FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II) DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 I ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CHECK ENT 2 3 4 MATERIAL UNLOADING & RECEIPT 1 CHECK PHYSICAL CONDITION OF CASES THAT THERE IS NO DAMAGE IN TRANSIT 2 CHECK CASE NO. & DETAIL OF EQUIPMENT VISUAL C CLASS 5

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 01 OF 13

PACKAGE: LT SWITCHGEAR QUANTUMM OF REFERENCE DOCUMENTS AND ACCEPTANCE NORMS CHECK 6 7

FORMAT OF RECORDS 8

100%

THERE SHOULD NOT BE ANY DAMAGE TO CASE

MATERIAL RECEIPT REGISTER AS PER DELIVERY CHALLAN

VISUAL

100%

DELIVERY CHALLAN

3 CHECK THAT PROPER CRANE ETC. ARE USED FOR UNLOADING OF EQUIPMENT 4 CHECK THAT ALL NECESSARY DOCUMENTS ARE AVAILABLE WITH THE CONSIGNMENT II STORAGE: 1 CHECK ADEQUECY & SUITABILITY OF STORAGE SPACE

VISUAL

100%

VISUAL

100%

PURCHASE ORDER

VISUAL

ONCE IN FORTNIGHT

STORAGE IN OPEN YARD, COVERED WITH SITE STORAGE LOG TARPOLIAN,SPACE SHOULD BE CLEAN AND FREE FROM BOOK HAZARDS, SECURE AND SHALL HAVE ADEQUECY FOR MOVEMENT OF EQUIPMENT. THE PACKING SHOULD BE INTACT AND CASES SHOULD BE PROPERLY COVERED WITH POLYTHENE APPROVED DRAWINGS ISSUE RECORD

2 CHECK CASE CONDITIONS

VISUAL

100%

3 CHECK THAT ONLY REQUIRED EQUIPMENT IS BROUGHT TO SITE FOR ERECTION

VISUAL

100%

CONTRACTOR

CONTRACTOR

SIGNATURE

SIGNATURE

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. FOR ADANI USE 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TCMANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK REVIEWED BY

DOC. NO.:

NAME & SIGN OF APPROVING AUTHORITY AND SEAL

NI/ J2648/ 800

No. - 4500018188

REMARKS 9

D SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FIELD QUALITY PLAN

FQP NO.ADANI/ J2648/ 800 REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II) DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 3 VISUAL 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 02 OF 13

PACKAGE: LT SWITCHGEAR QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS FREQUENCY OF CHECK 6 ONCE ALL ITEMS ARE RECEIVED, RANDOM CHECK DURING STORAGE 100% 7 8 SITE STORAGE LOG BOOK

2 4 FOR EASY IDENTIFICATION MARKS OR TAGS ARE KEPT INTACT

5 C

5 CHECK THAT ITEMS ARE STORED IN SYSTEMATIC WAY FOR EASY REMOVAL AND TO AVOID ANY DAMAGE. 6 CHECK THAT HEAVY PACKAGES ARE NOT STORED ONE ABOVE THE OTHER 7 CHECK THAT SUITABLE SLINGS ARE USED WHILE HANDLING OF EQUIPMENT AND THERE IS NO IMPACT ON PACKAGES. III PRE-ERECTION: 1 CHECK AVALABILITY OF ALL DOCUMENTS SPECIALLY BILL OF MATERIAL & LAYOUT DRAWING 2 CHECK FOUNDATION SITE AS PER LAYOUT DRAWING FOR VARIOUS OPENING CUTOUT AMENDMENT AND FOUNDATION BLOCK

VISUAL

DRAWINGS/ STORAGE INSTRUCTION

VISUAL

100%

DRAWINGS

VISUAL

100%

DRAWINGS

VISUAL

100%

LIST OF DRAWING

VISUAL

100%

SITE SHOULD BE FULLY CLEARED AND ALL CIVIL WORK IS COMPLETED.

CONTRACTOR

CONTRACTOR

SIGNATURE

SIGNATURE

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA FOR ADANI USE DOCUMENT. 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SRSITE REGISTER ;TR = TEST REPORT; TCMANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, REVIEWED BY LB = LOG BOOK

DOC. NO.:

NAME & SIGN OF APPROVING AUTHORITY AND SEAL

NI/ J2648/ 800

No. - 4500018188

REMARKS

SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II) DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CHECK ENT 3 LEVELLING 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 03 OF 13

PACKAGE: LT SWITCHGEAR QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS FREQUENCY OF CHECK 6 100% 7 LEVELLING OF FOUNDATION SHOULD BE PROPER 8 SITE LOG BOOK

2 3 CHECK THAT GROUNDING OF THE FOUNDATION SILL AND LEVEL ETC. ARE CORRECT 4 CHECK THAT ALL TOOLS AND TACKLES INSTRUMENTS ETC. REQUIRED FOR ERECTION ARE AVAILABLE AT SITE AND THAT THE MEASURING INSTRUMENTS ARE PROPERLY CALIBRATED/ TESTED. 5 CHECK THAT ALL NECESSARY ACCESSORIES ARE AVAILABLE AT SITE FOR CARRYING OUT NECESSARY TEST. 6 CHECK AVAILABILITY OF ALL ERECTION HARDWARES FOUNDATION BOLTS, TOUCH UP PAINTS ETC. 7 CHECK THAT POINT OF ELECTRICITY SUPPLY AVAILABLE FOR TESTING PURPOSE AT NEAREST PLACE 8 CHECK THAT PROPER SECURITY ARRANGEMENT IS THERE TO TAKE CARE OF EQUIPMENT AT ERECTION SITE

5 C

VISUAL

100%

LIST OF INSTRUMENTS

SITE LOG BOOK

VISUAL

100%

LIST OF INSTRUMENTS

SITE LOG BOOK

VISUAL

100%

DRAWINGS

VISUAL

100%

VISUAL

100%

CONTRACTOR

CONTRACTOR

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. 2. FOR ADANI USE CLASS OF CHECK - A,B,C NOTE:ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK

DOC. NO.:

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II) DATE: 11.05.2010

DATED 28.04.2010 ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA PAGE; 03 OF 13 PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL DOCUMENT. 2. CLASS OF CHECK A,B,C NOTE:ESTATE SIDCUL, HARIDWAR (U.P.) PACKAGE: LT SWITCHGEAR ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SL CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CLASS QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS SHALL NOT PROCEEDED TILL IT IS WITNESSED AND OF NO. CHECK ENT FREQUENCY CLEARED IN WRITING. SR- SITE CHECK REGISTER ;TR = TEST REPORT; TC- MANUFACTURER SIGNATURE SIGNATURE TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK NAME & SIGN OF APPROVING AUTHORITY AND SEAL REVIEWED BY

CONTRACTOR: ITEMS: LT SWITCHGEAR LEGEND:1. RECORD IDENTIFIED SUB CONTRACTOR: C&S ELECTRIC LTD.WITH TICK(X) SHALL

CONTRACT No. - 4500018188

NI/ J2648/ 800

No. - 4500018188

REMARKS

NI/ J2648/ 800

No. - 4500018188

REMARKS

SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 IV ERECTION: 1 CHECK THAT PRE LAYOUT SURVEY HAS BEEN CARRIED OUT AND NECESSARY MODIFICATION DONE TO VERIFY THE POSITION OF VARIOUS EQUIPMENTS TO BE CONNECTED. LEVEL OF FLOOR AND POSITION OF FOUNDATION BLOCKS & CUTOUTS. 2 CHECK THAT ONLY REQUIRED ASSEMBLIES AND COMPONENT ARE BROUGHT TO ERECTION SITE AT PARTICULAR STAGE. 3 CHECK THAT UNIPACKING THE PANEL AND ROLLING ON FOUNDATION IS DONE IN PROPER WAY. VISUAL C ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CHECK ENT 2 3 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 04 OF 13

PACKAGE: LT SWITCHGEAR QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS FREQUENCY OF CHECK 6 100% 7 AS PER APPROVED LAYOUT DRAWINGS 8 SITE LOG BOOK

REMARKS

VISUAL

100%

APPROVED DRAWINGS

ISSUE RECORD

VISUAL

100%

INSTRUCTION MANUAL

ISSUE RECORD

4 CHECK THAT THE LIFTING CEILLING CRANE ARE PUT PROPERLY TO AVOID ANY DISTORTION AND ALSO ENSURE TEMPORARY SUPPORT FOR SAFE LOADING AS MAY BE NECESSARY ARE READY BEFORE LIFTING THE ASSEMBLIES. 5 CHECK THAT THE CUBICLES ARE LIFTED ONLY BY MEANS OF LIFTING HOOK PROVIDED ON TOP. 6 CHECK THAT PROPER TOOLS AND TACKLE AND METHODS ARE USED FOR TRANSPORTING TO ERECTION SITE.

VISUAL

100%

INSTRUCTION MANUAL

VISUAL

100%

INSTRUCTION MANUAL

VISUAL

100%

INSTRUCTION MANUAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CHECK ENT CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 04 OF 13 REMARKS

CONTRACTOR

CONTRACTOR

SIGNATURE

SIGNATURE

PACKAGE: LT SWITCHGEAR QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS FREQUENCY OF CHECK LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. 2. FOR ADANI USE DOC. NO.: CLASS OF CHECK - A,B,C NOTE:ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK NAME & SIGN OF APPROVING AUTHORITY AND SEAL REVIEWED BY

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CHECK ENT 3 4 MEASUREM MEASURI ENT NG TAPE VISUAL CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 05 OF 13

QUANTUM/ FREQUENCY OF CHECK 6 100%

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS

REMARKS

2 7 CHECK THAT PANEL IS PLACED ON FOUNDATION PROPERLY AS PER DRAWING 8 CHECK CORRECTNESS OF PANELS AFTER JOINING OF SHIPPING SECTIONS

5 B

7 AS PER APPROVED LAYOUT DRAWINGS

100%

INSTRUCTION MANUAL

SITE LOG BOOK

9 CHECK THAT GASKET IS PROVIDED BETWEEN TO SHIPPING SECTIONS 10 CHECK THE EARTHING OF VARIOUS CUBICLES WITH MAIN EARTHING GRID AS PER APPROVED EARTHING LAYOUT DRAWINGS 11 CHECK THE POWER & CONTROL TERMINATION AS APPROVED EXTERNAL CONNECTION DIAGRAM. 12 CHECK ALL COMPONENTS AS PER DRAWING ARE AVAILABLE AND PROPERLY FITTED. 13 CHECK THE PHYSICAL CONDITION OF INSIDE CONNECTION AND OTHER COMPONENTS RECORD DAMAGE/ DISPLACEMENT IF ANY. 14 CHECK ALL THE BUSBAR SUPPORTS ARE INTACT AND HAVE NOT BEEN DAMAGED IN TRANSIT

VISUAL

100%

INSTRUCTION MANUAL

SITE LOG BOOK

VISUAL

100%

EARTHING LAYOUT DRAWING

SITE LOG BOOK

VISUAL

100%

APPROVED EXTERNAL CONNECTION DRAWING

SITE LOG BOOK

VISUAL

100%

BILL OF MATERIAL

SITE LOG BOOK

VISUAL

100%

APPROVED SLD, GA, SCHEME DRAWING

SITE LOG BOOK

VISUAL

100%

APPROVED SLD, GA, SCHEME DRAWING

SITE LOG BOOK

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA FOR ADANI USE DOCUMENT. 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SRSITE REGISTER ;TR = TEST REPORT; TCMANUFACTURER TEST CERTIFICATE; LR = LAB REPORT,

DOC. NO.:

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 05 OF 13 REMARKS

1. RECORD IDENTIFIED WITH TICK(X) SHALL ESTATE SIDCUL, LEGEND:HARIDWAR (U.P.) ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA SL CHARACTERISTICS/ ITEMS TYPE OF INSTRUM CLASS QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS DOCUMENT. NO. CHECK ENT FREQUENCY OF 2. CLASS OF CHECK - A,B,C CHECK CONTRACTOR CONTRACTOR NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SRSITE REGISTER ;TR = TEST REPORT; TCSIGNATURE SIGNATURE MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, NAME & SIGN OF APPROVING AUTHORITY AND SEAL REVIEWED BY LB = LOG BOOK

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 3 4 MEASUREM SPANNER/ ENT TORQUE WRENCH VISUAL AIR BLOWER/ VACCUM CLEANER CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 06 OF 13

QUANTUM/ FREQUENCY OF CHECK 6 100%

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS

REMARKS

1 2 15 CHECK THAT ALL FISH PLATES OF MAIN CONTROL AND EARTH BUS BARS ARE TIGHTENED PROPERLY 16 CHECK THAT THOROUGH CLEANING OF INSULATORS/ BUSBARS SUPPORT IS DONE

5 C

7 INSTRUCTION MANUAL

8 SITE LOG BOOK

100%

17 CHECK THAT ALL DOORS AND COVERS OF PANELS ARE CLOSED. 18 CHECK PROPER EARTH BUSBAR IS CONNECTED TO PLANTS MAIN EARTHING AT TWO SEPERATE POINTS 19 CHECK THAT EQUIPMENTS BASE STRUCTURE IS PROPERLY TAG WELDED TO THE FOUNDATION 20 CHECK TIGHTNESS OF BOLTED JOINTS OF BUSBARS BY TORQUE WRENCH.

VISUAL

100%

VISUAL

100%

EARTHING LAYOUT DRAWING

SITE LOG BOOK

VISUAL

100%

SITE LOG BOOK

VISUAL

100%

INSTRUCTION MANUAL

M6: 0.30-0.70 Kgf-m; M8: 1.25-2.50 Kgf-m; M10: 2.50-4.00 Kgf-m; M12: 4.30- 7.10 Kgf-m; SITE LOG BOOK

21 COMPONENTS OF ALL INSTALLATION OF COMPLETE SWITCHGEAR SYSTEM AT ALL LOCATION

VISUAL

100%

APPROVED GA, SLD, SCHEME DRAWING

CONTRACTOR

CONTRACTOR

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. 2. FOR ADANI USE CLASS OF CHECK - A,B,C NOTE:ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK

DOC. NO.:

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010 CONTRACT No. - 4500018188 DATED 28.04.2010

CONTRACTOR: ITEMS: LT SWITCHGEAR LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL SUB CONTRACTOR: C&S ELECTRIC LTD. ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA

DOCUMENT. 2. PAGE; 06 OF 13 PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL CLASS OF CHECK - A,B,C NOTE:ESTATE SIDCUL, ALL HARIDWAR (U.P.) 'B' CHECKS SHALL BE CHP AND WORK CLASS'A'AND SL CHARACTERISTICS/ ITEMS TYPENOT OF PROCEEDED INSTRUME TILL CLASS QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS SHALL IT IS WITNESSED AND NO. CHECK IN WRITING. NT FREQUENCY CLEARED SR- SITE OF CHECK REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK SIGNATURE SIGNATURE NAME & SIGN OF APPROVING AUTHORITY AND SEAL REVIEWED BY

REMARKS

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 V ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 2 PRECOMMISSIONING: 1 CHECK CLEANING OF POWER AND CONTROL TERMINATION. 2 CHECK ALL COMPONENTS THAT ARE MOUNTED ON THE PANEL ARE AS PER APPROVED DRAWINGS. 3 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 07 OF 13

QUANTUM/ FREQUENCY OF CHECK 6

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS

REMARKS

VISUAL

100%

PHYSICAL VERIFICATION

SITE LOG BOOK

VISUAL

100%

BILL OF MATERIAL/ DRAWINGS

3 CHECK ALL THE TERMINAL DETAILS AS PER APPROVED TERMINALS DRAWINGS

VISUAL

100%

TERMINAL DRAWING

4 TORQUE MEASUREMENT AND CHECK TIGHTNESS OF ACCESSIBLE BOLTED JOINT BY TORQUE WRENCH

TEST

TORQUE WRENCH

100%

INSTRUCTION MANUAL

5 CHECK ALL THE WIRING IS DONE AS PER APPLICABLE WIRING DIAGRAM.

VISUAL/ ELEC

100%

WIRING DIAGRAM

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA FOR ADANI USE DOCUMENT. 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK

DOC. NO.:

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 07 OF 13

PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESTATE SIDCUL, HARIDWAR (U.P.) ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA SL CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CLASS QUANTUM/ DOCUMENT. NO. CHECKOF CHECK NT - A,B,C FREQUENCY OF 2. CLASS CHECK NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND CONTRACTOR CONTRACTOR WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS

REMARKS

SIGNATURE

SIGNATURE

REVIEWED BY

NAME & SIGN OF APPROVING AUTHORITY AND SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 A CIRCUIT BREAKER: 1 CHECK ALIGNMENT OF BREAKER DRAWOUT ARRANGEMENT FOR FREE MOVEMENT. 2 CHECK CONTINUITY OF CONTROL WIRING FOR CORRECTNESS 3 CHECK CORRECT OPERATION OF THE SHUTTERS 4 MANUAL OPERATION OF BREAKER 5 POWER CLOSING/ OPENING OPERATION MANUALLY AND ELECTRICALLY PHYSICAL A ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 2 3 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 08 OF 13

QUANTUM/ FREQUENCY OF CHECK 6

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS

REMARKS

100%

IEC-947, GUARANTEED DATA/ OPERATION MANUAL/ APPROVED DRAWINGS. ..DO..

MFGR. TC

ELECTRICAL

100%

MFGR. TC

PHYSICAL

100%

..DO..

MFGR. TC

PHYSICAL PHYSICAL/ ELEC

A A

100% 100%

..DO.. ..DO..

MFGR. TC MFGR. TC

6 TRIP FREE AND ANTI PUMPING OPERATION 7 IR VALUE OF CONTACTS

ELECTRICAL

100%

..DO..

MFGR. TC

ELECTRICAL

100%

..DO..

MFGR. TC

CONTRACTOR SIGNATURE

CONTRACTOR SIGNATURE

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. FOR ADANI USE 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK REVIEWED BY

DOC. NO.:

NAME & SIGN OF APPROVING AUTHORITY AND SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 3 ELECTRICAL/ PHYSICAL 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 09 OF 13

QUANTUM/ FREQUENCY OF CHECK 6 100%

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF RECORDS

REMARKS

2 8 CHECK ELECTRICAL AND MECHANICAL INTERLOCKS PROVIDED

5 A

7 IEC-947, GUARANTEED DATA/ OPERATION MANUAL/ APPROVED DRAWINGS. ..DO..

8 MFGR. TC

9 CHECK SPRING CHARGING MOTOR ELECTRICAL CORRECT OPERATION OF LIMIT SWITCH 10 FUNCTIONAL TESTS ELECTRICAL

100%

MFGR. TC

100%

..DO..

MFGR. TC

CURRENT TRANSFORMERS 1 VISUAL INSPECTION VISUAL A 100% SPECS/ APPROVED DRAWING MFGR. TC

2 RATIO TEST

ELECTRICAL CURRENT INJECTION SET ELECTRICAL MEGGER

5%

IEC-185/ APPROVED DRAWING

MFGR. TC

3 IR VALUE

100%

..DO.. ..DO..

MFGR. TC

4 WIRING CONNECTION

VISUAL

100%

MFGR. TC

CONTRACTOR

CONTRACTOR

SIGNATURE

SIGNATURE

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. FOR ADANI USE 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SRSITE REGISTER ;TR = TEST REPORT; TCMANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK REVIEWED BY

DOC. NO.:

NAME & SIGN OF APPROVING AUTHORITY AND SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 C ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 2 VOLTAGE TRANSFORMERS 1 VISUAL INSPECTION 2 RATIO TEST 3 VISUAL ELECTRICAL VARIABLE VOLTAGE ELECTRICAL MEGGER VISUAL 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 10 OF 13

QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FREQUENCY OF CHECK 6 100% 100% 7 IEC-186 SPECS/ APPROVED DRAWINGS ..DO..

FORMAT OF RECORDS 8 MFGR. TC MFGR. TC

REMARKS

5 A A

3 IR VALUE 4 LINE CONNECTION AS PER CONNECTION DIAGRAM

A A

100% 100%

APPROVED DRAWING ..DO..

MFGR. TC MFGR. TC

CUBICLE WIRING 1 CONTINUITY TEST CHECKING OF WIRING ELECTRICAL AS PER DRAWING, CHECKING OF INTERCONNECTIONS BETWEEN PANELS/ EQUIPMENT 2 FUNCTION CHECK OF CONTROL ELECTRICAL CIRCUITS INCLUDING CLOSING TRIPPING CONTROL, INTERLOCK & ALARM CKT A 100% ..DO.. SITE LOG BOOK

100%

..DO..

SITE LOG BOOK

PROTECTION RELAY 1 CHECK WIRING CONNECTION 2 CHECK OPERATING CHARACTERISTICS BY SECONDARY INJECTION 3 CHECK OPERATION OF ELECTRICAL & MECHANICAL TARGET VISUAL ELECTRICAL A A 100% 5% ..DO.. ..DO.. SITE LOG BOOK SITE LOG BOOK

PHYSICAL

5%

..DO..

SITE LOG BOOK

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN FOR ADANI USE QA DOCUMENT. 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TCMANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK

DOC. NO.:

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 10 OF 13 REMARKS

RECORD IDENTIFIED WITH TICK(X) ESTATE SIDCUL, LEGEND:HARIDWAR1. (U.P.) SHALL BE INCLUDED IN REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD SL CHARACTERISTICS/ ITEMS TYPEESSENTIALLY OF INSTRUME CLASS BY SUPPLIER QUANTUM/ FORMAT OF QA DOCUMENT. NO. CHECK NT FREQUENCY RECORDS 2. CLASS OF CHECK - A,B,C OF CHECK NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP CONTRACTOR CONTRACTOR AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TCSIGNATURE SIGNATURE MANUFACTURER TEST CERTIFICATE; LR = LAB NAME & SIGN OF APPROVING AUTHORITY AND SEAL REVIEWED BY REPORT, LB = LOG BOOK

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 4 RELAY SETTING 5 CHECK VT & CT CONNECTION F METERS 1 FUNCTIONAL CHECK OF METERS BY CURRENT INJECTION 2 CHECK VT & CT CONNECTION 3 CALIBRATION ELECTRICAL STANDARD METER PHYSICAL ELECTRICAL CURRENT INJECTION SET/ VARIABLE VOLTAGE SOURCE A ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUMENT CHECK 2 3 PHYSICAL PHYSICAL 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 11 OF 13

QUANTUM/ FREQUENCY OF CHECK 6 100% 100%

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD

FORMAT OF RECORDS 8 SITE LOG BOOK SITE LOG BOOK

REMARKS

5 A A

7 APPROVED DRAWING ..DO..

5%

SUPPLIERS CERTIFICATE

SITE LOG BOOK

A A

100% 5%

APPROVED DRAWING SUPPLIERS CERTIFICATES

SITE LOG BOOK SITE LOG BOOK

CONTACTORS 1 CHECK VOLTAGE OF COIL 2 CHECK MINIMUM PICK UP & DROP OFF VOLTAGE OF COIL PHYSICAL ELECTRICAL A A 100% 5% IEC-947 IEC-947 SITE LOG BOOK SITE LOG BOOK

VI

COMMISSIONING GENERAL 1 CHECK NAME PLATE DETAIL ACCORDING TO APPROVED DRAWING 2 CHECK FOR PHYSICAL DAMAGE VISUAL A 100% APPROVED DRAWING SITE LOG BOOK

VISUAL

100%

PHYSICAL

CONTRACTOR

CONTRACTOR

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. FOR ADANI USE 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK

DOC. NO.:

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010 CONTRACT No. - 4500018188 DATED 28.04.2010

CONTRACTOR: ITEMS: LT SWITCHGEAR LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL SUB CONTRACTOR: C&S ELECTRIC LTD. ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA

DOCUMENT. PAGE; 11 OF 13 PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL 2. CLASS OF CHECK - A,B,C ESTATE SIDCUL, NOTE:HARIDWAR (U.P.) ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND SL CHARACTERISTICS/ ITEMS TYPE OF NOT INSTRUMENT CLASS QUANTUM/ REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD FORMAT OF WORK SHALL PROCEEDED TILL IT IS WITNESSED NO. CHECK FREQUENCY OF RECORDS AND CLEARED IN WRITING. SR- SITE CHECK REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK SIGNATURE SIGNATURE NAME & SIGN OF APPROVING AUTHORITY AND SEAL REVIEWED BY

REMARKS

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. 1 ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 3 4 MECHANICAL SCREW DRIVER/ TORQUE VISUAL VISUAL CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 12 OF 13

QUANTUM/ FREQUENCY OF CHECK 6 100%

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD

FORMAT OF RECORDS 8 SITE LOG BOOK

REMARKS

2 3 CHECK TIGHTNESS OF ALL BOLTS, CLAMPS AND CONNECTING TERMINALS

5 A

7 INSTRUCTION MANUAL

4 CHECK EARTH CONNECTION 5 CHECK CLEANLINESS OF INSULATORS/ BUS BAR SUPPORTS 6 CHECK HEATERS ARE PROVIDED 7 CHECK ALL PROTECTION RELAYS SETTING IS CORRECT 8 CHECK ALL PROTECTION RELAYS ETC. AND THEIR TESTING RESULTS ARE SATISFACTORY 9 CHECK THAT ALL CT SHORTINGS ARE REMOVED AND CONNECTED TO AMMETER RELAY

A A

100% 100%

APPROVED DRAWING PHYSICAL VERIFICATION

SITE LOG BOOK SITE LOG BOOK

VISUAL MECHANICAL SCREW DRIVER ELECTRICAL RELAY TESTER

A A

100% 100%

APPROVED DRAWING DESIGN DATA

SITE LOG BOOK SITE LOG BOOK

100%

MANUFACTURER GURANTEED PARTICULARS

SITE LOG BOOK

MECHANICAL SCREW DRIVER

100%

APPROVED DRAWINGS

SITE LOG BOOK

CONTRACTOR SIGNATURE

CONTRACTOR SIGNATURE

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. FOR ADANI USE 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK REVIEWED BY

DOC. NO.:

NAME & SIGN OF APPROVING AUTHORITY AND SEAL

CUSTOMER: PROJECT:

ADANI POWER MAHARASHTRA LTD.

FQP NO.ADANI/ J2648/ 800

FIELD QUALITY PLAN

REV. 00

TIRORA THERMAL POWER PROJECT,1980MW(2X660MW PHASE-I+1X660MW PHASE-II)

DATE: 11.05.2010

CONTRACTOR: SUB CONTRACTOR: C&S ELECTRIC LTD.


PLOT NO.1A/ 3 , SEC. 8C, INTEGRATED INDUSTRIAL SL NO. ESTATE SIDCUL, HARIDWAR (U.P.) CHARACTERISTICS/ ITEMS TYPE OF INSTRUME CHECK NT 3 VISUAL/ ELECTRICAL 4 CLASS

ITEMS: LT SWITCHGEAR

CONTRACT No. - 4500018188 DATED 28.04.2010 PAGE; 13 OF 13

QUANTUM/ FREQUENCY OF CHECK 6 20%

REFERENCE DOCUMENTS AND ACCEPTANCE STANDARD

FORMAT OF RECORDS 8 SITE LOG BOOK

REMARKS

1 2 10 CHECK MECHANICAL/ELECTRICAL INTERLOCKING OF COMPONENTS IS IN ORDER 11 CHECK THAT ALL DOORS AND COVERS OF EQUIPMENT ARE CLOSED PROPERLY 12 CHECK IR VALUE OF EQUIPMENT 13 CHECK THAT ALL FEEDERS ARE OFF 14 CHECK THAT ALL POWER AND CONTROL CABLE TERMINATION ARE CORRECT AND FULLY TIGHTNESS AT BOTH ENDS

5 A

7 APPROVED DRAWINGS

VISUAL

100%

SITE LOG BOOK

ELECTRICAL VISUAL PHYSICAL

MEGGER

A A A

100% 100% 100%

IEC-947

SITE LOG BOOK SITE LOG BOOK

INSTRUCTION MANUAL

SITE LOG BOOK

15 IR-HV-IR TEST

ELECTRICAL

MEGGER/ HV TESTER

100%

INSTRUCTION MANUAL

CONTRACTOR SIGNATURE

CONTRACTOR SIGNATURE

LEGEND:- 1. RECORD IDENTIFIED WITH TICK(X) SHALL ESSENTIALLY BE INCLUDED BY SUPPLIER IN QA DOCUMENT. FOR ADANI USE 2. CLASS OF CHECK - A,B,C NOTE:- ALL CLASS'A'AND 'B' CHECKS SHALL BE CHP AND WORK SHALL NOT PROCEEDED TILL IT IS WITNESSED AND CLEARED IN WRITING. SR- SITE REGISTER ;TR = TEST REPORT; TC- MANUFACTURER TEST CERTIFICATE; LR = LAB REPORT, LB = LOG BOOK REVIEWED BY

DOC. NO.: