ov
ADANI
ADAN! POWER LumiITED
MUNDRA THERMAL POWER PROJECT,
ADANI POWER SEZ,
VILLAGE: TUNDA & SIRACHA,
TAL? MUNDRA, PIN:S70435 DISTIKUTGH, GUJARAT
Phone:028a5 226600-04
Fax:02835-266120
Ref: APL / FQA/Civil/ 0 dated: 12.02.2009
To,
The Gpneral Manager [Quality Assurance],
SEPCDIIl, C/o APL, Mundra
Sub: Revised Design Mixes
te 12 Juror e
In continuation to MoM,the mixes have been re-designed to take care for fines as to
obtain larger workability in terms of slump suitable for pouring of concrete by Pumps.
CCS at the age of 7 days and 28 days is compatible with the requirements hence these
mixes can be adopted .the details are as under:
Moreover liquid admixtures, enlisted below, are approved for the ongoing civil works of
Power Plant at Mundra and therefore same can be used as per the proportions
indicated in the mix designs , attached separately
1. Sikament 600 HP / 2 [A] being manufactured by M/s Sika India Pvt .Ltd.
2. Rheobuild 821 EJ being manufactured by M/s BASF Construction Chemicals
[India] Pvt. Ltd.
3. Conplast SP 430 MS being manufactured by M/s Fosroc Chemicals [India] Pvt
Ltd,
"eit
IK.P.Chakerwart]
Deputy General Manager,
Field Quality Assurance,
5 x 660 MW, Adani Power Limited,
Mundra. Gujarat State
CC to
VP / AVP / GM [Civil] APL Mundra. [By e-mail]
Del Quality Assrence Messures\Admicur aprovalRevised Ingredients ofcancrate Later writen to SEPCO IlLdoeDetails of ingredients
Mix M25
Cement [OPC , Grade 53]
Water [W/C Ratio=0.47]
Sand Zone II
10 mm Fine Aggregates
20 mm Coarse Aggregates
Liquid Admixture
Mix M30
Cement [OPC , Grade 53]
Water [W/C Ratio=0.49]
Sand Zone Il
10 mm Fine Aggregates
20 mm Coarse Aggregates
Liquid Admixture
Mix M35
Cement [OPC , Grade 53]
Water [W/C Ratio=0.46]
Sand Zone I!
10 mm Fine Aggregates
20 mm Coarse Aggregates
Liquid Admixture
340.00 Kgs.
160.00 Liters
760.00 Kgs.
456.00 Kgs.
684,00 Kgs.
1.20% by weight of cement
360.00 Kgs.
176.00 Liters
748.00 Kgs.
449.00 Kgs.
673.00 Kgs.
1.40% by weight of cement
438.00 Kgs.
200.50 Liters
687.00 Kgs.
449.00 Kgs.
673.00 Kgs.
1.20% by weight of cement
DAField Quality Assrance Messured\Admixture approvalRevied Ingrecins of conerete eter writen SEPCO IiLdoeShandong TIEJUN Electric Power Engineering Co., LTD
A Village: Tunda&Siracha, Taluka:Mundra,District;Kutch, Gujarat-370435,India.
Tel: 02838-26650 Fax: 02638-26150
Name of the item: India Mundra Project No. MDR/APL~STEPC-APL-L/LT-£ 9) 7
From:Shandong TIEJUN Electric Power
To:Adani Power Limited Engineering Co. LTD.
Kind Attn: K.P.Chakerwarti Name:Zhang Zenghai
Tel:9426600495 Tel:9909956650
Fax: Fax:02838-266150
Pages:1 Date:14-02-2009
‘Subject:Reply to your letter Ref.No.APLFQA/Civil/027 date:12.02.2009
Classification:Safetyo; Qualityo; Progresso; Othera
Specialty: Civila; TGo; Boilero; Electrica; 1&Co; Weldo;
Heat insulationa Other
Required finish time: Contract No.: APLI2 x 660/C/05/2008-50
Dr Sir:
This is reply to your letter Ref. No.APL/FQA/Civil/027--- dated 12.02.2009.
We have received your above letter and noted the content.
Our pointwise reply is as follows
The Mix Design we are using is fine to workability in terms of slump suitable for
pouring concrete by Pumps, and CCS is also enough to meet the requirement of
IS. You change Mix Design, it is unnecessary , so we kindly suggest that do not
change it. We will use the old one .
Thanks ow. re
| one oo
With regards ov get Army
4
Oa "E50
wore
Feedback of the APL: Signature:
SHERE chaae B poraph canner Rignate™S TY
J
The Happiness Project: Or, Why I Spent a Year Trying to Sing in the Morning, Clean My Closets, Fight Right, Read Aristotle, and Generally Have More Fun