SPIN-IN FITTING WITH DAMPER AND 45 EXTRACTOR

45 EXTRACTOR

FLEXIBLE DUCT OVER RIGID DUCT WITH METAL BAND, "KRIMP" RIGID DUCT AS REQUIRED
INSULATED FLEXIBLE DUCT (MAXIMUM 8'-0" IN LENGTH)

354 Pennsylvania Ave. Centreville, MD 21617 phone 410.758.1000 fax 410.758.1002

1" DUCTWRAP INSULATION WITH FOIL VAPOR BARRIER SPIN-IN FITTING WITH INTEGRAL DAMPER AND 45 DEGREE EXTRACTOR (REFER TO SPIN-IN FITTING DETAIL)
FOIL TAPE

STRAINER W/BLOWDOWN

TRIPLE DUTY VALVE OR PROVIDE NON-SLAM CHECK VALVE, FLOW METER AND ISOLATION VALVE.

SHEET METAL PLENUM WITH 1/2" ACOUSTIC LINING. FULL SIZE OF DIFFUSER AND 2" HIGHER THAN NOTED TAP SIZE. SUPPLY TAP SUPPLY TAP

Salisbury, Maryland 21801 Tel: 410.341.0200 Fax: 410.341.0400

205 East Market Street

FLEXIBLE DUCT (6'-0" MAX. LENGTH)

DAMPER OPERATOR ROUND RIGID DUCTWORK

T-BAR DIFFUSER WITH INTERNAL INSULATION (25 NC MAX. @ GIVEN AIR QUANTITIES, SEE PLANS)
SUPPLY INLET

FLEXIBLE CONNECTORS

REDUCERS OR INCREASERS AS REQUIRED PUMP AS SCHEDULED PUMP BASEPLATE CONCRETE HOUSEKEEPING PAD

CEILING LINEAR BAR DIFFUSER SIDE VIEW LENGTH x WIDTH 48"x4"-300 TOTAL CFM END VIEW

CEILING LINEAR BAR DIFFUSER

SPIN-IN FITTING DETAIL


NO SCALE

SUCTION DIFFUSER

NOTES:
1. USE SPIN-IN FITTING WHERE TAP SIZE IS 2" SMALLER THAN DUCT RAIL DIMENSION. 2. WHERE TAP SIZE IS 3" SMALLER THAN DUCT RAIL DIMENSION BELLMOUTH FITTING MAY BE USED. 3. PROVIDE DAMPER ONLY AT LOCATIONS INDICATED ON THE DRAWINGS WHERE ACCESS IS POSSIBLE.
METAL BANDS (TYPICAL) SUPPLY AIR DUCT

LINEAR BAR DIFFUSER KEY


NO SCALE

ROUND RIGID SUPPLY DUCT WITH 1" FLEXIBLE DUCT WRAP "KRIMP" END AS REQUIRED

6'-0 " MA XI M UM

SHEET METAL SPACER (DAMPER OPERATOR TO CLEAR INSULATION) RIVET OR SHEET METAL SCREW

EXTENDED FULL SIZE TO DRAIN ADJUSTABLE SUPPORT LEG

INLINE PUMP

STRAINER

VIBRATION ISOLATORS-TYP.

1 PRESSURE GAUGE WITH NEEDLE VALVE AND SNUBBER-TYP. FLOW METER: CIRCUIT SETTER FOR SIZES 2" & SMALLER CIRCUIT SENSOR 2 1/2" & UP

20 GAUGE X 1" METAL STRAP CONNECTED TO STRUCTURE ABOVE (TYPICAL) THROUGH BOLT

FLEXIBLE DUCT WITH LINEAR SUPPLY AIR DIFFUSER DETAIL


NO SCALE

PIPING CONNECTIONS AT BASE MOUNTED END SUCTION PUMP(S)


NO SCALE OUTSIDE DUCT DIMENSION = INSIDE DIMENSION + 2 (FOR 1" SOUNDLINING ONLY) 18 GAUGE SHEET METAL 6" WIDE AND INSTALLED CONTINUOUSLY AROUND LINING END

ISOLATION VALVE

NOTE:

PIPING CONNECTIONS AT INLINE PUMPS


NO SCALE RFHW MAINS
1/2" NORMALLY CLOSED BYPASS FOR FLUSHING
CW MAINS

1. DIFFUSER SHALL BE COMPLETE WITH CENTER "T"-BAR AND OUTER "T"-BAR (ON INLET SIDE).
DRAW THRU UNITS A = STATIC PRESSURE OF AHU IN INCHES OF WATER X 1.25 B = 2 INCHES MINIMUM BLOW THRU UNITS A = 2 INCHES MINIMUM B = STATIC PRESSURE OF AHU IN INCHES OF WATER X 1.25 PLUG

6'-0 "M

AX IMU M

INSULATION ROUND DUCT

N.C.

FLOW METER: CIRCUIT SETTER FOR SIZES 2" & SMALLER CIRCUIT SENSOR- 21/2" & UP 1/2" GAUGE VALVE CONNECTION - TYP. MANUAL AIR VENT

SPEED WASHER

MAX. SAG 1/2" PER FOOT OF SUPPORT SPACING.

UNION 6" PITCH DOWN

FULLY INSULATED DRAIN PAN

NOMINAL DUCT SIZE SHOWN ON PLAN, FREE AREA INSIDE DUCT

FLEXIBLE DUCT RUN-OUT SUPPORT DETAIL


NO SCALE

CLEAN OUT

A TRAP IS TO BE THE SAME DIAMETER AS THE PAN CONNECTION B

SPOT WELD DUCT TO DUCT

1/2" NORMALLY CLOSED BYPASS FOR FLUSHING

N.C.

ISOLATION VALVE - TYP.

TO TEMPERATURE SENSOR

AIR FLOW

SOUNDLINER DETAIL
TERMINATE SLEEVE FLUSH WITH FINISHED WALL SURFACES SEAL OR CAULK SLEEVES THRU FIRE WALLS IN A SMOKE TIGHT MANNER

WELDED PIN

N.O.

NO SCALE

NOTES:
1. FLEXIBLE DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM RECTANGULAR DUCT CONNECTION BEFORE BENDING. 2. FLEXIBLE DUCT SHOULD NOT EXCEED 6'-0" IN LENGTH. USE RIGID ROUND DUCTWORK WHEN RUNOUTS EXCEED 6'-0".

TO FLOOR DRAIN (PIPING SIZE EQUAL)

AUTO-CHANGE OVER COIL ISOLATION CONTROL VALVE - TYP.


STANDARD WEIGHT STEEL PIPE SLEEVE OF SIZE TO PASS PIPE AND INSULATION

STRAINER

3/4" HOSE END DRAIN VALVE TWO WAY AUTOMATIC TEMP. CONTROL VALVE 8 FT. MAX P.D. 4 FT. MIN P.D.
Project Number:

COOLING COIL CONDENSATE TRAP


SOUNDLINED OR INSULATED SUPPLY AIR DUCT. SEE DRAWINGS FOR SIZE.

FAN COIL UNIT 6 THRU 10 CHILLED WATER COIL CONNECTION DETAIL


NO SCALE

NO SCALE

A0601
Date:

NOTE:
SUPPLY AIR DIFFUSER

NOTE:
PIPE AND INSULATION TO BE CENTERED IN SLEEVE - DO NOT SUPPORT PIPE FROM SLEEVE INTERIOR WALLS

PROVIDE INTERMEDIATE DRAIN PAN FOR MULTIPLE (STACKED) COOLING COILS. PIPE INTERMEDIATE DRAIN PAN TO BOTTOM DRAIN PAN
COMBINATION REDUCING/RELIEF VALVE WITH BUILT IN STRAINER AND CHECK VALVE. PROVIDE FAST FILL FEATURE.

RIGID DUCT WITH INSULATION SAME SIZE AS FLEX DUCT. LENGTH NECESSARY TO MEET MAXIMUM FLEX DUCT LENGTH REQUIREMENTS FLEX DUCT (6'-0" MAX) EXTERNALLY INSULATED HOSE CLAMPS (TYP. 2 PL)

1. HEATING WATER SUPPLY CONNECTION SHALL BE UPSTREAM OF AIR FLOW. 2. PROVIDE A THREE WAY CONTROL VALVE ON THE LAST FAN COIL UNIT IN EACH PIPING LOOP. 3. THIS DETAIL APPLIES TO FAN COIL UNITS 6 THRU 10 CHILLED WATER COILS ONLY, SEE "TYPICAL FAN COIL CONNECTION DETAIL" FOR ALL OTHER COIL CONNECTIONS.
FINISHED ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZE TO COMPLETELY COVER OPENING (FOR EXPOSED CONDITIONS)
EXTERIOR WALL

04.03.07
Revisions:
1

06.06.07

BRANCH DUCT
END BEARING

3/8" SQUARE ROD VOLUME DAMPER WITH LOCKING TYPE INDICATOR QUADRANT AND SADDLE TO CLEAR INSULATION

Drawn By:

DH
Key Plan:

AUTOMATIC AIR VENT


CONNECTION (BOTH SIDES OF PUMPS) FOR 5 GALLON BYPASS FEEDER AS PROVIDED BY ARC WATER TREATMENT COMPANY OR APPROVED EQUAL P-7

SEE PLUMBING DRAWINGS FOR CONTINUATION

1/4 W ', 4" MIN. CLINCH COLLAR


W SUPPLY AIR FLOW MAIN DUCT

PRESSURE GAUGE (TYP.)


IN-LINE AIR SEPARATOR

BACKFLOW PREVENTER PIPE TO FLOOR DRAIN

PIPE SLEEVE DETAIL


NO SCALE

FLOW METER - CIRCUIT SENSOR SHUT OFF VALVE (TYP.)

45

SPIN COLLAR W/ VOLUME DAMPER (REFER TO SPIN-IN FITTING DETAIL)

PROVIDE ADJ. 90 26 GA. ELBOW WITH INSULATED FLEX COVER. SEAL JOINTS OF ELBOW

3"
TO SYSTEM FROM SYSTEM CS

P-6 CS

3"

3"
CR

SUPPLY AIR DIFFUSER CONNECTION DETAIL


NOT TO SCALE

LOW PRESSURE RECTANGULAR DUCT TAP WITH VOLUME DAMPER DETAIL


NO SCALE
THERMOMETER (TYP.) FLUSHING PORT (TYP.) P.T. PLUG (TYP.)

P/T PLUG TYP. STAINLESS STEEL BRAIDED HOSE W/ SWIVEL CONNECTORS - TYP.

MANUAL AIR VENT AT ALL HIGH POINTS-TYP. FLOW SWITCH


FS

1
ISOLATION VALVE TEMPERATURE SENSOR CWS / RFHWS FLOW METER TYP.
TO SYS TEM

FROM WELL FIELD TO WELL FIELD MAINS

ISOLATION VALVE - TYP.

1"

LEFRAK RESIDENCE
Sheet:

SYSTEM TEMPERATURE SENSOR TYP.

FLOW METER: CIRCUIT SETTER FOR SIZES 2" & SMALLER CIRCUIT SENSOR- 21/2" & UP

1/2" GAUGE VALVE CONNECTION - TYP. MANUAL AIR VENT

TEMPERATURE CONTROL VALVE TYP. CS


VIBRATION ISOLATORS TYP.

N.C.

HEAT PUMP

UNION TYP.

CWR / RFHWR

STRAINER TWO WAY AUTOMATIC TEMP. CONTROL VALVE 8 FT. MAX P.D. 4 FT. MIN P.D.

N.O. 3/4" HOSE END DRAIN VALVE

CONCRETE EQUIPMENT HOUSEKEEPING PAD

3/4" DRAIN VALVE AT ALL LOW POINTS TYP.

ISOLATION VALVE STRAINER (TYP.)


DIAPHRAGM PRESSURIZED EXPANSION TANK ET-3

TYPICAL FAN COIL UNIT CONNECTION DETAIL


NO SCALE

MECHANICAL DETAILS

CR

1/2" NORMALLY CLOSED BYPASS FOR FLUSHING

TO TEMPERATURE SENSOR

AIR FLOW

FLOOR

NOTE:
PIPING SCHEMATIC DIAGRAM
NO SCALE

PIPING CONNECTIONS AT WATER TO WATER HEAT PUMPS


NO SCALE

NOTE:

CONDENSER WATER SYSTEM SHALL BE 10% PROPYLENE GLYCOL.

1. HEATING WATER SUPPLY CONNECTION SHALL BE UPSTREAM OF AIR FLOW. 2. PROVIDE A THREE WAY CONTROL VALVE ON THE LAST FAN COIL UNIT IN EACH PIPING LOOP. 3. SEE "FAN COIL UNIT 6 THRU 10 CHILLED WATER COIL CONNECTION DETAIL" FOR PIPING REQUIREMENTS OF FAN COIL UNITS 6 THRU 10 CHILLED WATER COILS. THIS DETAIL DOES NOT APPLY TO THOSE COILS.

M1.1
COPYRIGHT C
2006

ASC JOB# 0631037

1101 BROOK VALLEY LANE MCLEAN, VIRGINIA 22101

INC

SUPPLY DUCT

FROM SYSTEM

TO SYSTEM