Basic Parameters

Boiler Operators Training


Programme

D D Ananda Namal
MEng.(Energy Technology), BSc(Hon)Eng,, CEng, MIE(SL)

DG - NERDC
President- SLEMA

tilla@sltnet.lk

0112236434(O), 0115854302 (R)

Pressure , Temperature, Heat , Volume, Capacity


Boiling Point

1 bar
1 bar
1 psi

= 100
= 14.7
= 2.31

1 kg

= 2.2 lb

kPa
psi
Water feet

0777640187 0718001900
1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

1/28/2011 6:51:59 AM

Steam Basic

D D Ananda Namal - 0115854374,


0777640187

What is Steam

What is steam
Change of state with Heat
Steam properties

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

Properties of Steam

Properties of Steam
Temperature of Steam
200

3000
2500
2000
1500
1000
500
0

Tem perature o C

k J /k g

Heat Content of Steam


150
100

Latent Heat

Sinsible Heat

10

50
0
0

Pressure -Barg
1/28/2011 6:51:59 AM

10

Pressure Barg

D D Ananda Namal - 0115854374,


0777640187

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

Properties of Steam

Basic Boiler Operation


Specific Volume of Steam

2.0

m /k g

1.5
3

1.0
0.5
0.0
0

10

Pressure - Barg
1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

BOILER CLASSIFICATION

CLASSIFICATION BY DESIGN
FIRE TUBE
WATER TUBE
COMBINATION
TUBELESS

BOILERS ARE CLASSIFIED BY,


THE DESIGN

CLASSIFICATION BY NO. OF PASSES


SINGLE PASS
TWO PASS
THREE PASS
FOUR PASS

NO. OF PASSES OF THE FLUE GAS


TYPES OF FUEL USED
LOCATION AND WAY OF FABRICATION
CONDITION OF STEAM
1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

CLASSIFICATION BY FUEL
LIQUID FUEL
NUCLEAR
GAS
WASTE HEAT
SOLID
ELECTRIC
MULTI FUEL
FLUIDISED BED

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

10

CLASSIFICATION BY CONDITION OF STEAM


SATURATED STEAM
SUPER HEATED STEAM
HOT WATER

CLASSIFICATION BY LOCATION & METHOD OF


FABRICATION
PACKAGE
IN SITE
HORIZONTAL
VERTICAL
1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

11

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

12

CONVENTIONAL 3 PASS BOILER- FRONT VIEW

CONVENTIONAL THREE PASS BOILER

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

13

REVERSE FLAME 3 PASS BOILER

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

14

REVERSE FLAME 3 PASS BOILER-FRONT VIEW

15

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

16

Two Pass Boiler

Packaged Boiler

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

17

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

18

Wet back and Dry back Boilers


Three Pass Boiler

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

19

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

20

Boiler Task

Reverse Flame Boiler

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

21

1/28/2011 6:51:59 AM

Boiler Control
Safety trouble free operation
Excessive Pressure
Low water level
Gas Explosion
Pressure control
Water level control
Back Fire

D D Ananda Namal - 0115854374,


0777640187

D D Ananda Namal - 0115854374,


0777640187

22

Pressure Control

1/28/2011 6:51:59 AM

To provide steam
High quality
Correct amount
Correct Pressure
Safely
Efficiently

23

Pressure Switch
To control Burner
High pressure cut off
High pressure alarm

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

24

Water Level Control

Sequence of operation

Float Switch
High Water level Feed pump Stop
Low level Feed pump start
Low water alarm
Low water burner cut off

Back Fire, Gas Explosion

check water level and operate water pump


Operate fuel heater
Operate burner blower (Purging)
Operate fuel supply, spark and flame
Burner cut of at high pressure setting
Repeat the cycle at low pressure setting

Photo electric cell


Purge cycle
1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

25

0777640187

D D Ananda Namal - 0115854374,


0777640187

26

Level Gauge

BOILER ACCESSORIES
BLOW DOWN VALVE
WATER LEVEL CONTROL
WATER LEVEL GAUGE GLASSES
FEED WATER PUMP
PRESSURE CONTROLS
PRESSURE GAUGES
VALVES
MAIN STOP VALVES
CONTROL PANEL
WATER SOFTENER
BURNER
AM
ECONOMISER
1/28/2011 6:51:59
D D Ananda Namal - 0115854374,

1/28/2011 6:51:59 AM

Connect between steam and water space


50 mm above the tube
new glass is required when erosion/corrosion
detect
When cleaning - Temporally shut off valves
Testing steam connection Shut WC
Testing water connection Shut SC
Choked SC indicate high water level
Choked WC - low or high water level

27

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

28

Level Gauge - Testing

Safety Valve

Close the WC, open the DC


Close the WC, open the DC (WC Choke)
Close the SC, open the DC
Close the DC, open the SC (SC choke)

Capacity
Minimum Bore 20 mm
Discharge Pipe Un obstructed, Drained
hole at the base

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

29

Pressure Gauge

D D Ananda Namal - 0115854374,


0777640187

D D Ananda Namal - 0115854374,


0777640187

30

Feed water Pump

Dial > 150 mm


Marking- WP, Max P
Siphon tube or U tube

1/28/2011 6:51:59 AM

1/28/2011 6:51:59 AM

High Pressure
NRV Spring equivalent to Elevation of
FWT
Cavitations

31

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

32

Main Valve

Boiler Water

Opening
Size

Blow Down Valve

Make up Water
Feed Water
Boiler Water

Purpose
Method
Outlet

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

33

1/28/2011 6:51:59 AM

Impurities in Water

Mud and sand


Ca and Mg Ions
Floating Oil and Dust
Acid
DO

Hard Water Ca and Mg So4 - Scaling


Soft Water Ca and Mg Co3

D D Ananda Namal - 0115854374,


0777640187

34

Effect of Impurities
in Water

Hard Water - Scaling


Acidic Water - Corrosion
Oxygen - Corrosion
Chorine - Corrosion

Impurities in Water

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

35

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

36

Boiler Operator

Boiler Carry Over

Priming
High water level
Operating the boiler below designed pressure
Higher Steam Demand
Foaming
Impurities
High TDS
Effect of forming

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

37

Class 1 Less than 2000 lb/hr


Class 2 2000 to 6000 lb/hr
Class 3 greater than 6000 lb/hr

Boiler Attendant Certificate

Experience
Class III - one year +
Class II - three years +
Class I - six years +
1/28/2011 6:51:59 AM

Boiler Operator

Boiler Attendant Certificate

Experience
Class III - one year +
Class II - three years +
Class I - six years +
D D Ananda Namal - 0115854374,
0777640187

38

&``&

Class 1 Less than 2000 lb/hr


Class 2 2000 to 6000 lb/hr
Class 3 greater than 6000 lb/hr

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

39

$<
<$ $& $<
$<
< $<

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

40

10

&``&

&``&

&$

$&<

$< < $$&


< , ` $
$ (Ignition Electrode) &

&$$$ <| < (Solonoide Valve)


$$< $

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

41

1/28/2011 6:51:59 AM

42

$ &$$ ` { .
<` &{ $ ` $ <` .

$& <

\ &

$& <
< $ operation within the range
$
&_ $ $

D D Ananda Namal - 0115854374,


0777640187

D D Ananda Namal - 0115854374,


0777640187

$ &{ `

&``&

1/28/2011 6:51:59 AM

$ ` &
< &> &
&> &
$ (Safety Valve) $
$ &

43

{$

<
<${ <$ <

<
&

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

44

11

1/28/2011 6:51:59 AM

D D Ananda Namal - 0115854374,


0777640187

45

12