GE Multilin

MODEL: MIFIIPI00E20**00 v4.01 FILE: C:\GE Power Management\MIIPC\files\Settings\220kV Temp Ghazi-KSK MIFII.ajs DATE: 05/09/13 1:13:52 PM

MIIPC

Setpoint
PRODUCT SETUP Relay Operation Frequency Phase CT Type Ground CT Type Phase CT Ratio Ground CT Ratio READY 50 5A 5A 600 600

PHASE TOC 51P Trip Enable 51P Pickup 51P Curve 51P TD Mult 51P Def Time 51P Yes 1.5 In DEFINITE TIME .19 .8 s

GROUND TOC 51G Trip Enable 51G Pickup 51G Curve 51G TD Mult 51G Def Time 51G Yes .2 In DEFINITE TIME .2 .8 s

PHASE IOC 50P1 Trip Enable 50P1 Pickup 50P1 Delay 50P1 No 3 In 0s

PHASE IOC 50P2 Trip Enable 50P2 Pickup 50P2 Delay 50P2 No 1 In 0s

GROUND IOC 50G1 Trip Enable 50G1 Pickup 50G1 Delay 50G1 No 1 In 0s

GROUND IOC 50G2 Trip Enable 50G2 Pickup 50G2 Delay 50G2 No 1 In 0s

THERMAL MODEL 49 Trip Enable 49 Pickup 49 Alarm Level 49 Heat Time 49 Cool Time 49 No .5 In 80 % 6 min 1 T1

ADV. GENERAL SETTINGS IDENTIFICATION Settings Group Trip Min Time MIF II 1 200 ms

GE Multilin

MIIPC

PHASE TOC 51P (group 2) Trip Enable 51P T2 Pickup 51P T2 Curve 51P T2 TD Mult 51P T2 Def Time 51P T2 No .5 In DEFINITE TIME .5 1s

GROUND TOC 51G (group 2) Trip Enable 51G T2 Pickup 51G T2 Curve 51G T2 TD Mult 51G T2 Def Time 51G T2 No .5 In DEFINITE TIME .5 1s

PHASE IOC 50P1 (group 2) Trip Enable 50P1 T2 Pickup 50P1 T2 Delay 50P1 T2 No 1 In 0s

PHASE IOC 50P2 (group 2) Trip Enable 50P2 T2 Pickup 50P2 T2 Delay 50P2 T2 No 1 In 0s

GROUND IOC 50G1 (group 2) Trip Enable 50G1 T2 Pickup 50G1 T2 Delay 50G1 T2 No 1 In 0s

GROUND IOC 50G2 (group 2) Trip Enable 50G2 T2 Pickup 50G2 T2 Delay 50G2 T2 No 1 In 0s

THERMAL MODEL 49 (group 2) Trip Enable 49 Pickup 49 T2 Alarm Level 49 T2 Heat Time 49 T2 Cool Time 49 T2 No 1 In 80 % 6 min 1 T1

USER CURVE A Parameter B Parameter P Parameter Q Parameter K Parameter .05 s 0s .04 1 0s

EVENT MASK 50P1 Pickup 50G1 Pickup 51P Pickup 51G Pickup 50P2 Pickup 50G2 Pickup 49 Alarm 50P1 disabled (by DI) 50P2 disabled (by DI) 50G1 disabled (by DI) No No No No No No No No No No

GE Multilin
50G2 disabled (by DI) 51P disabled (by DI) 51G disabled (by DI) 49 disabled (by DI) Trip disabled (by DI) 50P1 Trip 50G1 Trip 51P Trip 51G Trip 50P2 Trip 50G2 Trip 49 Trip General trip Protection status Output 1 Output 2 Output 3 Output 4 Digital Input 1 Digital Input 2 Sett. change disable Trip operation by input Trip operation by command Reset latch aux Close Breaker operation Settings group change Oscillo trigg by DI Oscillo trigg by comm Cold load Pickup Breaker 52A Breaker 52B Breaker Closed BF to open I^2 Alarm Settings change EEPROM Failure User settings No No No No No No No No No No No No Yes No No No No No No No No No No No No No No No No No No No No No No No No

MIIPC

OSCILLOGRAPHY MASK Oscillo by communic. Oscillo by digital input Oscillo by tripping Oscillo by pickup No No Yes Yes

COUNTERS I^2 MAX Value 999 kA2

COLD LOAD PICKUP Function Outage Time On Load Time Phase IOC Mult Phase TOC Mult No 2s 1s 1 1

BF TO OPEN Function Delay No 400 ms