SPECIFICATIONS SHEET

SHEET REV

OF

DATA SHEET NO. 1240-23 73 10/23 62 14- 1/2

PROJECT TITLE :MOL FIELD DEVELOPMENT SURFACE FACILITIES

AIR HANDLING UNITS (DX COIL)

PROJECT NO. : FND/1240 LOCATION : MAKORI UNIT (IPS) (SI) Nos m kW kW m /hr m3/hr C C C L / min C Nos. 3

DATA

(IPS)

(SI)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

IDENTIFICATION SYMBOL SPECIFICATIONS REFERENCE QUANTITY FND CALC. REF. NO.: ALTITUDE AMSL APPLICATION COOLING COIL DATA: TOTAL COOLING COIL LOAD SENSIBLE COIL LOAD SUPPLY AIR VOLUME MAKEUP AIR VOLUME ENTERING AIR, DRY BULB/WET BULB LEAVING AIR, DRY BULB/WET BULB DESIGN SUPPLY TEMPERATURE WATER FLOW RATE ENTERING WATER TEMP./LEAVING WATER TEMP. REFRIGERANT MINIMUM ROWS MAXIMUM FINS/INCH COATED COILS CONDENSOR TYPE CONDENSOR ENTERING TEMPERATURE (DB) HEATING COIL DATA: CAPACITY COIL AIR VOLUME ENTERING AIR, DRY BULB LEAVING AIR, DRY BULB WATER FLOW RATE ENTERING WATER TEMP./LEAVING WATER TEMP. STEAM FLOW RATE STEAM PRESSURE FAN DATA TYPE OF FAN TYPE OF FAN BLADE PULLEY SUPPLY AIR VOLUME EXTERNAL STATIC PRESSURE (NOTE-1) MOTOR POWER POWER SUPPLY FAN MOTOR VOLTAGE VARIATION AHU MOTOR VFD COMPATIBLE MECHANICAL PERFORMANCE OF CASING-EN 1886 (2007) MECHANICAL STRENGTH OF CASING (EN1886) CASING AIR LEAKAGE CASING AIR LEAKAGE (at 700 Pa Positive Pressure) (EN1886) FILTER BYPASS LEAKAGE (Maximum filter bypass leakage rate as % of nominal flow rate) (EN1886) kW V/Ph/Hz

Nos FT MBH MBH CFM CFM F F F USGPM F Nos. Nos/Inch -

ACR/AHU-01 & 02 CU-/01 & 02 23 73 10/23 62 14 2 (One Standby) 1939 591

796 748 26600 1,100 79.3/62.4 53.3 / 51.7 52.5 -

233 219 45193 1869 26.2/16.8 11.8/10.9 11.3

R-407C / R-410A / R-134A As Required 12 Yes -

108

42.2

MBH CFM F F USGPM F Lbs/hr Psig CFM Inch of WG

KW m3/hr C C L / min C Kg/hr Bars

CENTRIFUGAL FAN m3/hr Pascal kW V/Ph/Hz 26600 1.5 18.5 415/3/50 10% Yes <0.048 (D1) <0.00144 (L2) <0.0021 (L2) <4 (D1) <0.441 (L2) <0.631 (L2) Forward Curve Variable 45193 375

in/ft ft3/s.ft2) ft3/s.ft2) -

mm/m l/s.m-2 l/s.m-2 -

<1 (F8)

47 48 49 50 51 52 53 54 55 56

THERMAL TRANSMITTANCE (U) OF CASING (EN1886) THERMAL BRIDGING OF CASING (Thermal bridging factor kb) (EN1886)

Btu / ft2hF -

W / m2 K -

U<0.088 (T1)

U<0.5 (T1)

0.75 kb 1.0 (TB2)

CONSTRUCTION TYPE INSULATION THICKNESS HYGENIC MODEL (REFER SPECIFICATION NO. 23 73 10) MIXING BOX PANEL FILTER SECTION WITH FILTERS BAG FILTER SECTION WITH FILTERS HEPA FILTER SECTION WITH FILTERS Inch mm DOUBLE SKIN, HORIZONTAL, DRAW THROUGH 2 NO Yes G-4 F-6 NO 50

SPECIFICATIONS SHEET

SHEET REV

OF

DATA SHEET NO. 1240-23 73 10/23 62 14- 1/2

PROJECT TITLE :MOL FIELD DEVELOPMENT SURFACE FACILITIES

AIR HANDLING UNITS (DX COIL)

PROJECT NO. : FND/1240 LOCATION : MAKORI UNIT (IPS) (SI) (IPS) NO NO NO NO YES NO As per Manufacturer Yes Yes 2 (SI) DATA

57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114

RETURN AIR FAN EMPTY/ACCESS SECTION BYPASS SECTION ULTRAVIOLET & GERMICIDAL IRRADIATION(UVGI) LAMP WEATHER PROOF CONSTRUCTION & CANOPY SOUND ATTENUATOR MAXM. ALLOWABLE UNIT DIM. (L X W X H) PORT HOLES LIGHTS MAGNEHELLIC GAGES HEAT EXCHANGER -

NOTES: 2) FILTER PRESSURE DROP SHOULD BE BASED ON MEDIAN PRESSURE DROP OF FILTERS. 3) MOISTURE ELIMINATOR TO BE PROVIDED FOR COIL FACE VELOCITIES EXCEEDING 550 FPM. 4) AHU PANEL THICKNESS SHALL BE 50MM 5) LIGHT TO BE PROVIDED IN FAN SECTION, BAG FILTER SECTION. 6) HEAT PUMP MODEL REQUIRED 7) MAGNEHELLIC GAUGES TO BE PROVIDED ON BAG FILTERS SECTION. 8) FAN OUTLET VELOCITY SHALL BE LESS THAN 1800 fpm. 9) GLANDS TO BE PROVIDED FOR FAN MOTOR CABLE & DP SENSOR ACROSS FILTERS AND TEMPERATURE SENSOR ACROSS COILS. 10) CONDENSER OF AIR HANDLING UNIT TO BE PROVIDED WITH SPECIALLY ACRACLAD COATED CONDENSER & FANS

1) EXTERNAL STATIC PRESSURE DATA INCLUDES ONLY PRESSURE DROP EXTERNAL TO AHU. PRESSURE DROP ACROSS AHU, ALL FILTERS & COIL ARE NOT INCLUDED.

REVISION STATUS DATE CHECKED / SIGN. APPROVED BY

0 ISSUED FOR TENDER 20/03/2013 MUHAMMAD ASHRAF OSAMA QAZI

1 ISSUED FOR TENDER 30/03/2013 MUHAMMAD ASHRAF OSAMA QAZI

THE INFORMATION ON THIS DATA SHEET IS CONFIDENTIAL TO FAHIM, NANJI & DESOUZA (PVT.) LTD AND SHALL NOT BE DISCLOSED TO A THIRD PARTY WITHOUT PRIOR WRITTEN PERMISSION

SPECIFICATIONS SHEET

SHEET REV

OF

DATA SHEET NO. 1240-23 73 10/23 62 14- 1/1

PROJECT TITLE :MOL FIELD DEVELOPMENT SURFACE FACILITIES

AIR HANDLING UNITS (DX COIL)

PROJECT NO. : FND/1240 LOCATION : MAKORI DATA UNIT (IPS) Nos FT (SI) Nos m 1939 591 (IPS) (SI) ACR/AHU-03 & 04 CU/03 & 04 23 73 10/23 62 14 2 (One Standby)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

IDENTIFICATION SYMBOL SPECIFICATIONS REFERENCE QUANTITY FND CALC. REF. NO.: ALTITUDE AMSL APPLICATION COOLING COIL DATA: TOTAL COOLING COIL LOAD SENSIBLE COIL LOAD SUPPLY AIR VOLUME MAKEUP AIR VOLUME ENTERING AIR, DRY BULB/WET BULB LEAVING AIR, DRY BULB/WET BULB DESIGN SUPPLY TEMPERATURE WATER FLOW RATE ENTERING WATER TEMP./LEAVING WATER TEMP. REFRIGERANT MINIMUM ROWS MAXIMUM FINS/INCH COATED COILS CONDENSOR TYPE CONDENSOR ENTERING TEMPERATURE (DB) HEATING COIL DATA: CAPACITY COIL AIR VOLUME ENTERING AIR, DRY BULB LEAVING AIR, DRY BULB WATER FLOW RATE ENTERING WATER TEMP./LEAVING WATER TEMP. STEAM FLOW RATE STEAM PRESSURE FAN DATA TYPE OF FAN TYPE OF FAN BLADE PULLEY SUPPLY AIR VOLUME EXTERNAL STATIC PRESSURE (NOTE-1) MOTOR POWER POWER SUPPLY FAN MOTOR VOLTAGE VARIATION AHU MOTOR VFD COMPATIBLE MECHANICAL PERFORMANCE OF CASING-EN 1886 (2007) MECHANICAL STRENGTH OF CASING (EN1886) CASING AIR LEAKAGE CASING AIR LEAKAGE (at 700 Pa Positive Pressure) (EN1886) FILTER BYPASS LEAKAGE (Maximum filter bypass leakage rate as % of nominal flow rate) (EN1886) kW

MBH MBH CFM CFM F F F USGPM F Nos. Nos/Inch -

kW kW m3/hr m3/hr C C C L / min C Nos. -

356 331 13000 500 79.2/63.6 55.7/54.2 52.5

104 97 22087 850 26.2/17.5 13.2/12.3

11.3 R-407C / R-410A / R-134A As Required 12 Yes -

108

42.2

MBH CFM F F USGPM F Lbs/hr Psig CFM Inch of WG V/Ph/Hz

KW m3/hr C C L / min C Kg/hr Bars

CENTRIFUGAL FAN m3/hr Pascal kW V/Ph/Hz 13000 1.5 10 415/3/50 10% Yes <0.048 (D1) <0.00144 (L2) <0.0021 (L2) <4 (D1) <0.441 (L2) <0.631 (L2) Forward Curve Variable 22087 375

in/ft ft /s.ft2) ft3/s.ft2) 3

mm/m l/s.m-2 l/s.m-2 -

<1 (F8)

47 48 49 50 51 52 53 54 55 56

THERMAL TRANSMITTANCE (U) OF CASING (EN1886) THERMAL BRIDGING OF CASING (Thermal bridging factor kb) (EN1886) CONSTRUCTION TYPE INSULATION THICKNESS HYGENIC MODEL (REFER SPECIFICATION NO. 23 73 10) MIXING BOX PANEL FILTER SECTION WITH FILTERS BAG FILTER SECTION WITH FILTERS HEPA FILTER SECTION WITH FILTERS -

Btu / ft2hF -

W / m2 K -

U<0.088 (T1)

U<0.5 (T1)

0.75 kb 1.0 (TB2)

Inch -

mm -

DOUBLE SKIN, HORIZONTAL, DRAW THROUGH 2 NO Yes G-4 F-6 NO 50

SPECIFICATIONS SHEET

SHEET REV

OF

DATA SHEET NO. 1240-23 73 10/23 62 14- 1/1

PROJECT TITLE :MOL FIELD DEVELOPMENT SURFACE FACILITIES

AIR HANDLING UNITS (DX COIL)

PROJECT NO. : FND/1240 LOCATION : MAKORI DATA UNIT (IPS) (SI) (IPS) NO NO NO NO YES NO As per Manufacturer Yes Yes 2 (SI)

57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114

RETURN AIR FAN EMPTY/ACCESS SECTION BYPASS SECTION ULTRAVIOLET & GERMICIDAL IRRADIATION(UVGI) LAMP WEATHER PROOF CONSTRUCTION & CANOPY SOUND ATTENUATOR MAXM. ALLOWABLE UNIT DIM. (L X W X H) PORT HOLES LIGHTS MAGNEHELLIC GAGES HEAT EXCHANGER -

NOTES: 1) EXTERNAL STATIC PRESSURE DATA INCLUDES ONLY PRESSURE DROP EXTERNAL TO AHU. PRESSURE DROP ACROSS AHU, ALL FILTERS & COIL ARE NOT INCLUDED. 2) FILTER PRESSURE DROP SHOULD BE BASED ON MEDIAN PRESSURE DROP OF FILTERS. 3) MOISTURE ELIMINATOR TO BE PROVIDED FOR COIL FACE VELOCITIES EXCEEDING 550 FPM. 4) AHU PANEL THICKNESS SHALL BE 50MM 5) LIGHT TO BE PROVIDED IN FAN SECTION, BAG FILTER SECTION. 6) HEAT PUMP MODEL REQUIRED 7) MAGNEHELLIC GAUGES TO BE PROVIDED ON BAG FILTERS SECTION. 8) FAN OUTLET VELOCITY SHALL BE LESS THAN 1800 fpm. 9) GLANDS TO BE PROVIDED FOR FAN MOTOR CABLE & DP SENSOR ACROSS FILTERS AND TEMPERATURE SENSOR ACROSS COILS. 10) CONDENSER OF AIR HANDLING UNIT TO BE PROVIDED WITH SPECIALLY ACRACLAD COATED CONDENSER & FANS

REVISION STATUS DATE CHECKED / SIGN. APPROVED BY

0 ISSUED FOR TENDER 20/03/2013 MUHAMMAD ASHRAF OSAMA QAZI

1 ISSUED FOR TENDER 30/03/2013 MUHAMMAD ASHRAF OSAMA QAZI

THE INFORMATION ON THIS DATA SHEET IS CONFIDENTIAL TO FAHIM, NANJI & DESOUZA (PVT.) LTD AND SHALL NOT BE DISCLOSED TO A THIRD PARTY WITHOUT PRIOR WRITTEN PERMISSION