SITIO :

EL VINCULO

I.- MEDICION DE RESISTIVIDAD DE SUELO

FECHA INSTRUMENTO METODO DATOS MEDIDOS: MEDICION 1 2 3 4 5 6 7 8 9 10 11 a 1 1 1 1 1 1 1 1 1 1 1

: 22/02/2006 : MEGABRAS MTD SERIE 20 KW : SISTEMA DE 4 ELECTRODOS, CONFIGURACION SCHLUMBERGER

n 1 2 4 6 8 10 12 15 18 23 28

na 1.0 2.0 4.0 6.0 8.0 10.0 12.0 15.0 18.0 23.0 28.0

L 0.6 0.8 4.5 6.5 8.5 10.5 12.5 15.5 18.5 23.5 28.5

Re [ohm] 18.86 5.44 3.42 0.46 0.15 0.09 0.05 0.03 0.02 0.015 0.01

Pa [ohm] 6.52 6.67 214.88 60.70 33.93 31.10 24.50 22.62 21.49 26.01 25.51

RESULTADOS DE MEDIDA CURVA PATRON CAPA 1 2 3 A -9 (0,5) ESPESOR [m] E1 = E2 = E3 = 0.8 5.0 10E+06 RESISTIVIDAD [ohm-m] P1 = P2 = P3 = 50 43.08 10E+06 43.08

190

170

150

130

110

90

70

50

30

10

0.1

1.0

SITIO EL VINCULO

10.0

100.0

MEMORIA CALCULO MALLA BT SITIO EL VINCULO

1.- CALCULO RESISTIVIDAD EQUIVALENTE DEL TERRENO, DE ACUERDO AL MODELO DE YAKOBS, DONDE:
r

eq (1k)

=
k

Fk

S
i=1

1 r

(Fi Fi-1)

DONDE:

Fi =

1-

vi ro

CON:

ro2 = r2 b2

r =

= RADIO EQUIVALENTE

vi2 =

0,5 * [

ui -

ui2 - 4q2ro2

ui(1k) = q2 + hi2 + ro2 ; q2 = 2r ( r + b ) hi(1k) = PROFUNDIDAD CAPA i

DATOS INICIALES SUPERFICIE DISPONIBLE [m2] PROF. ENTERRAMIENTO [m] RADIO CIRCULO EQUIV. [m] ro2 q2 4q2ro2 15.237 35.934 2190.105 S b r 49 0.6 3.949

LUEGO h1 = h2 = h3 = ENTONCES vo 2 v1 v2 2 v3 2
2

0.8 5.8 1.00E+07

h12 = 2 h2 = 2 h3 =

0.64 33.64 1.00E+14

u1 = u2 = u3 =

51.811 84.811 1.00E+14

= = = =

15.237 14.790 7.040 0.000

F1 = F2 = F3 =

0.171 0.733 1.000

0.02 0.02321024 0.0000001

CON ESTO LA RESISTIVIDAD EQUIVALENTE ES:

r eq

57.38

ohm-mt

2.- CALCULO DE LA RESISTENCIA DE LA MALLA BT SEGN METODO DE SCHWARZ CARACTERISTICAS MALLA PROPUESTA LADO MAYOR [m] LADO MENOR [m] PROFUNDIDAD DE ENTERRAMIENTO DIAMETRO CONDUCTOR [m] LARGO CONDUCTOR MALLA [m] N ELECTRODOS

A B b dc L N

8 8 0.8 0.011 70 8

SEGN SCHWARZ
R =

req
L

Ln 2 L bd

+ K1 L S

- K2

]
Y
K2 = 5,5 8b S +

DONDE
K1 = 1,43 - 2,3 b S - 0,044 A B

0,15 -

b S

A B

LUEGO K1 = 1.123 Y K2 = 4.621

ENTONCES LA RESISTENCIA DE LA MALLA ES: Rpt = 3.63 [ohm]

Rpt (tratamiento ericogel) =

2.17894905

3.- CALCULO DE CORTOCIRCUITO MONOFASICO CORTOCIRCUITO MONOFASICO:


Icc1f = 3* 3V (3R) 2 + (x1 + x2 + x0)2

(1)

DONDE, PARA SECUENCIA CERO:

x1 = x2 =

V 3 * Icc3f

x0 =

3V 3 * Icc1f

- x1 - x2

DONDE: R = Icc1f = Icc3f = V = ENTONCES: x1 = x2 = x0 = 25.403 25.403 63.509 3.63 200 300 13200 ohm [A] [A] [V]
RESISTENCIA MALLA TIERRA CORRIENTE CCTO MONOFASICO (POR EMPRESA ELECTRICA) CORRIENTE CCTO TRIFASICO (POR EMPRESA ELECTRICA) VOLTAJE DE LINEA (POR EMPRESA ELECTRICA)

REEMPLAZANDO EN (1) Icc1f = 199 [A]

LA CORRIENTE DE CORTOCIRCUITO REAL SERA Ig = Icc1f * FD * Fc DONDE FD = Fc = 1 1 FACTOR DE DECREMENTO PATA t = FACTOR DE CRECIMIENTO PARA t = 0,5 Seg 0,5 Seg

LUEGO: Ig = CON ESTO: 199 [A]

4.- DETERMINACION SECCION MINIMA CONDUCTOR MALLA DE ACUERDO A ECUACION DE ONDERDONKS:

I =

1 Log10 32,85 * t

1 +

Tm - Ta 234 + Ta

]
CORRIENTE CCTO REAL RMS TIEMPO DESPEJE T ADMISIBLE MAXIMA POR CONDUCTOR T AMBIENTE SECCION DEL CONDUCTOR EN CM

DONDE I t Tm Ta A = = = = = 199 0.5 1083 40 [A] [seg] C C CM

REEMPLAZANDO TENEMOS QUE A = A = A = 977 0.98 0.50 CM MCM [mm2] PERO 1 MCM = 0.5067 [mm2]

5.- CALCULO VALORES MAXIMOS DE POTENCIALES TOLERADOS


116 + 0,174*Cs*rg t 116 + 0,7*Cs*rg t

Vmp =

Vpp =

DONDE Vmp = Vpp = Cs =


Cs = 1 -

VOLTAJE CONTACTO VOLTAJE PASO FACTOR DE CORRECCION


a

1 (rs/rg) 2 bo + a

]
ESPESOR RECUBRIMIENTO RASISTIVIDAD 1 CAPA RESISTIVIDAD RECUBRIMIENTO TIEMPO DESPEJE FUSIBLE EQUIVALENCIA PIE A ESFERA DE RADIO a (GRAVILLA)

DONDE bo rs rg t a = = = = = 0.1 50 3000 0.5 0.106 [mt] [ohm-mt] [ohm-mt] [seg] [mt]

REEMPLAZANDO TENEMOS QUE Cs = 0.659

LUEGO: Vmp = Vpp = 651 2122 [V] [V]

6.- CALCULO POTENCIALES MALLA PROPUESTA


Vmp = Km * Ki * req *
Km * Ks * req * Ig L

Ig L

Vpp =

DONDE
Ki = 0,656 + 0,172*n

Km =

1 2

[ (
Ln

D2 + (D + 2b)2 16 b d 8Dd

b 4d

+ Kii Ln Kn

(2n-1)

Ks =

Kii =

1 + 1 + 1 (1 0,5(n-2)) 2b D+b D

1 (2 n)2/n

Kn =

1 + b b0

DONDE L = n = D = ho = REEMPLAZANDO Kii = Kn = Km = Ki = Ks = LUEGO Vmp = Vpp = 256 124 [V] [V] 0.526 1.341 0.712 2.204 0.344 70 9 4 1 [mt] [mt] [mt]
LARGO CONDUCTOR MALLA N CONDUCTORES LADO MENOR SEPARACION CONDUCTORES LADO MENOR

256 124

< <

651 2122

Elaborado: Ing. Hctor Ed. Graffe Cantillo

Revisado por: Ing. Favio Casas Ospin

DATOS BASE PARA EL CLCULO DE LA MALLA DE


Resistencia Objetivo menor a ......(W) Resistividad aparente del terreno (r) Corriente de falla monofsica a tierra en el secundario I (A) Corriente de falla monofsica a tierra en el primario I o (A) Tiempo de despeje de la falla t c (ms) Material a utilizar en la puesta a tierra, con temperatura ambiente de 40C Marque la casilla de verificacin si existe una capa superficial. Conductor a utilizar en la malla de puesta a tierra 2 Cuadrada Rectngular En forma de L Geometra de la malla
L a r g o

5 64.34

40 100 140

7.00 Resistividad 50 64 Area (mm2) 0.40


Largo (m)

Ancho (m)

L1 (m)

L1

L2 (m) L2 Lado de Cuadrcula (cm)

Ancho

TRUE

Marque la Nmero de varillas casilla si la PT Longitud de varilla tiene Varillas (cm) malla 80

Profundidad de enterramiento de la (cm)

CLCULO DE TENSIONES DE PASO Y CONTACTO M 1


1
Tensin de contacto tolerable Tensin de paso tolerable 340 430

CLCULO DE RESISTENCIA DE PUESTA A


Resistenica de Puesta a Tierra (W) 33 0.305 Maximo potencial de tierra GPR (V) Tensin de malla en caso de falla (V) Tensin de paso en caso de falla (V) El GPR es menor que la tensin de contacto tolerable? La tensin de malla en caso de falla es menor que la tensin de contacto tolerable? La tensin de paso en caso de falla es menor que la tensin de paso tolerable? RESISTENCIA DE MALLA DE Ohm 2.47 TIERRA CALCULADA La resistencia obtenida es menor a la resistencia objetivo? 1.000 1.00

4.11

CLCULO DE TENSIONES EN CASO DE #VALUE!

782 #VALUE! 88 Verifique la # #

OK!!! Su dis

Revisado por: Ing. Favio Casas Ospina

CLCULO DE LA MALLA DE PUESTA A TIERRA

Subestaciones de alta y extra alta tensin. 3 Subestaciones de media tensin en poste. Subestaciones de media tensin de uso interior.

1 Ver propiedades de los diferentes materiales FALSE 20


Calibre 2/0 AWG 8
Longitud Conductor Horizontal (m)

Espesor hs

(cm) 0

Dimetro (m) 0,0093

8 0 0 400 8 150

48 120 121

48

Longitud total varillas (m)


12

Longitud del permetro (m) 8 150


64

32

rea de la malla (m2) 64

ES DE PASO Y CONTACTO MXIMAS PERMITIDAS


340 430 Persona de 50 kg Persona de 70 kg

E RESISTENCIA DE PUESTA A TIERRA


4.11
1.09 1.00

1.342 DE TENSIONES EN CASO DE FALLA

782 #VALUE! 88 Verifique la tensin de malla!!! #VALUE! #VALUE!

OK!!! Su diseo ha sido exitoso

una placa de 1mts^2 Equivale a 63 barras de 5/8

2.4679954 Aplicando ericogel

1.09

1000.00

100.00

Series1 Expon. (Series1)

10.00

1.00
1 2 3 4 5 6 7 8 9 10 11

SITIO