DESCRIPTION 11KV 1250A 25KA VCB of horizontal isolation / draw out VCB fitted with manual/motor operated spring charging mechanism with 220V AC Motor, shunt trip coil of 24V DC, closing coil of 24V DC, Aux. contact 4NO+4NC mechanical on/Off indicator and push button, mechanical operation counter - 1 No. Current Transformers : The current transformers shall be single phase resin cast and suitable for system voltage of 11KV and of Ratio 125-100/5-5A, Core-1 Class 0.5, 15VA for metering, Core-2 class 5P10, 15VA for protection. 3Nos. Potential Transformers : The potential transformers shall be Single Phase resin cast suitable for system voltage 11kv and of ratio 11KV/3/110V/3 accuracy 1 100VA 3Nos. Metering 0 - 150A Digital Ammeter with ASS 1 set 0-11KV Digital Voltmeter with VSS 1 set Digital Multifunction Meter 1 No. Protection 3O/C + 1E/F relay 1 no. Master Trip relay 1 no. Auxiliary Relays for Transformer Protection - 2Nos CB On/Off/Trip/Spring Charge/Trip Circuit Healthy, and R,Y,B Indication Lamps 8nos. Hooter 1 No 8 Window Annunciator 1 no. Trip Circuit Healthy Push Button 1 no TNC Breaker Control Switch 1 no. 24V DC battery charger -1 No. MS sheet steel enclosure with paint shade 7035 suitable for outdoor installation with provision for connecting incoming and outgoing cable provision through bottom entry. MAKES: VACCUM CIRCUIT BREAKER : PROTECTION RELAYS : AMMETER/VOLTMETER : DIGITAL MULTIFUNCTION METER : ANNUNCIATOR, HOOTER : CTs (OUTDOOR) : CTs (INDOOR) : INDICATION LAMPS : PUSH BUTTONS : SELECTOR SWITCH :
2.
3.
ABB EASUN / AREVA AE / RISHAB CONZERV / ELMEASURE ALAN / JVS VAMET KALPA ESBEE (L&T) ESBEE (L&T) SALZER