B. Water Flow Switches: 1. Paddle type for pipe sizes 1-1/4 inches through 2 inches: a.

Rated for 175 psi working pressure. b. Two sets 120 VAC - 24 VDC form C contacts. c. Compatible for use with fire alarm system. d. To be connected to the fire alarm system. 2. Paddle Type for pipe sizes 2 inches through 8 inches, with 0 - 70 second adjustable pneumatic retard. a. Rated for 175 psi working pressure. b. Two sets 120 VAC - 24 VDC form C contacts. c. Compatible for use with fire alarm system. d. To be connected to the fire alarm system. 12.2.08 SYSTEM ACCESSORIES

A. Combination Test and Drain Connection: 1. 2. 3. Manufactured combination test, drain, and sight glass fitting. 175 psi working pressure. 1/4 inch NPT gauge fitting.

B. Pressure Gauges: 3-1/2 inch dial marked in pound increments. 1. 2. 1/4 inch NPT. 250 psi working pressure.

Pressure gauges shall be provided on the discharge of the pumps and on wet pipe sprinkler system riser as shown on the drawing. Each gauge shall not be less than 100 mm dia in dial size and shall comprise of a corrosion resistant housing with glass window and brass trim. It shall have accuracy within +/-5% of the full-scale deflection when working at 50 degree C. Each gauge shall be provided with a gauge cock. The pressure gauges shall be calibrated in psi or bars, or both. Each gauge shall have a range of 0 to 11/2 times the normal working pressure. C. Automatic Ball Drips: 1/2 inch or 3/4 inch NPT.