LT. When the load side (LT) suffers some dip the LT current try to go out of phase with HT current, so 30 degree phase shift in Dyn-11 keeps the two currents in phase when there is dip. So the vector group at the generating station is important while selecting distribution Transformer.
8/22/13
output from the Transformer. If we use Yd1 Transformer on Generating Side and Distribution side Dy5 transformer than -30 lag of generating side (Yd1) is more lag by -150 Lag at Receiving side (Dy5) so Total phase difference respect to generating Side is 180 deg (-30+-150=-180) and if we are on the HV side of the Transformer, and if we denote the phases as R- Y-B from left to right, the same phases on the LV side will be R- Y -B, but from Right to Left. This will make the Transmission lines have No same color (for identification) whether it is input to or output from the Transformer. The difference in output between the Dyn11 and Dny5 and is therefore 180 degrees.
FILED UNDER UNCATEGORIZED About Jignesh.Parmar Jignesh Parmar has completed his B.E(Electrical) from Gujarat University. He has more than 11 years experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical Projects(Planning-Designing-coordination-Execution). He is Presently associate with one of the leading business group as a Assistant Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for "Electrical Mirror" and "Electrical India" Magazines. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.
In a system of 1 grid incomer connected to Dy11 transformer and a local generator connected to
19/26
8/22/13
In a system of 1 grid incomer connected to Dy11 transformer and a local generator connected to Dy1 transformer is it possible to synchronise the two incomers? Reply Hussain Shaik says: May 24, 2012 at 11:17 am Thank you so much for whatever you have, the best you are giving to us regarding the subject Transformers. Brother Jignesh, kindly provide a bit of ANSI Standard Transformer also in brief wherever it suits for the comparison of IEC Standards. Reply nikhil says: May 24, 2012 at 12:11 pm SIR PLEASE INSIST ME WHAT GRASE OF TRANSFORMER OIL SHOULD BE USED FOR 5 mva TRANSFORMER FOR 33 kV SUPPLY. Reply Priyanka says: June 2, 2012 at 5:07 am Thank you so much for this information Reply Tapani Julin says: June 8, 2012 at 12:02 pm Six Ways to wire Star Winding is very helpful to me,Honestly i dont know how to do it but because of it i learn thanks for a very good information. Reply Byju Ramachandrn says: July 1, 2012 at 8:03 am Dear Sir, I understood that the generator transformer vector group is delta at generator side and star in yard side. But in your article it is mentioned as reverse order. Please clarify Reply Jignesh.Parmar says: July 1, 2012 at 10:22 am As per IEC Vector group shown in HV winding / LV winding so i Generator transformer HV side is Transmission side and LV is Generator side. Reply k mohana krishna says: July 5, 2012 at 6:06 pm sir Iam an electrical engineer working in APTRANSCO, Sir I want to know the operation of OLTC in 100 mva power transformer with tap connection. we have 25 nos of taps with 21st tap as normal if
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/ 20/26
8/22/13
possible explain with sketch. Thanking sir K Mohana Krishna Reply Imranullah says: June 5, 2013 at 8:01 am Please see the Rating & Diagram plate of that (100 MVA) transformer. Reply rehan says: July 13, 2012 at 10:00 pm we good stuff i really liked that Reply SUJITH C NAIR ,KANHANGAD-KERALA says: September 15, 2012 at 11:50 am sir all the informations are 100% practical..thank you very much sir Reply randy addae junior says: October 17, 2012 at 5:11 pm I really like your diagrames and the explanations Reply jaswant singh bhamra says: October 22, 2012 at 8:29 am i really like your diagrames and the explanations jaswant singh bhamra senior test & commissioning sts switchgear uk Reply R.K.SHARMA says: October 22, 2012 at 4:34 pm Information quite useful.Can we use YD7 in place of Yd1 generator transformer. Reply ram says: October 28, 2012 at 6:00 am good job sir Reply Md. Anowarul Islam says: October 31, 2012 at 3:04 pm This is a fantastic tropics. But I want to know about the test methode and voltage relation of
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/
21/26
8/22/13
This is a fantastic tropics. But I want to know about the test methode and voltage relation of different type vector group. Reply umar says: November 4, 2012 at 4:53 pm sir what is matching factor in differential protection Reply Rashid says: November 6, 2012 at 5:57 am Please give the detail procedure of vector group test with the example of.Dyn1 Thanks. Rashid Reply SANTHOSH ESWARAN POTTY says: December 2, 2012 at 4:51 pm Use full information. Reply Ajay Shida says: December 24, 2012 at 6:18 am T hank you so much sir Reply Vinoth says: January 28, 2013 at 6:21 pm Nice information Reply Marios Moschakis says: February 24, 2013 at 12:30 am Dear Jignesh, Thank you for the interesting information about the selection of transformers vector group. I would like to add another interesting point: The positive effect and other characteristics of transformers of certain vector groups on the mitigation of voltage sags. This can be done by the positive effect of transformers of vector group 1, 5, 7 and 11 (e.g. Dy1, Yd5 etc) on asymmetrical faults and especially as regards one-phase-to-ground faults, which are the most frequent faults. Moreover, it can be proved that two-phase, two-phase-to-ground and three-phase faults at the one side of such transformers give the same sag magnitude at the other side of the transformer under common assumptions used in short-circuit analysis. I have published a journal and a conference paper on that effect.
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/ 22/26
8/22/13
Kind Regards, Dr. Marios Moschakis, Lecturer Department of Electrical Engineering Technological Educational Institute of Larissa, GREECE Reply M.Ali Imran says: March 7, 2013 at 12:12 pm sir, if i have a transformer of vector group Ynd11 on generating side.how can i take a neutral on LV side? Reply Siddavatam Nizamuddin says: March 24, 2013 at 6:40 am This is a good ready reference regarding vector group and selection of various vector groups. I would like to ask one thing regarding distribution transformers. As you know the distribution system normally on HV side connected in parallel and LV side radial. That means the LV of two transformers will never be connected in parallel. In that case, can we connect the two distribution transformers with different vector group in parallel? Reply sachin says: May 2, 2013 at 12:49 pm Dear sir,which vector group give highest secondary voltage? Reply Bino says: May 6, 2013 at 10:37 am what are the advantage of star star over delta star or vice versa? Reply sachidanand kumar says: May 6, 2013 at 11:08 am Thanks, To clearify my problem of vector grouptransformer? Reply Roman says: May 6, 2013 at 7:10 pm I do not even know how I ended up right here, but I assumed this submit used to be good. I dont know who youre however certainly youre going to a famous blogger when you are not already. Cheers! Reply power transformer says:
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/ 23/26
8/22/13
May 22, 2013 at 7:58 am I read this article and i realy appreciate your efforts.Thanks for sharing this information.This is very helpful for people Reply patomchon L says: June 4, 2013 at 4:32 am What s the difference in diagram between the Dyn11 and Dy11 Reply sunil says: June 5, 2013 at 9:38 am we want to step up 415volts to 11000volts for tunnel work. the transformer we have is star (LV) and Delta(HV). How to give earth fault protection? Reply Roop Bundele says: June 17, 2013 at 8:17 pm For Step up Transformer 415/11kV You would normally choose Yd11 or Yd1 or Yy0 or ( Yz1 or Yz11)( depending upon if it is likely to go in parallal with other existing supply at this voltage or further after steps up/down) instead of Dy11 or Dy1 for Earth fault Protection. As per IEC presentation of vector Group First letter represent High voltage winding Reply harish patel says: June 14, 2013 at 10:41 am dear sir will you explaine me formula kva=1.732*v*i*pf in which v=line voltage or phase voltage,i=line ampere or phase ampere,because as per my knownge v= avrage line to line voltage and i= avrage phase to phase current but i am facing problem from transformer manufacturer hope you do needful to me Reply javad ahamad says: June 19, 2013 at 7:55 am very nice information,but why we are sending with 30 deg lag in generation station??what is the point behind lagging while sending? Reply Jignesh.Parmar says: June 20, 2013 at 5:34 pm already given in post Reply Timika Laljie says:
electricalnotes.wordpress.com/2012/05/23/vector-group-of-transformer/ 24/26
8/22/13
June 24, 2013 at 5:51 pm dear sir am using the PSS Sincal software, and i cant figure out which group vector represents the single phase two winding transformer. please help Reply Courtney Powell says: June 27, 2013 at 5:42 am very helpful, thank you! Reply rajasekaran palani says: July 23, 2013 at 2:46 pm For a 5MVA, 0415/6.6KV, Whic h vector group I have to choose Please advise Reply natasha says: August 2, 2013 at 11:44 pm What are the only phase displacements in degrees with which it is possible to parallel the secondaries of two transformers? Reply Rags says: August 13, 2013 at 1:54 pm Does the downstream transformer vektor groups have an effect on fault currents. This is specifically as distance from the source and voltage levels have effect Reply Sujit Sengupta says: August 13, 2013 at 6:03 pm Great work Jignesh, I would like to connect with you, Sujit Sengupta, Reply anandkumar says: August 14, 2013 at 3:16 pm I learn more subject from you thanks Reply sandeep says: August 17, 2013 at 8:40 am Jignesh Sir, Thank u for good information. In star-star transformer how can we do vector group test??