THREE TASKS:
TO MEASURE MAIN C.B. POLES AND AUXILIARY CONTACT INTERVENTION TIMES; TO MEASURE THE STATIC AND DYNAMIC MAIN CONTACT RESISTANCE; TO MEASURE ANALOG OR DIGITAL INPUTS AND TO CONVERT THEM INTO MOVEMENT, SPEED, ACCELERATION.
2.
3.
MAIN SENSE COIL DRIVERS #2 (4) I SOURCE CLOSED DETECT #6 (12, 18)
CBA1000 (2000)
HIGH V MEAS IN 1 (2) SYN IN/OUT
(ALMOST) NO POWER GENERATION ALL CIRCUITS HAVE TO BE ISOLATED TO AVOID INDUCTIONS SEQUENCE OF TESTS: MICRO DELAY MEASUREMENT AND RECORDING: 2 SLAVE MICRO METER AND RECORD COIL CURRENTS LOW VOLTAGE INPUTS MEASURE FOR TRAVEL MOVEMENT HIGH VOLTAGE INPUTS FOR ANY OTHER MEASUREMENT OPTIONAL THREE DIGITAL INPUTS FOR TRAVEL MEASUREMENTS (CBA2000 ONLY) SYNCHRONIZE UP TO 4 TEST SETS
CBA2000
2; 4 OPT 3 PHASES, 2 BREAKS OPT: 4, 6 BREAKS 2 GROUPS OF 2 EACH OPT: 4, 6 GROUPS
CBA1000
2; 4 OPT 3 PHASES, 2 BREAKS 2 GROUPS OF 2 EACH
AUX OUTPUT
ANALOG INPUTS
RELAY: C, NO, NC
10 IN ALL: 2 (4) COIL CURRENT; 1 RESISTANCE (5 V) 3 LOW V (10 V); 2 HIGH V (500 V) YES, 3 YES
NO
6 2 1 1 IN ALL: (4) COIL CURRENT; LOW V (5 V); HIGH V (500 V)
NO NO
COIL
PLANT
CLAMP
R
VMAX = 20 V (PRE-INS) I DC
OPTO COUPLER
OUT
PREINS
V SENSE
PLANT
V BATT = 24 V
CBA1000 (2000)
TWO INPUTS HAVE THE SAME COMMON CBA1000: THREE PHASES, TWO BREAKS CBA2000: THREE PHASES, 2 4 6 BREAKS
CONTACT
WET
IDC = 2 mA
OPTO COUPLER
BRIDGE
DRY
THRESH
I DC
OUT
IN
WET
PLANT
DRY
CBA1000 (2000)
TWO INPUTS HAVE THE SAME REFERENCE CBA1000: 2 GROUPS, 4 INPUTS CBA2000: 2, 4, 6 GROUPS
SAME CIRCUITS
A1 T OPEN
T CLOSE T OPEN
BOUNCES
BOUNCES
LAST TOUCH
FIRST TOUCH
PROBLEM: SQUEEZE AN HIGH CURRENT GENERATOR INTO THE SET WITHOUT A DRAMATIC INCRESE OF WEIGHT AND DIMENSIONS SOLUTION: ENERGY PROVIDED BY A DISCHARGING CAPACITOR
I LIMIT DC SUPPLY
L OF CABLE
V
3 ms
T IS INVERSELY PROPORTIONAL TO I: 30 ms @ 200 A DURING T WE MEASURE V, I AND COMPUTE R = V/I THE RESULT IS THE AVERAGE OF 300 MEASUREMENTS MINIMUM
OPEN
PROBLEM
CLOSE
OPEN
CONTACT: CLOSED
OPEN
NO SYNCHRONIZATION PROBLEM
CLOSE
CURRENT OUT
PURPOSES: TO MEASURE THE STROKE: WEAR TO MEASURE SPEED: PLAYS HOW TO DO IT: DEFINE WHERE AND HOW TO CONNECT THE TRANSDUCER PREPARE H/W FIXTURES TRANSDUCER TYPES: ANALOG: POTENTIOMETER (LINEAR, ROTATIVE) DIGITAL (CBA2000): ROTATIVE
ANALOG TRANSDUCER: IT IS AN HIGH ACCURACY POTENTIOMETER. THE CURSOR VOLTAGE IS PROPORTIONAL TO THE CURSOR POSITION CBA MEASURES THE CURSOR VOLTAGE AND CONVERTS IT INTO STROKE AND SPEED
+ V (CBA) +V MARGIN V CLOSED (OPEN) Vc
TRANSDUCER LENGTH, L
Vc = V * P / L
MARGIN
POSITION P
0
V OPEN (CLOSED)
ANALOG ROTATING TRANSDUCER: CONTINUOUS TURN THERE IS A GAP ACROSS THE SUPPLIES: V DROPS TO ZERO FOLLOW THE CALIBRATION PROCEDURE
+ V (CBA)
+V
355 360
ANGLE
4.
DIGITAL TRANSDUCER: CONTINUOUS ROTATION; NO GAPS TRAIN OF IMPULSES: ACCURACY = IMPULSES/TURN TWO TRAINS TO DETECT FORWARDS AND REVERSE MOVEMENTS RS488 STANDARD
A TRACE B TRACE
2.
CALIBRATION: CB STROKE KEY PARAMETERS ARE: a) THE CB STROKE; b) THE TRANSDUCER STROKE AT THE CONNECTION POINT; c) THE TOTAL TRANSDUCER LENGTH (ANALOG) OR THE IMPULSES PER TURN (DIGITAL) FROM THE ABOVE, THE TEST SET DISPLAYS THE ACTUAL CB STROKE
4.
DATUM POINTS IN THE RESULT TABLE IS REPORTED THE CONTACT SPEED THE SPEED CHANGES DURING THE MOVEMENT THE REPORTED SPEED IS COMPUTED BETWEEN TWO DATUM POINTS MANY DEFINITIONS: SEE THE MANUAL
2.
SLOW MOTION: WHAT IS IT? DURING ITS MOVEMENT THE MECHANISM HITS AGAINST SHOCK ABSORBERS HOW MUCH MORE STROKE IS AVAILABLE?
TOTAL STROKE
A EXTRA STROKE
A MARGIN OVERTRAVEL (O/C)
CB STROKE
B EXTRA STROKE
OVERTRAVEL (C/O) B MARGIN
THE CB HAS TO BE OPENED AND ISOLATED BEFORE CONNECTING IT TO CBA FRICTIONS DEVELOPED DURING THE TIME SLOW THE CB ON THE FIRST TRIP: THIS INFORMATION IS LOST
I CB Busbar with voltage I Clamp OPEN COIL COMMAND (I Clamp)
Circuits
CBA
500 V
d e v e l o p e d d e v e l o p e d
(500 V)
AUX 1
d e v e l p e d
d e v e l o p e d
d d u u r r
d u d r u i r
IF THE CB CLOSES ON COMPENSATION CAPACITORS, HUGE CURRENTS ARE DEVELOPED SOLUTION: SEPARATELY CLOSE THE THREE PHASES WHEN THE VOLTAGE IS AT ZERO
CT CB
I Clamp
VT
Circuits
500 V 1
(500 V 2)
AUX 1
CBA