Sei sulla pagina 1di 1

TEC NPSH Calculation PUMP Selection

Date: Job Name: Drawings / Page: Max GPM:

7/5/2013 21:25 Address:

NPSH Calculation

Constants / Assumptions:
Mean Operating Fluid Temperature: 45 F Total Flow Through Pump: Vapor Pressure of Liquid: 0 gpm 0.75 ft. water Atmospheric Pressure: Surface Pressure: 14.70 PSIA 20 PSIG 33.96 ft. Water (if exposed to air surface pressure = 0)

Pumped Fluid: WATER

Piping Configuration:
Pipe Sub System#: Pipe Diam. (Nom): Pipe Length: Flow Rate: Pipe Pressure Drop: Valves (Fully Open) / Fittings 1 Eq. Length Total 20 20 16 0 340 340 150 0 8 0 29.9 0 55 0 20 0 60 0 0 0 360 2 Eq. Length 20 16 340 150 8 29.9 55 20 60 0 3 Eq. Length 20 16 340 150 8 29.9 55 20 60 0 4 Eq. Length 20 16 340 150 8 29.9 55 20 60 0 5 Eq. Length 20 16 340 150 8 29.9 55 20 60 0 6 Eq. Length 20 16 340 150 8 29.9 55 20 60 0 1 3 inch 100 feet 100 gpm 1.9 ft. Water 0.8 psi 0.0 0.0 2 1 inch 0 feet 0 gpm ft. Water psi 0.0 0.0 3 1 inch 0 feet 0 gpm ft. Water psi 0.0 0.0 1 inch 0 feet 0 gpm ft. Water psi 0.0 0.0 4 1 inch 0 feet 0 gpm ft. Water psi 0.0 0.0 5 1 inch 0 feet 0 gpm ft. Water psi Total 1.9 0.8 6

90 Ells 45 Ell Globe Valve Angle Valve Ball Valve BF-Valve Ck-Valve Stand. Tee - flow through run Stand. Tee - flow through branch Eq. Length Total:

Qt. 1 0 1 0 0 0 0 0 0 0

Qt. 0 0 0 0 0 0 0 0 0 0

Total 0 0 0 0 0 0 0 0 0 0 0

Qt. 0 0 0 0 0 0 0 0 0 0

Total 0 0 0 0 0 0 0 0 0 0 0

Qt. 0 0 0 0 0 0 0 0 0 0

Total 0 0 0 0 0 0 0 0 0 0 0

Qt. 0 0 0 0 0 0 0 0 0 0

Total 0 0 0 0 0 0 0 0 0 0 0

Qt. 0 0 0 0 0 0 0 0 0 0

Total 0 0 0 0 0 0 0 0 0 0 0

Total 360 1.8 0.8

Fitting Pressure Drop: 1.8 ft. water 0.8 psi

0.0 0.0 Description input here input here input here input here input here

ft. water psi

0.0 0.0

ft. water psi

0.0 0.0

ft. water psi

0.0 0.0

ft. water psi

0.0 0.0

ft. water psi

Additonal Pressure Drops:

Total:

0.0 0.0 0.0 0.0 0.0 0.0

ft. water ft. water ft. water ft. water ft. water ft. water

Total Head Loss (Pipe + Fittings + Additional Drops) :

361.9

Results
(Static Head) (Vapor Pressure) (Loss in Fittings) 1.9 (Loss in Pipe Length) NPSHA

NPSHA
Net Positive Suction Head Available

= 34.0 + (Atmospheric Pressure)

100.0

20.0 (Surface Pressure)

0.8

1.8

0.0 (Additonal Loss)

149.52 ft. Water

Pump Schedule #: MFR: Model #:

NPSHR Net Positive Suction Head Required (From Pump Curve)

ft. Water

Safety Factor Enter NPSHR

Air Systems Confidential

7/5/2013

Page 1