TITLE : RELAY SETTING CALCULATIONS FOR GENERATOR RELAY PANEL FOR KOTHAGUDEM TPP

DOCUMENT NO. PE-DC-274-510-E014 REV NO. : 0 DATE : 04.09.2010 SHEET : 10 OF 16

GENERATOR VT VOLTAGE SUPPLY SUPERVISION RELAY (60VT1, 60VT2 & 60VT3) DEVICE NO. TYPE OF RELAY RATED VOLTAGE NO SETTING IS REQUIRED ON THE RELAY GENERATOR PROTECTION RELAY (64G/ 64R) DEVICE NO. TYPE OF RELAY : : 64G/R REG316 : : : 60VT1, 60VT2 & 60VT3 MVAPM32 110V

A) 100% GENERATOR STATOR EARTH FAULT PROTECTION (64G) NGT ratio, N1/N2 = 21kV / 220 V CONDITION 1: MAX. STAR POINT CURRENT, IEmax REs + RPs CONDITION 2: INJECTION VOLTAGE, Uis = 1.7 V

7.8 A

170.6 m

23.12 m and RPs 31.01 m RPs ASSUMING RPs = 25 m


CONDITION 3: REs 4.5 x RPs 112.5 m and REs 5 k x

548.75 m

In order to fulfill conditions 1, 2 and 3 : REs = 150 m MTR ratio =

1.27

CONDITION 4: 0.8 x n, where n = 1.2 x n The ratio selected fulfills the condition 4. REs = REs x = 1367 MTR = MTR x = 82 SETTINGS SELECTED : REs Measurement transformer ratio, MTR ALARM STAGE Alarm setting, Rfs Time setting, Alarm Delay TRIP STAGE Trip setting, Rfs Time setting, Trip Delay

= 1.08

: : : : : :

1.4 k 82 5.0 k 2.0 SECONDS 0.5 k 1.0 SECONDS