SYSTEM: 220 kV Switchyard Menouf I Over Head Transmission line

Equip. Name
Distance Relay Main I [ REL 531 ]

Description / Function
Distance zone settings

Manu.
ABB Z1 = 80 %

Setting Values Time

First Comm. date


12/2004

First Service date

Test /Check Period

Test Type
Secondary injection

Test Equip.
ISA

Main./ Test Steps

Remarks

Z2 = 120 %
Z3 = 200 % Z4 = 30 % Z1 (forward) X1pp = 9.8 ohm/phase R1 pp = 1.3 ohm/phase RF1 pp = 7.3 ohm/phase X1 pE= 9.8 ohm/phase R1 pE = 1.3 ohm/phase X0 pE = 32 ohm/phase R0 pE = 8.4 ohm/phase RF pE = 35.3 ohm/phase Z2 (forward) X1pp = 18.9 ohm/phase R1 pp = 2.33 ohm/phase RF1 pp = 8.33 ohm/phase X1 PE= 18.9 ohm/phase R1 pE = 2.33 ohm/phase X0 pE= 56 ohm/phase R0 PE = 14.7 ohm/phase RF PE = 36.33 ohm/phase Z3 (forward) X1pp = 33.8 ohm/phase R1 pp = 5.6 ohm/phase RF1 pp = 11.6 ohm/phase X1 pE= 33.8 ohm/phase R1 pE = 5.6 ohm/phase X0 pE = 85.5 ohm/phase R0 pE = 22.5 ohm/phase RF pE = 39.6 ohm/phase Z4 (backward) X1pp = 20 ohm/phase T4 pp= 2.5 sec T3 pE= 2.5 sec T3 pp= 0.9 sec T3 pE= 0.9 sec T2 pp= 0.45 sec T2 PE= 0.45 sec T1 pp= 0.0 sec T1 pE = 0.0 sec

SYSTEM: 220 kV Switchyard Menouf I Over Head Transmission line


1

Equip. Name
Continuo Distance Relay Main I [ REL 531 ]

Description / Function

Manu.

Setting Values Time

First Comm. date

First Service date

Test /Check Period

Test Type

Test Equip.

Main./ Test Steps

Remarks

R1 pp = 1.56 ohm/phase

RF1 pp = 7.6 ohm/phase X1 pE= 20 ohm/phase R1 pE = 1.56 ohm/phase X0 pE = 13 ohm/phase R0 pE = 3.5 ohm/phase RF pE = 36 ohm/phase Earth fault protection I = 0.3 IN 2.5 sec IN = nominal C.T secondary current

Equip. Name
Voltage transformer V.T.

Description / Function

Setting Manu.
220 / 0.1 3 3 200 VA

Values
KV

Time

First Comm. date

First Service date

Test /Check Period

Test Type

Test Equip.

Main./ Test Steps

Remarks

ABB

Current transformer C.T.

ABB

2000/1 A 30 VA 5P20

SYSTEM: 220 kV Switchyard Menouf I Over Head Transmission line


2

Equip. Name

Description / Function

Manu.

Setting Values Time

First Comm. date

First Service date

Test /Check Period

Test Type

Test Equip.

Main./ Test Steps

Remarks

Distance Relay Main II [ REl 316*4 ]

Distance zone settings

ABB

HV distance starting

12/2004

Secondary injection

ISA IN = nominal C.T secondary current

I starting = 0.6 IN Imin = 0.08 IN Xa = 51 ohm/phase Xb = -25.5 ohm/phase Ra =44.2 ohm/phase Rb = - 44.2 ohm/phase Rload = 28.9 ohm/phase Angle load = 45 Z1 (forward) X1 = 9.21 ohm/phase R1 = 1.23 ohm/phase RR1 = 6.68 ohm/phase RRE1= 32.1 ohm/phase Z2 (forward) X2= 17 ohm/phase R2 = 2.1 ohm/phase RR2 = 8.36 ohm/phase RRE2= 33.8 ohm/phase Z3 (forward) X3= 30.5 ohm/phase R3 = 5.32 ohm/phase RR3 = 10.8 ohm/phase RRE3= 36.2 ohm/phase Z(4 / OR) X(4 / OR) = 17 ohm/phase R(4 / OR) = 2.9 ohm/phase RR(4 / OR) = 8.36 ohm/phase RRE(4 / OR) = 33.8 ohm/phase Z (back) X(back) = - 2.88 ohm/phase R(back) = - 0.38 ohm/phase RR(back) = - 5.84 ohm/phase Delay= Def 2.5 sec 0.4 sec 0.90 sec 0.45 sec 0 sec

RRE(back)

= - 31.3 ohm/phase

SYSTEM: 220 kV Switchyard Menouf I Over Head Transmission line

Equip. Name

Description / Function

Setting Manu. Values Time

First Comm. date

First Service date

Test /Check Period

Test Type

Test Equip.

Main./ Test Steps

Remarks

Continue
Distance Relay Main II [ REl 316*4

Power swing blocking

OK

2 sec

12/2004

Secondar y injection

ISA IN = nominal C.T secondary current

Over current back-up protection Autoreclosure Synchro check

I oc = 0.6 IN OK Ok

2.5 sec